10 SPRECON Basic Training T3 Modules
10 SPRECON Basic Training T3 Modules
2
Highlights
• Cost-effective, expandable and modular system
• Engineering and diagnostics with SPRECON-E Engineering Center
• Plug & Play for spare parts with mobile memory (microSD card)
• Easy handling through modular design
• Direct measurement for power / voltage
• Integrated communication GSM-GPRS Modem
• Webserver
• IPsec encryption directly by CPU
3
Application Areas
• Automation and telecontrol for
• Electric power supply
• Hydro-electric power plants
• Oil and gas pipelines
• Water / sewage systems
• Transportation,
traction power, tunnels
• etc.
4
Configuration
IEC60870-5-104
T3 T3
(stand alone)
T3
IEC60870-5-101
T3
T3 T3 T3 T3
IEC60870-5-101
IEC60870-5-101
IEC60870-5-101
T3
T3 T3 T3
T3 T3 T3
5
Design
• CPU, I/O modules and power supply module
(DIN-rail, 35 mm)
IEC 60870-5-101/104
IPsec
Webserver
T-Bus connector
6
Basic Modules
• CPU-module MC-33xx:
• Management of up to 8 SPRECON-E-T3 I/O modules
• IEC 61131-3 programming
• 512 KB non-volatile memory for user program
• Slot for microSD card
• 10 ms cycle time
• 2 x Ethernet LAN
• Time synchronisation via serial interface (GPS, DCF-77)
• 1 x serial service interface (RJ45, isolated)
• Connector for a control panel and alarm panels (max. 2 total)
• up to 2 x serial RS232 communication interface (isolated)
• up to 1 x serial RS485 communication interface (isolated)
• 2 binary outputs on the module
• 1 optional quad-band GSM/GPRS radio modem (MC-3340)
• LED status displays
• Online test
• SPRECON-E-C compatible
7
Basic Modules
• CPU-module MC-33xx variant:
MC-3310 MC-3320
MC-3310 MC-3320
RX X3 RX X3 RX X9
TX COM2 TX COM2 TX COM4
STATUS STATUS
ERROR ERROR
BO 01 BO 01
BO 02 BO 02
X6 RX X5 X6 RX X5
ACT/LK ACT/LK
LAN TX COM1 LAN TX COM1
X7 RX X2 X7 RX X2 RX X12
ACT/LK ACT/LK
LAN TX PANEL LAN TX PANEL TX COM3
T3 T3 T3 T3 T3 T3
MC-3310 1x 1x -- 2x 1x
MC-3320 1x 2x 1x 2x 1x
8
Basic Modules
• CPU-module MC-34xx:
• Power supply for up to 2 SPRECON-E-T3 modules
• IEC 61131-3 programming
• 512 KB non-volatile memory for user program
• Slot for microSD card
• 10 ms cycle time
• 2 x Ethernet LAN
• Time synchronisation via serial interface (GPS, DCF-77)
• 1 x serial service interface (RJ45, isolated)
• up to 1 x serial RS232 communication interface (isolated)
• up to 2 x serial RS485 communication interface (isolated)
• 2 binary outputs on the module
• LED status displays
• Online test
• SPRECON-E-C compatible
9
Basic Modules
• CPU-module MC-34xx variant:
MC-3410 MC-3450
MC-3410 MC-3450
RX X9
TX COM4
STATUS STATUS
ERROR ERROR
BO 01
BO 01
BO 02
BO 02
X6 RX X5
ACT/LK X6 RX X5
LAN TX COM1 ACT/LK
LAN TX COM1
X7 RX X12
ACT/LK X7 RX X12
LAN TX COM3 ACT/LK
LAN TX COM3
T3 T3 T3 T3 T3 T3 T3 T3
99 x 90 x 114.5 mm 99 x 90 x 114.5 mm
MC-3410 1x -- 1x 2x --
MC-3450 1x -- 2x 2x --
10
Digital Input/Output Modules
• Digital inputs DI-3011 DO-3005 DX-3011
BI 01
•
BI 01
•
BI 07
Cycle: 1 ms BI 08 BI 08
BO 01 BO 01
BO 02 BO 02
BO 03 BO 03
BO 04 BO 04
• Counter function
T3 T3 T3
• Command outputs
• 24-220 VDC, 230 VAC
• Grouping of 8x1 or 4x1 outputs
DO-3115 DI-3121
BI 01 BI 09
BI 02 BI 10
BI 03 BI 11
• Digital outputs
BI 04 BI 12
BI 05 BI 13
BI 06 BI 14
BI 07 BI 15
BI 08 BI 16
BO 01
T3 T3 T3
11
Analog Input/Output Modules
• Analog inputs
• 4 analog inputs
• 2 galvanically isolated groups AI-3100 AO-3000
AO 01
AO 02
AO 03
• Analog outputs AO 04
• 4 analog outputs in
T3 T3 T3
• 2 galvanically isolated groups
• Current loop outputs (0…20 mA)
12
Analog Input/Output Modules
• C/V measuring modules AX-3100
• Transducer inputs 3 VT/4 CT
• 1A/5A
AX-3100 AX-3110
•
ERROR
F 0 1 2 F 0 1 2
B C D E
B C D E
3 4 5 6
3 4 5 6
50/60 Hz 7 8 9 A
COM - Address
7 8 9 A
COM - Address
• Up to 2 modules at an MC-3xxx
• Power supply via system bus
T3 T3 T3
• Assembly DIN EN 60715 DIN rail (TH35) 99 x 22,5 x 114.5 mm
13
Analog Input/Output Modules
• SPRECON-E-T3 GPRS radio modem CI-3100
• Communication module CI-3100
• GSM frequencies 850/900/1800/1900 MHz
• Connector for external antenna
• SIM card in the front CI-3100
RX X3
•
TX MC
•
SIM
14
Analog Input/Output Modules
• SPRECON-E-T3 Power supply module
PS-3003/PS-3004 PS-3003
99 x 45 x 114.5 mm T3 T3
15
Analog Input/Output Modules
• SPRECON-E-T3 Power supply module
PS-3005/PS-3006 PS-3003
T3 T3
PS-3005
PWR
24VDC OK
Uin
110 – 220VDC
110 – 230VAC
T3 T3
16
Configuration
• Configuration, maintenance and service
with the SPRECON-E Progam Suite
17
SPRECON-E Engineering Center
• Program suite consists of
• SPRECON-E Engineering Center
• Administration center for all automation objects
• SPRECON-E Configurator
• System configuration
• SPRECON-E Designer
• Configuration tool
• SPRECON-E PLC Designer
• Add-on according to IEC 61131-3 standard
• SPRECON-V460 Editor
• Design and parameterisation of process visualisation
• SPRECON-E Service Program
• Commissioning and service tool
• SPRECON-E COMM-3
• Configuration and administration of
protection devices and disturbance data
18
SPRECON-E Designer
SPRECON-E Designer
Documentation
SQL database
server
Configuration data
Serial comm.
or Ethernet
File
Database (HDD)
19
© 2019 Sprecher Automation
Any liability regarding the correctness and completeness of any information Created by: VM
and/or specifications in the presentation is excluded. All rights are reserved 2019-03_SPRECON-E-T3_EN.ppt
to alter specifications, make modifications, or terminate models without prior
notice. The specifications of a model may vary from country to country.
www.sprecher-automation.com