SPRECON-E-T3

Compact RTUs and Automation Devices „Smart RTU“

© Sprecher Automation 2019


SPRECON-E-T3
• Multifunctional remote control and automation devices
for small and medium data volumes

• Applicable as station computer, RTU and stand-alone device


• According to IEC 61131-3
• Maximum flexibility through modular design
• Protocols IEC 60870-5-101/104
• Connection to individual components possible (e.g. IEC 60870-5-103, Modbus, SAT1703)
• Meet all standards for remote control of power utilities
• Smart Grid applications

2
Highlights
• Cost-effective, expandable and modular system
• Engineering and diagnostics with SPRECON-E Engineering Center
• Plug & Play for spare parts with mobile memory (microSD card)
• Easy handling through modular design
• Direct measurement for power / voltage
• Integrated communication GSM-GPRS Modem
• Webserver
• IPsec encryption directly by CPU

3
Application Areas
• Automation and telecontrol for
• Electric power supply
• Hydro-electric power plants
• Oil and gas pipelines
• Water / sewage systems
• Transportation,
traction power, tunnels
• etc.

4
Configuration

Configuration HMI workstation Service and maintenance

SPRECON-E-Designer SPRECON-V460 SPRECON-E Service Program

IEC60870-5-104

T3 T3

(stand alone)

IEC60870-5-101/104 Star coupler,


PSTN/GSM, ...

T3
IEC60870-5-101

T3

T3 T3 T3 T3
IEC60870-5-101

IEC60870-5-101

IEC60870-5-101
T3

T3 T3 T3

T3 T3 T3

5
Design
• CPU, I/O modules and power supply module
(DIN-rail, 35 mm)

IEC 60870-5-101/104

GSM / GPRS / UMTS

IPsec

Webserver

T-Bus connector

6
Basic Modules
• CPU-module MC-33xx:
• Management of up to 8 SPRECON-E-T3 I/O modules
• IEC 61131-3 programming
• 512 KB non-volatile memory for user program
• Slot for microSD card
• 10 ms cycle time
• 2 x Ethernet LAN
• Time synchronisation via serial interface (GPS, DCF-77)
• 1 x serial service interface (RJ45, isolated)
• Connector for a control panel and alarm panels (max. 2 total)
• up to 2 x serial RS232 communication interface (isolated)
• up to 1 x serial RS485 communication interface (isolated)
• 2 binary outputs on the module
• 1 optional quad-band GSM/GPRS radio modem (MC-3340)
• LED status displays
• Online test
• SPRECON-E-C compatible
7
Basic Modules
• CPU-module MC-33xx variant:
MC-3310 MC-3320

MC-3310 MC-3320
RX X3 RX X3 RX X9
TX COM2 TX COM2 TX COM4

STATUS STATUS
ERROR ERROR

BO 01 BO 01
BO 02 BO 02

X6 RX X5 X6 RX X5
ACT/LK ACT/LK
LAN TX COM1 LAN TX COM1

X7 RX X2 X7 RX X2 RX X12
ACT/LK ACT/LK
LAN TX PANEL LAN TX PANEL TX COM3

T3 T3 T3 T3 T3 T3

99 x 45 x 114.5 mm 99 x 67,5 x 114.5 mm

System communication interface CP / CCP / AP


Design
Connection Seriell RS2322 RS4855 Ethernet/LAN ----
RJ45 Male, DSUB 9-pole Female, DSUB 9-pole Rj45 RJ45

MC-3310 1x 1x -- 2x 1x
MC-3320 1x 2x 1x 2x 1x

8
Basic Modules
• CPU-module MC-34xx:
• Power supply for up to 2 SPRECON-E-T3 modules
• IEC 61131-3 programming
• 512 KB non-volatile memory for user program
• Slot for microSD card
• 10 ms cycle time
• 2 x Ethernet LAN
• Time synchronisation via serial interface (GPS, DCF-77)
• 1 x serial service interface (RJ45, isolated)
• up to 1 x serial RS232 communication interface (isolated)
• up to 2 x serial RS485 communication interface (isolated)
• 2 binary outputs on the module
• LED status displays
• Online test
• SPRECON-E-C compatible
9
Basic Modules
• CPU-module MC-34xx variant:
MC-3410 MC-3450

MC-3410 MC-3450
RX X9
TX COM4

STATUS STATUS
ERROR ERROR

BO 01
BO 01
BO 02
BO 02

X6 RX X5
ACT/LK X6 RX X5
LAN TX COM1 ACT/LK
LAN TX COM1
X7 RX X12
ACT/LK X7 RX X12
LAN TX COM3 ACT/LK
LAN TX COM3

T3 T3 T3 T3 T3 T3 T3 T3

99 x 90 x 114.5 mm 99 x 90 x 114.5 mm

System communication interface CP / CCP / AP


Design
Connection Seriell RS2322 RS4855 Ethernet/LAN ----
RJ45 Male, DSUB 9-pole Female, DSUB 9-pole Rj45 RJ45

MC-3410 1x -- 1x 2x --
MC-3450 1x -- 2x 2x --

10
Digital Input/Output Modules
• Digital inputs DI-3011 DO-3005 DX-3011

• 24 VDC, 48-60 VDC, 100 VDC, 220 VDC READY


ERROR
READY
ERROR
READY
ERROR

BI 01


BI 01

Grouping of 2x8 or 1x8 inputs BI 02


BI 03
BI 04
BI 05
BI 02
BI 03
BI 04
BI 05
BI 06 BI 06
BI 07


BI 07

Cycle: 1 ms BI 08 BI 08
BO 01 BO 01
BO 02 BO 02
BO 03 BO 03
BO 04 BO 04

• Counter function
T3 T3 T3

• Command outputs
• 24-220 VDC, 230 VAC
• Grouping of 8x1 or 4x1 outputs
DO-3115 DI-3121

