Service Manual: Screw Compressor
Service Manual: Screw Compressor
Screw compressor –
Refrigeration dryer – Combination
Model: AIRTOWER 26 / 10 bar
GL-Nr.: 1_8840_20290-00 06
Table of contents:
Part No.:
Serial No.:
Manufacturer:
B
0 bar/psig!
1
SERVICE MANUAL E
Screw Compressor
Model: SK 26 / 10 bar
GL---Nr.: 1_9764_50261---00 02
Manufacturer:
3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
3.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
3.2 Incorrect Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
3.3 Compressed Air Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
3.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
3.5 Accompanying Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 10
4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 11
4.1 Transport Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 11
4.2 Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 11
4.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 12
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 19
6.1 Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 19
6.2 Connection of the Compressed Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 20
6.3 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 20
i
Table of Contents
Chapter --- Page
8 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 28
8.1 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 28
8.2 SIGMA controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 28
8.2.1 Emergency Stop Pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 28
8.2.2 Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 29
8.2.3 Light emitting diodes and plain text display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 29
8.3 Compressor Package ON/OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 30
8.4 Acknowledgement of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 30
8.5 Acknowledgement of Service Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 31
8.6 Faults: Possible cause --- Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 32
8.6.1 Working temperature too high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 32
8.6.2 Motor overload protection relay trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 32
8.6.3 Compressor runs but does not reach pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 33
8.6.4 Oil running out of air filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 33
8.6.5 Too frequent switching between load and idle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 34
8.6.6 Pressure relief valve blowing off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 34
8.6.7 Oil in the package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 34
8.6.8 Cooling fluid consumption too high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 34
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 36
9.1 Observe the following during all maintenance and servicing. . . . . . . . . . . . . . . . 9 --- 36
9.2 Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 37
9.3 Opening and Closing the Compressor Package . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 38
9.4 Checking the Tension of the V---belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 39
9.5 Changing the V belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 39
9.6 Cleaning or Renewing the Filter Mat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 40
9.7 Cleaning or Renewing the Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 40
9.8 Servicing the Electric Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 41
9.9 Checking the Pressure Relief Valve on the Oil Separator Tank . . . . . . . . . . . . . . 9 --- 41
9.10 Venting the Compressor Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 42
9.11 Oil Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 43
9.11.1 Removal and replacement of the oil filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 43
9.12 Topping up the Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 44
9.13 Cleaning the Oil Cooler and Air Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 46
ii
Table of Contents
Chapter --- Page
11 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 56
11.1 Electrical Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 56
11.2 Spare Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 73
iii
Technical Specification
1 Technical Specification
Drawings:
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . T7471.05
P & I flow diagram . . . . . . . . . . . . . . . . . . . FSK26STL---00023.00
(Pipework and instrument flow diagram)
Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . SSK26---01027.01
1.3 Motor
Drive motor:
Rated power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 kW
Rated speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3600 min ---1
Protection class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 54
1 --- 1
Technical Specification
1 --- 2
Technical Specification
The duty cycle and ambient conditions are important criteria for the number and length of
the change intervals.
A sticker showing the type of oil filled is to be found near the oil separator filling port.
1 --- 3
Technical Specification
Synthetic cooling fluids can attack polycarbonate oil trays. For this
reason, we recommend metal oil trays.
Certain plastic parts in the compressed air supply may not be resistant
to synthetic cooling fluid.
When changing the type of cooling fluid, ensure that the fluid circulation system of the
compressor package is completely drained before filling with the new fluid. As far as poss-
ible, remove any deposits in the cooling system.
It is possible that the separator cartridge will have to be changed because of existing cool-
ing fluid deposits that detach themselves after changing the type of cooling fluid. This
one---off, additional requirement is caused by the cleaning effect of the new cooling fluid.
1 --- 4
Technical Specification
1 --- 5
Safety
2 Safety Regulations
This manual should be read and the instructions it contains followed before initial start ---up
and before carrying out maintenance work.
Beware of rotating parts. Do not touch rotating parts as this can cause
pinching/injury.
2 --- 6
Safety
Before work is carried out on electrical systems, carry out the follow-
ing measures in the sequence shown:
The following actions must be carried out in the order given before
working on any pressurised parts or enclosures (e.g. pipes, vessels,
valves).
The relevant statutory regulations must be observed during installation, operation, mainten-
ance and repair of the compressor package.
These are, for example, nationally applied European directives and / or valid national laws,
safety and accident prevention regulations.
These instructions must also be observed:
" Allow no open flames and flying sparks at the place of installation.
" Ensure that sparks or high temperatures cannot cause fire or explosion if welding is
carried out on or near the compressor.
" Ensure that the compressor unit can breathe clean intake air that contains no damag-
ing components.
" Do not allow the maximum ambient temperature to be exceeded (see chapter 1.6),
otherwise special measures must be agreed between the manufacturer and the cus-
tomer.
" Carry out oil changes according to the service manual.
" Use only oils recommended by the manufacturer.
" Do not mix cooling oils of different types.
" The operating temperature stipulated must be kept to and checked constantly to avoid
condensate in the oil circulation.
2 --- 7
Safety
" If maintenance work is carried out on any part of the oil circulation system, top up the
oil in the oil separator tank to the maximum level afterwards, run the compressor for a
short period and keep it under constant observation. Check the oil level again and top
up with oil to replace the oil taken up by the piping and the cooling system.
" Use the filter cartridge of the oil separator tank only as long as the pressure drop
across the filter is less than the 1 bar specified. Check constantly.
" This machine is not explosion ---proof.
