Analogue Addressable Manual Call Point

HCP-E
Features
 Fast response

 Status LED

 Non-frangible element fitted as


standard (conforms to EN54)

 Addressed with TCH-B100 Hand Held


Programmer

 Surface or flush mounting

 Different colours available

 LPCB Approved to EN54

Description
Model HCP-E is a Manual Call Point, which is fully compatible with Hochiki’s ESP analogue
addressable protocol.

The HCP-E incorporates a red LED mounted on the front cover, which can be selected as
pulsing/non-pulsing*1 for communications polling and is continuously lit when the HCP-E is
operated. The unit is operated by pressing the EN54 compliant non-frangible (plastic)
element and, once operated, produces a high level ESP interrupt, allowing the control panel
to respond very quickly. A built in test function initiated by the control panel ensures the
integrity of the device at all times and the device can be tested by insertion of a test key in
the underside of the unit. Two terminal blocks are provided for easy connection to the loop
wiring.

The unit is addressed using the TCH-B100 Hand Held Programmer for quick and reliable
addressing and the unit can also be flush mounted if required. An optional glass element is
also available.

Specification
Ordering Code HCP-E
Back Box Ordering Code SR
Operating Voltage 17 - 41Vd.c.
Low Power Mode (typ) 90μA
Quiescent Current (typ) 220μA
Alarm Current (typ) 5.0mA
Transmission Method Digital Communication Using ESP
Operating Temperature Range -10°C to + 50°C
Storage Temperature Range -30°C to + 60°C
Maximum Humidity 95%RH - Non Condensing (at 40°C)
Ingress Protection Rating IP24
Colour / Case Material Red / Modified Polyphenylene Oxide
(Flush Unit) 110 / W89 x H93 x D27.5
Weight (g) / Dimensions (mm)
(With Surface Mount Back Box) 161 / W89 x H93 x D59.5
Approval LPCB EN 54-11:2001
*1
Fire alarm control panel compatibility is required for this feature.