User Manual EtherNet/IP Master / PROFIBUS Slave

Document code: MN67643_ENG Revision 1.000 Page 1 of 24


Industrial Electronic Devices

User Manual
Revision 1.000
English

EtherNet/IP Master / PROFIBUS Slave -


Converter
(Order Code: HD67643-A1)

for Website information:


http://www.adfweb.com/?Product=HD67643

for Price information:


http://www.adfweb.com/?Price=HD67643-A1
For others EtherNet/IP Master devices, see also the following links:

EtherNet/IP Master from/to …


Benefits and Main Features: www.adfweb.com?Product=HD67158 (SNMP Agent)
www.adfweb.com?Product=HD67643 (PROFIBUS Slave)
Triple electrical isolation www.adfweb.com?Product=HD67645 (CAN)
www.adfweb.com?Product=HD67646 (CANopen)
Two Ethernet ports
www.adfweb.com?Product=HD67647 (DeviceNet Slave)
Temperature range: -40°C/+85°C (-40°F/+185°F) www.adfweb.com?Product=HD67661 (PROFINET)
www.adfweb.com?Product=HD67665 (Modbus TCP Slave)
www.adfweb.com?Product=HD67667 (Serial)
www.adfweb.com?Product=HD67669 (Modbus Slave)
www.adfweb.com?Product=HD67689 (BACnet Slave)
www.adfweb.com?Product=HD67806 (KNX)
www.adfweb.com?Product=HD67955 (MQTT)

Do you have an your customer protocol?


See the following links:
www.adfweb.com?Product=HD67003

Do you need to choose a device? do you want help?


Ask it to the following link:
www.adfweb.com?Cmd=helpme
User Manual

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 2 of 24
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2
Updated
REVISION LIST 2
WARNING 2 Related to the product you own
TRADEMARKS 2
SECURITY ALERT 3 To obtain the most recently updated document, note the “document code”
EXAMPLE OF CONNECTION 4 that appears at the top right-hand corner of each page of this document.
CONNECTION SCHEME 5
CHARACTERISTICS 6 With this “Document Code” go to web page www.adfweb.com/download/
and search for the corresponding code on the page. Click on the proper
CONFIGURATION 6
“Document Code” and download the updates.
POWER SUPPLY 7
FUNCTION MODES 8
LEDS 9
PROFIBUS 10 REVISION LIST:
ETHERNET 11
USE OF COMPOSITOR SW67643 12 Revision Date Author Chapter Description
NEW PROJECT / OPEN PROJECT 13 1.000 13/03/2018 Ff All First release version
SOFTWARE OPTIONS 14
SET COMMUNICATION 16
ETHERNET/IP ACCESS 17
GSD FILE 18
UPDATE DEVICE 19
MECHANICAL DIMENSIONS 21 WARNING:
ORDERING INFORMATIONS 22
ACCESSORIES 22 ADFweb.com reserves the right to change information in this manual about
DISCLAIMER 23 our product without warning.
OTHER REGULATIONS AND STANDARDS 23 ADFweb.com is not responsible for any error this manual may contain.
WARRANTIES AND TECHNICAL SUPPORT 24
Pagina 2 di 24
RETURN POLICY 24
TRADEMARKS:

All trademarks mentioned in this document belong to their respective


owners.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 3 of 24
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device, legal and
safety regulation are required for each individual application. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e.
independent limit switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and
who have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state-of-the-art and is safe. The instruments can represent a potential hazard if they are inappropriately installed and
operated by untrained personnel. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is a danger for people that could lead to serious injury or
death and / or the possibility of damage.

CE CONFORMITY
The declaration is made by our company. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 4 of 24
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 5 of 24
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1: Connection scheme for HD67643-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 6 of 24
Industrial Electronic Devices

CHARACTERISTICS:

The HD67643-A1 is a EtherNet/IP Master / PROFIBUS slave Converter.