It may not be operated in areas in which specific requirements with regard to ex-
plosion protection are applied.
These are, for example, the requirements for “specified use in hazardous explosive
environments” according to the 94/9/EU ATEX Directive.
2 --- 8
Safety
2 --- 9
General
3 General
The service manual must always be available for use at the location of
the compressor package.
The right is reserved to make technical changes and improvements to equipment which
may then result in discrepencies in the details of that equipment contained in this manual.
Attention! The equipment may only be used or serviced by persons who are au-
thorised and trained.
Attention! Inlet air may not contain any explosive or chemically unstable gas or
vapour.
3.4 Copyright
All rights reserved.
No part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without prior permission in
writing from KAESER COMPRESSORS.
3 --- 10
Transport
4 Transport
min. 1000 mm
Attention! Do not exert any side forces on the compressor package when trans-
porting with lifting equipment!
4.2 Packaging
Always observe the instructions in chapter 4.3 when packaging the machine for storage.
Use packaging suitable for the intended route if the machine is to be transported further by
the customer.
Overland
The machine should be protected from mechanical damage by a sturdy crate and from
moisture by plastic sheeting.
By sea or air
Special packaging instructions can be obtained from KAESER.
4 --- 11
Transport
4.3 Storage
If the equipment is to stand idle for a long period the prescribed measures must be taken
to avoid damage.
If any measures can not be taken, advice should be sought from the authorised KAESER
Service depot.
Attention! Basically, the equipment should be stored in a dry, frost-- free room.
Protect against ingress of moisture or formation of condensation.
See chapter 7.8 for instructions on start-- up.
Attention! Starting up the equipment without a full inspection can lead to dam-
age.
$ Have the the start ---up carried out by an authorised KAESER service technician.
4 --- 12
Construction and Operation
5 Technical Description
1 2 3 4 5
1 Drive shaft 4 Male rotor
2 Oil injection 5 Female rotor
3 Discharge port 6 Air inlet port
5 --- 13
Construction and Operation
5 --- 14
Construction and Operation
5 --- 15
Construction and Operation
p
max
Pressure
p
min
1 2 3 4 5
Full load t1 t2
Motor power
Idle
Standstill
Time
In DUAL Control mode (combined idle and start ---stop) the compressor normally runs at
full -- load, idle or standstill.
The controller regulates the compressor package between load and idle.
If the compressor package runs in idle for longer than the preset period (1) to (2), for
example t1 = 6 min, the drive motor is stopped completely (2). When the lower switching
point p min (3) is reached the compressor package is automatically started again. Pressure
rises to the upper switching point p max (4), and the compressor package switches to idle. If
the pressure falls again to, for example, p min (5) within a shorter period (4) to (5), then the
compressor is automatically switched from idle to load.
The idle period is dependent on the maximum motor starting frequency.
5 --- 16
Construction and Operation
p
max
Pressure
pmin
Full load
Motor power
Idle
Standstill
1 2 1 3 1 4 1 2 1 4 5 1
Time
tp rise
tp decay
Running period
Idle/
standstill period
Run ---on period
tp rise pressure rise time (the time during which the air main pressure rises
from the lower to the upper switching point)
tp decay pressure decay time (the time during which the air main pressure decays
from the upper to the lower switching point)
Functional description
Two fixed periods --- the running period and idle/standstill period --- are taken as the crit-
erium for selection of the operating mode of the compressor package when the air main
pressure reaches the upper switching point. These two periods are set according to the
maximum permissible starting frequency of the drive motor.
The running period starts every time the compressor package is switched on. It lasts as
long as the drive motor runs and stops when the compressor package switches to stand-
still.
The idle/standstill period starts every time the operating mode changes from full load to
idle. It runs during idle and also when the compressor package is switched to standstill
after the idle period. It stops when the compressor package switches to full load.
Every switching off point is delayed by the run ---on period, during which time the com-
pressor package vents.
The following switching cycles are possible:
# If the air main pressure decays to the lower switching point, the compressor package
switches to full load (1) irrespective of its previous operating mode. If the drive motor
was at a standstill the opening of the inlet valve is delayed to allow an unloaded com-
pressor package start.
5 --- 17
Construction and Operation
# If the air main pressure rises to the upper switching point and the running period has
already expired, the compressor package is switched off after the run ---on period has
expired (2).
# If the air main pressure rises to the upper switching point before the running period
has expired then the pressure decay time of the previous switching cycle is taken as
the criterium for the selection of the operating mode:
-- If the pressure decay time tp decay was longer than the period set for the idle/standstill
period, the compressor package is switched to standstill after the run ---on period has
expired (3).
-- If the pressure decay time tp decay was shorter than the period set for the idle / stand-
still period, the idle mode is selected (4), that is, the inlet valve closes and the com-
pressor is vented with running motor. When the running period expires the com-
pressor package switches to standstill only after the run ---on period has also
expired (5).
5 --- 18
Installation
6 Installation
Exhaust ventilator
Exhaust
min. 2200
A
duct
B
1017
h Air inlet
opening
800 784
A
500
B
b
820
min. 2200
min.
550
900
min. 2200
Measurements in mm
6 --- 19
Installation
Attention! The choice of exhaust air ducting, length of ducting and number
of bends can affect the compressor cooling system and must be
approved by the manufacturer.
Reliable, safe operation of the compressor package is only warranted if the temperature
limits (see chapter 1.6) of the air in the compressor space are kept to.
The compressor package is wired ready for connection to the main power supply as de-
tailed in the electrical diagram.
