Magnehelic Gauge Calibration
by Saurabh Vaidya
This article cover calibration of Magnehelic Gauge (Differential Pressure Gauge) using a Digital
Manometer.
Magnehelic Gauge or Differential Pressure Gauge has two ports – High and Low.
As name suggest Differential Pressure Gauge i.e. its measure Pressure difference between High port and
Low port.
Generally, units of Differential pressure Gauge are mmWC, Pascal, Mbar, Inch WC, PSI, mmHg
High Port is also called as Positive port and Low port is called as Negative port.
How to calculate differential pressure?
Pressure at high port is 100 Pascal and Pressure at low port is 75 Pascal.
Differential Pressure indicated by Magnehelic Gauge or Differential Pressure Gauge is 100-75= 25 Pascal,
Differential Pressure= High Port – Low Port
If pressure at Low Port is higher than Low Port, than indicator will show Negative readings.
Table of Contents
Magnehelic Gauge Calibration
Up-Cycle Calibration
Down-Cycle Calibration
Magnehelic Gauge Calibration
Magnehelic Gauge Calibration
Analog Magnehelic Gauge should be in Vertical position.
Generally, Magnehelic Gauge is installed above the door, input ports with a hose are located at the back
and front of the gauge. So opening the door will equalize the ambient pressure and the Magnehelic
gauge will turn back to zero (as both rooms are at equal pressure, High port – Low Port = 0)
Connect the pneumatic pump on the High Port of the Magnehelic Gauge. Leave the Low Port open to
ambient, in this way, the differential pressure gauge functions as a normal pressure gauge.
You can also connect Low Port to know Pressure and find the difference between High and low port.
The calibration Procedure from this step is the same as the Pressure Gauge. I.e. Preloading, UP Cycle,
Down Cycle.
Equally distribute calibration points into 5 points (0%, 25%, 50 %, 75% and 100%)
Pre Loading – Increase Pressure up to full scale & decrease it to zero of UUC, to make pointer movement
free.
We should wait at least 30 seconds to note the readings of Magnehelic Gauge. The waiting time for the
upper limit of the measuring range is 2 minutes.
Up-Cycle is measured from Minimum pressure range to Maximum Pressure Range
Down-Cycle is measured from Maximum pressure range to Minimum Pressure Range
Up-Cycle Calibration
Increase Pressure by operating the pump to set the calibration point on the UUC gauge.
When pointer of UUC Gauge reach first calibration point note down both UUC & standard reading. Wait
for 30 seconds to note down reading. Wait for 2 Minutes for upper limit of measuring range.
Slowly increase the pressure to set next set point .Write down reading Standard reading & UUC reading.
Repeat this procedure for remaining calibration points.
This completes Up cycle of calibration of Magnehelic Gauge
Down-Cycle Calibration
For Down Cycle, Last calibration point of Up Cycle is first point of Down Cycle.
Slowly decrease the pressure to set the next set point. Write down reading Standard reading & UUC
reading. Wait for 30 seconds to note down reading. Wait for 2 Minutes for the upper limit of the
measuring range.
Repeat this procedure for remaining calibration points.
This completes the Down Cycle of calibration of Magnehelic Gauge
If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical,
PLC, and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
History of Measurement
Pressure Gauge Calibration
Selection of Master Instrument
Importance of Unit Measurement
Reliability Centered Maintenance
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
Enter your name here...
Enter your email here...
We promise not to spam you. You can unsubscribe at any time.
CategoriesCalibration, Pressure Measurement
Controlling of Tank Level Using Proportional Controller in PLC
What are High-Speed Inputs in PLC?
Recommended Articles
Important Terms in Calibration
Prover Tank Calibration and Mass Flow Meter Verification Procedure
Control Valve Stroke Test Procedure
Fieldbus Transmitters Calibration and Ranging
What is Field Transmitter Damping ?
Closed tank DP Level Transmitter with cleaning leg Calibration
Instrument Maintenance and Calibration System
Importance of Unit Measurement
Turbidity Sensor Calibration Procedure
What is Sensor Trim and Output Trim in Smart Transmitter?
Leave a Comment
Comment
Name
Name *
Email
Email *
Website
Website
Subscribe to our newsletter
Play Video
PLC Basic Questions and Answers - Instrumentation Tools
Categories
Categories
Select Category
Play Video
What is a Calibrator? | Instrument Calibrator | Industrial Instrumentation
Recent Comments
Tyler CV on 15 Loop Diagram Questions
Harish Ramachandran on Instrument Junction Box Specification
Labadi ayoub on Thermocouple Calculations
T on Transformer Tap Changing Working Principle
KEVIN on Standard 4 to 20 mA Conversion Formula
muskan ali on Pros and Cons of Online Courses
jeff on DeMorgan’s Theorems using Ladder Diagram
More Articles
What is Sensor Trim and Output Trim in Smart Transmitter?
Load Cell Healthiness Checks
Temperature Standards
Functional Testing of Control Valve Positioners
Instrument Maintenance and Calibration System
What is Reliability Centered Maintenance? (RCM)
Step by Step Guide for Gas Flow Meter Calibration
How to do calibration checks of vibration Probe, extension cable and vibration monitor
Instrument Errors – Zero, Span, Linearity
Smart Transmitter Calibration Tutorial Part 1
2023 © Reproduction without explicit permission is prohibited. - PLC SCADA Courses - Engineers
Community
We and our partners share information on your use of this website to help improve your experience.
Do not sell my info:
Okay