• 1-pole, 1½-pole and 2-pole commands READY


ERROR
READY
ERROR

BI 01 BI 09
BI 02 BI 10
BI 03 BI 11

• Digital outputs
BI 04 BI 12
BI 05 BI 13
BI 06 BI 14
BI 07 BI 15
BI 08 BI 16
BO 01

• 24-220 VDC, 230 VAC


BO 02
BO 03
BO 04
BO 05
BO 06
BO 07

• Grouping of 2x8 or 1x8 relay outputs


BO 08

T3 T3 T3

11
Analog Input/Output Modules
• Analog inputs
• 4 analog inputs
• 2 galvanically isolated groups AI-3100 AO-3000

• Current loop inputs (±0…20 mA) and/or READY READY


ERROR ERROR

voltage loop inputs (±0…10 V)

AO 01
AO 02
AO 03

• Analog outputs AO 04

• 4 analog outputs in
T3 T3 T3
• 2 galvanically isolated groups
• Current loop outputs (0…20 mA)

12
Analog Input/Output Modules
• C/V measuring modules AX-3100
• Transducer inputs 3 VT/4 CT
• 1A/5A
AX-3100 AX-3110

• (Direct) Measurement 230 V AC/400 V AC


STATUS STATUS
ERROR


ERROR

Transducer inputs 110 V 1A


110V
5A
230V
1A
110V
5A
230V

F 0 1 2 F 0 1 2

B C D E
B C D E

3 4 5 6
3 4 5 6
50/60 Hz 7 8 9 A

COM - Address
7 8 9 A

COM - Address

• Up to 2 modules at an MC-3xxx
• Power supply via system bus
T3 T3 T3
• Assembly DIN EN 60715 DIN rail (TH35) 99 x 22,5 x 114.5 mm

• C/V measuring modules AX-3110 same as above, but


• Power supply for detached operation
• Up to 15 modules at an MC-3xxx interface
• Assembly DIN EN 60715 DIN rail (TH35), 99 x 45 x 114.5 mm

13
Analog Input/Output Modules
• SPRECON-E-T3 GPRS radio modem CI-3100
• Communication module CI-3100
• GSM frequencies 850/900/1800/1900 MHz
• Connector for external antenna
• SIM card in the front CI-3100
RX X3


TX MC

1 x RS232 system interface READY


NET


SIM

Communication protocols ONLINE

• IEC 60870-5-101/ -104 (PPT)


• Compatible to SPRECON-E-C
(in connection with PS-300X)
• Dimensions 99 x 45 x 114.5 mm, IP20 T3

• Assembly DIN EN 60715 DIN rail (TH35)

14
Analog Input/Output Modules
• SPRECON-E-T3 Power supply module
PS-3003/PS-3004 PS-3003

• Power supply module PS-3003


PWR
24VDC OK

• Input voltage range 24-60 VDC with -20 %/+30 % tolerance


• Max. output power 30 W
• Output for internal bus (equipping variant)
Uin
24 – 60VDC

• Output via plug-able terminals (equipping variant) T3 T3

• Output voltage 24 VDC +/-3%


• LED signalling
• Load regulation PS-3005

• Signal relay for supply failure (Live contact) variant PWR


24VDC OK

• Sustained short circuit-proof


• Bridging time at supply failure 10 ms at max. load
• Assembly DIN EN 60715 DIN rail (TH35) Uin
110 – 220VDC
110 – 230VAC

99 x 45 x 114.5 mm T3 T3

15
Analog Input/Output Modules
• SPRECON-E-T3 Power supply module
PS-3005/PS-3006 PS-3003

• Power supply module PS-3005


PWR
24VDC OK

• Same as PS-3003, but input voltage range


110-220 VDC/230 VAC with -20 %/+20 % tolerance
Uin
24 – 60VDC

T3 T3

PS-3005

PWR
24VDC OK

Uin
110 – 220VDC
110 – 230VAC

T3 T3

16
Configuration
• Configuration, maintenance and service
with the SPRECON-E Progam Suite

• IEC 61131-3 PLC functions via


graphical user interface

• Webbrowser for simple applications


• Display of parameters
• Diagnosis

17
SPRECON-E Engineering Center
• Program suite consists of
• SPRECON-E Engineering Center
• Administration center for all automation objects
• SPRECON-E Configurator
• System configuration
• SPRECON-E Designer
• Configuration tool
• SPRECON-E PLC Designer
• Add-on according to IEC 61131-3 standard
• SPRECON-V460 Editor
• Design and parameterisation of process visualisation
• SPRECON-E Service Program
• Commissioning and service tool
• SPRECON-E COMM-3
• Configuration and administration of
protection devices and disturbance data
18
SPRECON-E Designer
SPRECON-E Designer

Documentation

SQL database
server

Configuration data
Serial comm.
or Ethernet
File

Database (HDD)

19
© 2019 Sprecher Automation
Any liability regarding the correctness and completeness of any information Created by: VM
and/or specifications in the presentation is excluded. All rights are reserved 2019-03_SPRECON-E-T3_EN.ppt
to alter specifications, make modifications, or terminate models without prior
notice. The specifications of a model may vary from country to country.
www.sprecher-automation.com