Attention! The cross-- section of the supply cable and the fuse ratings are speci-
fied to DIN VDE 0100 part 430 and 523 for an ambient temperature of
30 !C. For other operating conditions, e.g. higher ambient tempera-
tures or longer supply lines (over 50 m) check and determine the
cross-- section of the cable and the fuse ratings according to
DIN VDE 0100 and local electricity authority regulations.
See chapter 1.4 for recommended cable cross-- sections and fuses.
6 --- 20
Initial Start
7 Initial Start---up
! Remove all packing materials, tools and transport devices on and in the machine.
" It is expected that safe working methods are used and that all locally applicable oper-
ational and safety regulations are complied with.
" The user is responsible for the safe operating condition of the compressor package.
" Do not operate this compressor package in environments where the air is heavily con-
taminated with dust or where toxic or inflammable gases may be present.
" Do not connect the compressor package to a power supply different to that shown on
the nameplate.
" Do not install the compressor package in an environment subject to freezing tempera-
tures. The air temperature specified for the air---intake must be kept to (see chapter
1.6).
" If exhaust ducting is fitted, it must have a cross sectional area at least equal to the
cooling air outlet on the compressor package itself, and may not create a pressure
drop greater than that specified by the compressor manufacturer.
7 --- 21
Initial Start
" The compressor must be positioned with its cooling air inlet opening at least 1 m from
any wall.
! Check the cooling fluid level in the fluid separator tank (see chapter 9.12).
" The airend shaft must rotate in the correct direction (see chapter 7.4).
! Check the tension of the V---belts (see chapter 9.4).
! The shut ---off valve (6.6, see chapter 5.3) must be closed.
! The shut ---off valve (20, see chapter 5.3) must be open.
Carry out the following work only when power is removed from the
compressor package.
Check all screws on the electrical connections for tightness (carry out
this check again after 50 operating hours).
" This compressor package is fitted with a running ---in oil filter. Replace the filter after the
running ---in period of 200 hours has elapsed (see chapter 9.11).
7 --- 22
Initial Start
7.3 Checklist
! Is the floor at the place of installation solid and level?
# yes # no
! Is the space large enough for the compressor package or its components?
# yes # no
! Are inlet and exhaust air apertures available in sufficient size and number?
# yes # no
! Are all components of the compressor package easily accessible?
# yes # no
! Is the power supply cable of sufficient cross---section?
(have electrical connection carried out by qualified electrician or company familiar with
local conditions)
# yes # no
! Is a shut off valve fitted by the user?
# yes # no
! Is a flexible connecting hose or axial compensator fitted between the compressor
package and the air main?
# yes # no
! Have all screws, bolts and electrical connections been checked for tightness?
# yes # no
! Has the oil level in the oil separator been checked?
# yes # no
! Is a main switch fitted (suited to the motor starting characteristics)?
# yes # no
! Has the setting of the drive motor overload current trip been checked?
# yes # no
! Have you ensured that there are no other air components located in the exhaust air flow
of the compressor package?
# yes # no
! Have service personnel been instructed on safety regulations?
# yes # no
7 --- 23
Initial Start
A check of the direction of rotation can be made by testing the phase sequence.
Arrows showing the direction of rotation are located on the motor and on the air end hous-
ing.
If the direction of rotation is incorrect, change over the supply conductors L1 and L2.
Attention! If the air end rotates in the wrong direction, the compressor package is
automatically shut down by the pressure switch (4.2, see chapter 5.3).
Value:
To prevent the overload circuit breaker from triggering (because of voltage fluctuations,
temperature influences or component tolerances), the set value can be up to 15% higher
than the arithmetical phase current.
7 --- 24
Initial Start
Attention! Switching from full load to idle running may take place no more fre-
quently than 2 times per minute.
Switching frequency can be improved by increasing the difference between cut ---in and
cut ---out pressure.
In addition, a larger air receiver can be installed to increase buffer capacity.
Attention! If the actuator (3) at the door interlock is incorrectly aligned, inadver-
tent shutdown of the compressor package can occur.
The actuator (3) should align with the door interlock switch (1) without
binding against the sides of the interlock switch when the access door
is closed.
7 --- 25
Initial Start
! If necessary, use shims to help align the actuator (3) with the interlock switch (1).
! Tighten the bolts (4) again.
2
3
4
4
Attention! A functional check of the door interlock switch must be made after in-
itial start.
7.8.1 Pour a small quantity of oil into the air inlet port.
7 --- 26
Initial Start
! Unscrew the filler plug (1) on the inlet valve (2) and pour the prescribed quantity of oil
(see chapter 1.7) into the airend.
! Turn the airend counterclockwise by hand using the belt pulley.
! Screw the plug back in again.
Attention! This oil must be of the same type as used to run the compressor (see
label near the oil filler plug on the oil separator tank).
If the compressor package was shut down for longer than 12 months,
further measures must be taken before putting it back into operation.
Consult the manufacturer first.
! Open the shut ---off valve between the compressor package and the air main.
1 Filler plug
2 Inlet valve
7 --- 27
Operation
8 Operation
1 SIGMA CONTROL
2 EMERGENCY STOP pushbutton
8 --- 28
Operation
7
11 8
10 9
6
1
5 2
4 3
1 ON key (“I”) 6 Menu scroll --- DOWN key
2 OFF key (“0”) 7 Menu scroll --- UP key
3 Timer ON/OFF key 8 Escape key
4 Remote ON key 9 Return key
5 Load/idle key 10 Info --- event key
11 Acknowledge (reset) key
13
14 12
15
16 19
17
18
20 21
12 Four ---line display 17 Load LED
13 Alarm LED 18 Idle LED
14 Communication alarm LED 19 Compressor ON LED
15 Warning --- maintenance LED 20 Remote ON LED
16 Power ON LED (to controller) 21 Timer ON LED
8 --- 29
Operation
Local ON:
! Switch on the main switch.