It allows the following characteristics:


Two-directional information between EtherNet/IP and PROFIBUS;
Electrical isolation between PROFIBUS – EtherNet/IP, Power Supply – EtherNet/IP, Power Supply – PROFIBUS;
Mountable on 35mm Rail DIN;
Wide power supply input range: 8…24V AC or 12…35V DC;
Wide temperature range: -40°C / 85°C [-40°F / +185°F].

CONFIGURATION:

You need Compositor SW67643 software on your PC in order to perform the following:
Define the parameter of the PROFIBUS;
Define the parameter of the EtherNet/IP;
Define the list of EtherNet/IP slaves connected to the converter;
Update the device.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 7 of 24
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered between a wide range of tensions. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
HD67643-A1 8V 24V 12V 35V

Consumption at 24V DC:

Device W/VA
HD67643-A1 4

Caution: Not reverse the polarity power

HD67643-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 8 of 24
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.

For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).

According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).

Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position to work even if the Ethernet cable is not inserted.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 9 of 24
Industrial Electronic Devices

LEDS:

The device has got six LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode


1: ON [supply voltage ] ON: Device powered ON: Device powered
(green) OFF: Device not powered OFF: Device not powered

2: PROFIBUS communication Blinks quickly: Boot state


Blinks when PROFIBUS communication is running
(green) Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
3: Device State (green) Blinks slowly (~1Hz)
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
4: Not used (green) OFF
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
5: Ethernet1 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
6: Ethernet2 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 10 of 24
Industrial Electronic Devices

PROFIBUS:

The PROFIBUS uses a 9-pin D-SUB connector. The pin assignment is defined like in the following figure.

Here some codes of cables:


Belden: p/n 183079A - Continuous Armor DataBus® ISA/SP-50 PROFIBUS Cable.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 11 of 24
Industrial Electronic Devices

ETHERNET:

The Ethernet connection must be made using Connector3 or Connector4 of HD67643-A1 with at least a Category 5E cable. The maximum
length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps. To
connect the device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is recommended
the use of a cross cable.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 12 of 24
Industrial Electronic Devices

USE OF COMPOSITOR SW67643:

To configure the Converter, use the available software that runs with Windows called SW67643. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).

When launching the SW67643, the window below appears (Fig. 2).

Note:
It is necessary to have installed .Net Framework 4.

Figure 2: Main window for SW67643

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 13 of 24
Industrial Electronic Devices

NEW CONFIGURATION / OPEN CONFIGURATION:

The “New Configuration” button creates the folder which contains the entire device’s configuration.

A device’s configuration can also be imported or exported:


To clone the configurations of a programmable “EtherNet/IP Master / PROFIBUS Slave
- Converter” in order to configure another device in the same manner, it is necessary
to maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the
button “Open Configuration”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 14 of 24
Industrial Electronic Devices

SOFTWARE OPTIONS:

By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.

In the section “Language” it is possible to change the language of the


software.

In the section “Connection Options”, it is possible to check if there are some


updatings of the software compositor in ADFweb.com website.
Checking the option “Check Software Update at Start of Program”, the
SW67643 check automatically if there are updatings when it is launched.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 15 of 24
Industrial Electronic Devices

In the section “Software Settings”, it is possible to enable/disable some


keyboard’s commands for an easier navigation inside the tables contained in
the different sections of the software.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 16 of 24
Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two buses,


PROFIBUS and EtherNet/IP.

By Pressing the “Set Communication” button from the main window for SW67643
(Fig. 2) the window “Set Communication” appears (Fig. 3).

The means of the fields for “PROFIBUS” are:


In the field “ID Device” the address of the PROFIBUS side is defined;
In the field “Baudrate” the data rate of the PROFIBUS side is defined (fixed to
“Auto Baudrate”);
In the field “Number Byte IN” the number of Input bytes of PROFIBUS is
defined (at maximum it is possible to use 244 byte);
In the field “Number Byte OUT” the number of Output bytes of PROFIBUS is
defined (at maximum it is possible to use 244 byte).