The controller carries out a self---test. The self---test sequence is visible in the display (12).
Afterwards, the green LED (16) illuminates permanently.
! Press the ON key (1)--- LED (19) illuminates.
The compressor status is indicated by LEDs (17) and (18):
Attention! If LED (19) is illuminated and both LEDs (17) and (18) are extinguished
the compressor package is at standstill but on duty.
Local OFF:
! Press the OFF key (2) --- LED (19) extinguishes.
! Switch off and lock out the main switch.
See chapter 2.3 for details of the main switch.
Attention! If the compressor was shut down with the EMERGENCY STOP push-
button, then reset by rotating the latched pushbutton in the direction of
the arrow before acknowledging the alarm.
8 --- 30
Operation
Attention! When the respective maintenance has been carried out, the remaining
interval period (programmed interval until the next maintenance is due)
must be reset.
Detailed information on resetting service counters is to be found in the service manual for
SIGMA CONTROL.
8 --- 31
Operation
8 --- 32
Operation
Oil level in the separator tank too high. Drain off oil till the correct level rea-
ched.
Defective inlet valve. Have the valve inspected by an autho-
rized KAESER Service Technician.
8 --- 33
Operation
8 --- 34
Operation
8 --- 35
Maintenance
9 Maintenance
Before starting any maintenance work switch off at the main switch
and lock off to secure against unwanted or accidental switching on.
Make sure the machine is shut-- off or isolated from the air main during
maintenance work to ensure that no compressed air flows back from
the main.
Attention! The venting nozzle required to vent the oil separator tank (for mainten-
ance work such as topping up the oil, oil change and filter change) is
fitted to the hose coupling (3, see chapter 9.10).
Carry out a visual and functional check of the door interlock switch
after any maintenance and servicing work.
9 --- 36
Maintenance
* The maintenance period can vary depending on the motor switching frequency and envi-
ronmental conditions.
We urgently recommend that a record is kept of all servicing done (see chapter 9.16) and
that the compressor package --- especially safety devices --- are checked annually by an
authorized KAESER service agency.
9 --- 37
Maintenance
To close:
! Close the panel (3) the access door (2) and the access door (1) in the reverse order.
Close all access doors and panels correctly before starting the com-
pressor package.
A B
3
1
B
1 Access door
2 Access door
3 Cover panel
9 --- 38
Maintenance
2
1
1 Hexagonal nut
2 Hexagonal nut
3 Marking pin
The V---belt tension is automatically adjusted within a limited range by the pressure spring
of the belt tensioning device.
Re---tension the V---belts if they have stretched to the point where the marking pin (3) is
located at the top end of its indicator slot.
! Loosen the hex nut (2).
! Re---tension the V---belts with the hex nut (1) until the marking pin (3) is located at the
bottom end of its slot.
! Tighten the hex nut (2).
9 --- 39
Maintenance
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
1 3
2
3
3
1 Filter
2 Mounting frame
3 Closure
Attention! If the mat is heavily soiled or has been cleaned often (maximum five
times), then replace it.
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
9 --- 40
Maintenance
1 3
1 Air filter
2 Air filter cap
3 Wing nut for opening air filter housing
4 Air filter cartridge
To open the air filter housing:
! Unscrew the wing nut (3) and remove the air filter cap (2) and the filter cartridge (4).
! Clean the air filter cap and sealing surfaces.
Cleaning the air filter cartridge (4) by tapping:
! Tap the air filter cartridge several times on the front with the ball of the hand.
Attention! Do not use force otherwise the air filter cartridge may be damaged.
! Clean all sealing surfaces.
Cleaning the air filter cartridge with compressed air:
! Blow dry compressed air at a pressure of not more than 5 bar at a slant from the in-
side to the outside of the air filter cartridge surfaces.
Attention! Do not clean the air filter cartridge with fluids. If the air filter cartridge
is heavily contaminated or was already cleaned several times (max.
five times), renew.
To close the filter housing:
! Insert the filter cartridge (4) and replace the air filter cap (2).
! Screw on the wing nut (3) tightly.
9.9 Checking the Pressure Relief Valve on the Oil Separator Tank
To check the operating pressure of the pressure relief valve the final pressure of the
compressor package must be increased above the pressure parameter entered in the
controller.
See chapter 1.5 for the operating pressure of the pressure relief valve.
Attention! The pressure relief valve must be checked by an authorized KAESER
service agency when the interval quoted in the regular maintenance
table (see chapter 9.2) has expired.
9 --- 41
Maintenance
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
! Close the shut ---off valve between the compressor package and the air main.
The oil circulation vents automatically.
Venting the oil separator tank:
11
3
A
2
B 4
5
9
10
8
! The pressure gauge on the oil separator tank must indicate zero bar.
Oil mist can escape when the oil separator tank is vented.
! Insert the nipple (6) in the hose coupling (3) on the oil separator tank (the residual
pressure in the oil separator tank escapes).
! Remove the nipple (6) from the hose coupling (3).
9 --- 42
Maintenance
When the compressor package is vented, the air-- cooler and the pipe-
work up to the minimum pressure check valve are still under pressure.
For this reason the compressor package must be isolated from the air
main (close the user’s shut-- off valve). If a shut-- off valve is not avail-
able, vent the air main completely.
! Carefully remove the pipe fitting (4, see chapter 9.13). The air---cooler vents.
! Tighten the pipe fitting again.
Close all access doors and panels correctly before starting the com-
pressor package.
During the running in period, a running ---in oil filter cartridge is fitted to clean the oil sys-
tem.
Attention! Replace the running -- in oil filter cartridge with a standard oil filter car-
tridge after approximately 200 operating hours.
A further filter change is recommended after the interval quoted in the regular maintenance
table (see chapter 9.2) or when the corresponding service message is displayed on SIGMA
CONTROL (see chapter 8.1). The filter must be changed after every oil change.
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
9 --- 43
Maintenance
! Spin off the used or contaminated oil filter counter---clockwise and catch escaping oil
in a suitable container.
Dispose of the used filter and used oil carefully according to environ-
mental regulations.
Attention! Do not use a tool as this may cause damage to the oil filter and the
gasket.
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
9 --- 44
Maintenance
11
3
A
2
B 4
5
9
10
8
! Unscrew the oil filler plug (4) on the oil separator tank.
! Top up the oil to the maximum mark.
! Check the sealing ring of the filler plug (4) for damage and then replace the filler
plug (4).
! Open the shut ---off valve between the compressor package and the air main.
Attention! After carrying out the oil change or oil cooler cleaning (with removal of
the oil cooler) run the compressor package up to operating tempera-
ture to ensure that the combination valve closes and that the oil cooler
is flooded with oil.
Attention! Always use the same brand and type of oil when topping up (see label
on the oil separator tank).
If the type of oil is changed, drain the old oil completely and renew the
oil filter.
9 --- 45
Maintenance
Switch off and lock out the main switch to prevent an accidental com-
pressor start.
2
4
1 Allen screw
2 Hose screw fitting
3 Pipe screw fitting
4 Pipe screw fitting
! Unscrew the hose connector (2) and the pipe connector (3) from the combination
valve.
! Unscrew the hex socket head screws (1) on the air cooler.
! Remove and check the O---ring on the air cooler.
! Close up the pipes and openings on the combination valve and air cooler.
9 --- 46
Maintenance
5 Hexagonal nut
6 Allen screw
Attention! Before unscrewing the two hex socket head bolts (6) prop up the air/
oil cooler.
! Remove the protective caps and unscrew the two hex socket head bolts (6).
! Take out the air/oil cooler.
Clean the soiled cooler with water or steam jet in washing areas that
that are suitable for such cleaning work and provided with an oil sep-
arator!
! Clean the cooler cells with compressed air, water or steam jet.
! Reassemble in the reverse order.
Attention! Seat the O rings correctly in the compressed air inlet of the air cooler
during reassembly.
9 --- 47
Maintenance
The oil change interval is dependent on the degree of cooling air contamination and on the
ambient temperature.
If the compressor package is operated close to the maximum permissible ambient tem-
perature (see chapter 1.6), the oil must be changed more often, if necessary, the interval
should be halved.
Attention! Drain the oil out of the separator tank, cooler and the pipework com-
pletely. See chapter 9.14.4 for putting back into operation.
! Shut down the compressor package under full load (see chapter 8.3).
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
11
3
A
2
B 4
5
9
10
8
9 --- 48
Maintenance
1
1 Oil drain plug (oil cooler)
Drain the oil from the oil cooler:
! Prepare an oil container to catch the oil.
! Slowly unscrew the oil drain plug (1). The oil drains out under the force of gravity.
! Screw the oil drain plug (1) back in tightly.
Dispose of the old oil according to environmental regulations.
If a different type of oil is used drain the old oil completely and always
renew the oil filter.
9 --- 49
Maintenance
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
! Close the shut ---off valve between the compressor package and the air main.
The compressor oil circulation vents automatically.
! The pressure gauge on the oil separator tank must indicate zero bar.
! Close the shut ---off valve (1).
Close all access doors and panels correctly before starting the com-
pressor package.
! Start the compressor package (see chapter 8.3) and allow to run for approximately 30
seconds.
! Shut down the compressor package under full load (see chapter 8.3).
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
! Check the actual pressure on the pressure gauge (2). Open the shut ---off valve (1), let
the pressure on the pressure gauge (2) sink to approximately 3 bar and then close the
shut ---off valve (1) again.
! Drain the oil from the oil separator tank and the oil cooler. Proceed as detailed in chap-
ter 9.14.1.
! Open the shut ---off valve (1).
! Top up with oil as described in chapter 9.14.2.
9 --- 50
Maintenance
Switch off and lock out the main switch to prevent an accidental com-
pressor run.
6
7
4
2 8
3
7
5 6
9
10
11
12
The metal parts of the oil separator cartridge are electrically conduc-
tive and thus require ”electrically conductive gaskets”. The gaskets (6)
are fitted with metal clips (7) that fulfil this requirement and provide an
electrical path to the oil separator tank and to the frame of the com-
pressor package.
! Unscrew the hexagonal bolts (4) and remove cover plate (5).
! Take out the old oil separator cartridge (8) together with the gaskets (6) and O ring (9).
Dispose of the old parts according to environmental regulations.
! Clean the sealing surfaces of the oil separator tank.
9 --- 51
Maintenance
! Insert the new O ring (9) in the groove in the oil separator tank.
! Insert the new oil separator cartridge (8) with new gaskets (6), fit and tighten down the
cover plate (5) with the hexagonal bolts (4).