The means of the fields for “EtherNet/IP Master” are:


In the fields “IP ADDRESS” the IP address for EtherNet/IP side of the converter
is defined;
In the fields “SUBNET Mask” the SubNet Mask for EtherNet/IP side of the
converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature
can be enabled or disabled pressing the Check Box field. This feature is used for
going out of the net;
In the field “Port” the port used for EtherNet/IP communication is defined. The
port has a fixed value of 44818.

Figure 3: “Set Communication” window


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 17 of 24
Industrial Electronic Devices

ETHERNET/IP ACCESS:

By Pressing the “EtherNet/IP Access” button from the main window for SW67643 (Fig. 2) the window “Set EtherNet/IP Slaves Access”
appears (Fig. 4).
This section is used to define the list of the EtherNet/IP slaves to read/write with the PROFIBUS Master.

Figure 4: “Set EtherNet/IP Slaves Access” window

The means of the fields are:


If the field “Enable” is checked, the polling to the EtherNet/IP slave is enabled;
In the field “IP Address” the IP Address of the EtherNet/IP slave is defined;
In the field “Start Input” the starting Input byte of the EtherNet/IP slave to map on PROFIBUS side is defined;
In the field “Num Input” the number of consecutive Input byte to map on PROFIBUS side is defined;
In the field “Start Output” the starting Output byte of the EtherNet/IP slave to write from PROFIBUS side is defined;
In the field “Num Output” the number of consecutive Output byte to write from PROFIBUS side is defined;
In the field “Time Poll” the polling time in ms is defined;
In the field “Instance T > O” the instance of the assembly for the Target to Originator data direction is defined;
In the field “Conn. Point T > O” the connection point of the assembly for the Target to Originator data direction is defined;
In the field “Instance O > T” the instance of the assembly for the Originator to Target data direction is defined;
In the field “Conn. Point O > T” the connection point of the assembly for the Originator to Target data direction is defined;
In the field “Mnemonic” a brief description is defined.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 18 of 24
Industrial Electronic Devices

GSD FILE:

By pressing the “PROFIBUS GSD” button it is possible to save the GSD file for the PROFIBUS side.
With this feature you can save the configuration of the gateway of the PROFIBUS side.

Note:
When you import the .gsd file on your Master PROFIBUS you have to add all the modules that are present inside it in the correct
order.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 19 of 24
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the “Update Device” button, it is possible to load the created


Configuration into the device; and also the Firmware, if necessary. This by using the
Ethernet port.

If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.

If you know the actual IP address of the device, you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter; Figure 5: “Update device” windows
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.

At this point the configuration/firmware on the device is correctly updated.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 20 of 24
Industrial Electronic Devices

Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67643 device.

Warning:
If Fig. 6 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
If you are using the program inside a Virtual Machine, try to use in the main

Operating System;
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you
have to cancel the ARP table every time you connect a new device on Ethernet. For
do this you have to launch the "Command Prompt" and write the command "arp -
d". Pay attention that with Windows Vista, Seven, 8, 10 you have to launch the
"Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
Figure 6: “Error” window

Warning:
In the case of HD67643 you have to use the software “SW67643”: www.adfweb.com\download\filefold\SW67643.zip.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 21 of 24
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 7: Mechanical dimensions scheme for HD67643-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 22 of 24
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:


HD67643 – A 1

Connectors Type
1: Removable 5mm Screw Terminal

Enclosure Type
A: 1M, 35mm DIN Rail mounting

Device Family
HD67643 Ethernet/IP Master / PROFIBUS Slave - Converter

Order Code: HD67643-A1 - Ethernet/IP Master / PROFIBUS Slave - Converter

ACCESSORIES:

Order Code: AC34011 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V DC


Order Code: AC34012 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 24 V DC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 23 of 24
Industrial Electronic Devices

DISCLAIMER:

All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS:

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual EtherNet/IP Master / PROFIBUS Slave
Document code: MN67643_ENG Revision 1.000 Page 24 of 24
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).

If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.

ADFweb.com S.r.l.
Via Strada Nuova, 17
IT-31010 Mareno di Piave
TREVISO (Italy)
Phone +39.0438.30.91.31
Fax +39.0438.49.20.99
www.adfweb.com

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31