! Renew the strainer (11) and the gasket (10) when the oil separator cartridge (8) is re-
newed.
! Open the shut ---off valve between the compressor package and the air main.
9 --- 52
Maintenance
9 --- 53
Spare Parts and After Sales Service
The removal of faults that are not explicitly described in this service
manual may only be carried out by KAESER or by an authorised
KAESER service agent.
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Year of production . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rated power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW
Ambient temperature . . . . . . . . . . . . . . . . . . C / . . . . . . . . C
Comprising:
Separating cartridge 1
Gasket 2
O Ring 1
Dirt screen filter 1
Gasket 1
10 --- 54
Spare Parts and After Sales Service
10 --- 55
Appendix
11 Appendix
11 --- 56
Appendix
11 --- 73
SERVICE MANUAL USE
Refrigerated Dryer
Model: TU 26
GL---Nr.: BA---TU26---1.8014.20110
Index: 000801
3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 6
3.1 Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 6
3.2 Improper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 6
3.3 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 6
4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 7
4.1 Transport Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 7
4.2 Temporary Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 7
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 14
6.1 Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 14
6.2 Compressed Air Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 15
6.3 Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 16
6.4 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 --- 16
i
Table of Contents
Chapter --- Page
8 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 19
8.1 Instrument Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 19
8.2 Starting the Refrigerated Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 20
8.3 Stopping the Refrigerated Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 21
8.4 To be Observed when Restarting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 21
8.5 Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 22
8.5.1 Water in the compressed air system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 22
8.5.2 High pressure losses via the refrigerated dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 22
8.5.3 Pressure dew point too high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 22
8.5.4 High compressed air losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 23
8.5.5 Red LED on the ECO---DRAIN housing flashes . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 --- 23
8.5.6 The safety pressure switch shuts down the refrigerated dryer . . . . . . . . . . . . . . 8 --- 23
9 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 24
9.1 Maintenance Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 24
9.2 Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 24
9.2.1 Check the condensate outlet daily as follows: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 24
9.2.2 Check ECO---DRAIN for proper operation monthly, as follows: . . . . . . . . . . . . . . 9 --- 25
9.2.3 Cleaning the condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 25
9.2.4 General checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 25
9.2.5 Cleaning the ECO---DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 --- 26
11 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 30
11.1 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 30
11.2 Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 --- 38
ii
Technical Specification
1 Technical Specification
Drawings:
P & I flow chart . . . . . . . . . . . . . . . . . . . . FKTTU26ST---00027.01
(Pipework and instrument flow chart)
Electrical diagram . . . . . . . . . . . . . . . . . . . . . . . . . STU---U0908.00
1.5 Connections
Compressed air outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NPT
Condensate drain connection (hose connection) . . . . . . . 3/8”
Service connection (Schrader valve) . . . . . . . . . . . . . . 7/16 UNF
1 --- 1
Technical Specification
Attention! Maximum dual element time -- delay fuses are selected according to
1996 N.E.C. Article 240 -- 6, 430 -- 52 and Tables 430 -- 148 & 150.
1.7 Settings
Safety pressure switch (refrigerant)
switching point (fixed)
POFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 psi
1.8 Designation
The nameplate of the dryer is located on the back, next to the compressed air connection
(see chapter 10 for the illustration of the name plate).
1 --- 2
Safety
2 Safety Regulations
Read this service manual very carefully and observe all cautionary references before the
initial start of this refrigerated dryer and before carrying out any maintenance on the unit.
2 --- 3
Safety
4. Lock the isolation shut-- off valve in the ”closed” position and vent
all compressed air trapped in the refrigerated dryer or in the piping
between the dryer and the isolation shut-- off valve in accordance with
applicable lock out/ tag out procedures (example: OSHA CFR 29
§ 1910.147).
Attention! Any alterations or reconstruction carried out without the prior written
authorization of KAESER COMPRESSORS Inc. will invalidate the war-
ranty.
2 --- 4
Safety
Ensure that all wear items, maintenance and replacement parts accu-
mulated during operation of the refrigerated dryer are disposed of ac-
cording to environmental regulations.
2 --- 5
General
3 General
The service manual must always be available for use at the location of
the refrigerated dryer.
3.3 Copyright
KAESER COMPRESSORS, INC.
All rights reserved. No part of this manual may be reproduced in any form without permis-
sion of KAESER COMPRESSORS, INC.
3 --- 6
Transport
4 Transport
! Always mount the refrigerated dryer on a suitable transporting medium (pallet or woo-
den base) during transport.
min. 32”
min. 40”
Attention! Do not exert any side forces on the refrigerated dryer with lifting equip-
ment.
Attention! Before initial start, wait until the temperature of the refrigerated dryer
has adapted to the ambient temperature.
4 --- 7
Construction and Operation
Items referred to in ( ) correspond with the items in the Pipe and Instrument Flow Diagram
(see chapter LEERER MERKER).
5.1 Construction
The main component of the refrigerated dryer comprises a combined heat exchanger (heat
transmitter). It consists of the two following main groups:
1st. stage: air to air heat exchanger (1)
2nd. stage: air to refrigerant heat exchanger (2)
A condensate separating system (3) is fitted in series with the heat exchanger.
A safety pressure switch (9) is fitted in the refrigerant circulation system as a protection
against excessive pressure.
A thermal overload switch protects the refrigerant compressor (11) against current over-
loads and high temperatures.
The refrigerated dryer housing is designed for mounting beneath a compressor of the
same manufacturer.
5 --- 8
Construction and Operation
sure, liquid refrigerant enters the evaporator (2) where heat from the compressed air is
transferred to the refrigerant. The added heat causes the refrigerant to boil and results in
the refrigerant becoming a low pressure gas. This becomes an endless cycle which allows
the refrigerant to simply remove heat from the compressed air and expel it to the ambient
air.
5.4.2 Function
Any moisture that is condensed flows to a low point where it enters the drain trap at the
inlet opening (1). The moisture is collected in the drain trap chamber (2). Once the cham-
ber is full, the electronic sensor (3) energizes the electronic controller (7). The controller
opens a small pilot port which allows the diaphragm valve (4) to open. As the liquid level
drops, the electronic sensor closes the valve again before any compressed air can escape.
8
1 2 3 4 5
1 Inlet opening 5 Outlet line
2 Collector 6 Housing
3 Level detector 7 Electronic control
4 Diaphragm valve 8 Light ---emitting diode
! If a fault occurs (e.g. overload), the valve cycles on and off continuously to clear the
fault. The light ---emitting diode flashes.
5 --- 9
Construction and Operation
8 9
8 Operational status --- light emitting diode
9 TEST pushbutton (condensate drain)
5 --- 10
Construction and Operation
1 2 3 4 5
14
13
13 8 11 10 14 2 12
1 Operating panel 8 Capillary tube (7)
2 Control cabinet 9 Hot gas bypass valve (19)
3 Condensate ECO ---DRAIN (5) 10 Safety pressure switch (9)
with outlet hose 11 Fan pressure switch
4 Shut ---off valve (4) 12 Condenser (10)
5 Refrigerant compressor (11) 13 Filter dryer (8)
6 Compressed air inlet 14 Heat exchanger with integrated
7 Compressed air outlet moisture separator (1), (2), (3)
5 --- 11
Construction and Operation
5 --- 12
Construction and Operation
5 --- 13
Installation
6 Installation
Attention! To ensure adequate ventilation and air circulation, be sure to allow for
the indicated minimum clearances at the cooling air inlet and exhaust.
The refrigerated dryer must not be installed in the air inlet and/or coo-
ling air outlet area of a compressor package.
The compressed air to be dried and the ambient air in the compressor
space may not contain any acid -- forming or other aggressive materi-
als.
6 --- 14
Installation
Exhaust ventilator
min. 87
Exhaust Air inlet
duct opening
28
20
min. 87
32
min. 87
Measurements in inches
Attention! Installing of inlet and/or exhaust air ducting without prior written ap-
proval from of KAESER COMPRESSORS Inc. is not permitted.
Attention! Use flexible connecting pipes at the compressed air inlet and dis-
charge to ensure vibration isolation, prevent strain on piping connec-
tions and allow easy installation.
To avoid damage, do not overtighten the compressed air connections.
All power driven systems must be equipped with a main stop system
for all forms of energy feed, the operation of which determines the
start and stop of the energy supply to the system.
The compressed air inlet and outlet pipework must be provided with shut off arrangements
(e.g. ball valves).
6 --- 15
Installation
Attention! Use caution when attaching the condensation drain line to ensure that
the condensate flow is not obstructed.
The refrigerated dryer is delivered completely wired, ready for connection to the power
supply.This connection must be made as detailed in the electrical diagram (see
chapter 11.1). See the Airtower dimensional diagram for the position and size of the cable
entry into the refrigerated dryer.
Attention! Maximum dual element time -- delay fuses are selected according to
1996 N.E.C. Article 240 -- 6, 430 -- 52 and Tables 430 -- 148 & 150.
6 --- 16
Preparation For Initial Start Up
Attention! The internal components of the refrigerated dryer are factory adjusted
for correct operation. Adjustments may not be made to these compo-
nents without prior written consultation with KAESER Compressors
Inc.
Do not operate the refrigerated dryer with the side panels removed.
Operation without the panels may result in injury.
! Remove all packaging materials, tools and transport securing devices on and in the
refrigerated dryer.
" It is expected that the operator uses safe working methods when operating the refrig-
erated dryer and that all valid operating and safety provisions are followed.
" The operator of this refrigerated dryer is responsible for its safe operating condition.
" The compressed air to be dried and the ambient air of the place of installation may not
contain any acid ---forming or other aggressive materials.
" Do not connect the refrigerated dryer to a supply voltage different to that shown on the
nameplate.
" Install the refrigerated dryer in a space that is not subject to freezing conditions. See
chapter 1.4 for the minimum ambient temperature..
" Allow the refrigerated dryer to reach the ambient temperature before putting into
operation.
Lock the main disconnect in the ”off” position in accordance with ap-
plicable lock out/tag out procedures (example: OSHA CFR 29
§ 1910.147) to ensure the refrigerated dryer does not restart.
7 --- 17
Preparation For Initial Start Up
" The refrigerated dryer is installed according to the conditions stated in chapter 6.
" All electrical connections, air piping and condensate lines are correctly connected and
properly tightened.
" The shut ---off valves in the compressed air inlet and outlet lines are closed.
" The condensate drainage line is free of obstructions.
" The refrigerated dryer is supplied with the correct voltage supply.
Attention! Start the refrigerated dryer for approximately 15 minutes before open-
ing the shut-- off valves in the compressed air inlet and outlet lines.
7 --- 18
Operation
8 Operation
During operation of the refrigerated dryer, condensate is separated from the compressed
air.
3 2 1
1 Control switch
2 Control Voltage ON indication
3 Pressure dewpoint gauge
8 --- 19
Operation
Explanation of the colored segment scale of the pressure dew point indication:
(suction pressure gauge)
B C
D
A
" A
Blue -- white range (low suction pressure) results in too low a pressure dewpoint due
to:
--- Evaporator temperature too low (evaporator freeze---up)
--- Dryer too large or very low air demand. Refer to chapter 1.4
" B
Green range (normal suction pressure) results in a normal pressure dew point.
" C
Green-- red range (elevated suction pressure) results in increased pressure dew point
to:
--- High ambient temperature
" D
Red range (high suction pressure) results in too high a pressure dew point due to:
--- Fault, see chapter 8.5.3 for help
Attention! Open the shut-- off devices in the air lines slowly after approximately
15 minutes.
8 --- 20
Operation
! Open the shut ---off valve of the compressed air inlet slowly
(admission of the compressed air).
! Open the shut ---off valve of the compressed air outlet slowly.
The compressed air system is now connected to the refrigerated dryer.
Attention! Press RESET if the safety pressure switch has shut down the refriger-
ated dryer.
1 RESET
8 --- 21
Operation
Condensate deposits in the com- Blow out the compressed air pipe
pressed air pipe work that were work with dry air until no more mois-
formed before the dryer was put into ture condenses.
service.
Compressed air inlet and outlet swap- Check the compressed air connec-
ped tions using the dimensional diagram.
The condensate is not drained out of Check the ECO---DRAIN (see chapter
the system. 9.2.2); refer to authorized KAESER dis-
tributor.
Refrigerated dryer iced up on the air Switch off the dryer until the air system
side. has thawed. If the system ices up
again after starting again, refer to
authorized KAESER distributor.
8 --- 22
Operation
Constant loss of pressure via the con- Clean the ECO---DRAIN (see chap-
densate drain. ter 9.2.5).
8.5.6 The safety pressure switch shuts down the refrigerated dryer
8 --- 23
Maintenance
9 Maintenance
Lock the main disconnect in the ”off” position in accordance with ap-
plicable lock out/tag out procedures (example: OSHA CFR 29
§ 1910.147) to ensure the dryer does not restart.
Before starting work, carry out the following procedure to prevent inadvertent ap-
plication of power to the refrigerated dryer:
! turn switch (1) to ‘‘ 0 ’’.
! lock out the switch (1) using a suitable padlock.
Before restarting the refrigerated dryer, ensure that:
" no maintenance personnel are working on the refrigerated dryer.
" all tools are removed from the refrigerated dryer.
" all guard and cover panels are properly installed and secured.
See chapter 7.3 and 8.2 for starting the refrigeration.
The maintenance periods are recommended periods and may need to be adjusted based
on installation and service conditions.
! Verify that condensate exits from the hose of the condensate drain outlet when the
drain opens (the LED extinguishes for a short period).
9 --- 24
Maintenance
8 9
8 Operational status --- light emitting diode
9 TEST pushbutton (condensate drain)
! Check all pipework, hoses and screwed fittings for leakage every two to three months
and carry out a visual check for any external damage. Correct any faults immediately!
9 --- 25
Maintenance
Before removing up the ECO -- DRAIN it must be shut off from the com-
pressed air.
! Close the shut ---off valve in the air line to the ECO---DRAIN.
Attention! The ECO -- DRAIN is still connected to the power supply cable.
9 --- 26
Maintenance
11
10
9
8
7
6
5
1 2 3
Attention! Watch for loose parts fitted into each other that could easily be lost
when disassembling the ECO -- DRAIN.
Note the final positions of the individual parts.
! Unscrew the four cross---head screws (1) on the diaphragm seat (4) and remove care-
fully with the diaphragm cover (6) from the housing (10). Watch for loose parts, such
as the pressure springs (5) and (8), diaphragm (2) and the O rings (3) and (7)!
Cleaning:
! Remove the thrust spring (5), diaphragm (2) and valve piston (9) with its thrust spring
(8) and clean them.
! Blow out the diaphragm seat (4), diaphragm cover (6), and the housing inside with
compressed air.
9 --- 27
Maintenance
! Check the diaphragm (2), the existence and correct seating of the O rings (3) and (7)
on the diaphragm seat (4) and diaphragm cover (6). Renew defective parts.
! Check the valve piston (9) for signs of wear and renew, if necessary.
! Check the existence and correct seating of the thrust spring (8) for the valve piston (9).
! Insert the valve piston (9) into the guide hole in the housing.
! Place the thrust spring (5) over the nipple on the diaphragm cover (6). Check that the
thrust spring (5) sits correctly.
! Fit and position the diaphragm cover (6) over the valve piston (9) in the housing.
! Fit the diaphragm (2) into the opening in the diaphragm seat (4).
! Fit the diaphragm seat (4) to the diaphragm cover (6). Check that the thrust spring (5)
is positioned in the recess provided in the diaphragm (2). Insert the four cross---head
screws (1) through the holes provided in the vertically assembled diaphragm seat, dia-
phragm cover and housing and screw the components together tightly.
Final work:
! Fit the ECO---DRAIN back into the refrigeration dryer with the screw fittings.
! Open the shut ---off valve (in the compressed air line to the ECO---DRAIN).
! Carry out a functional check of the ECO---DRAIN (see chapter 9.2.2).
See chapter 8.2 to start the refrigerated dryer.
9 --- 28
Spare Parts and After Sales Service
Provide the following details for all queries and spare parts orders:
(see also the name plate)
Refrigerated dryer, model: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial number: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part order number: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Always provide the date of initial start up when making claims under warranty!
Name plate:
lb.
psig
psig
1ph
3ph
10 --- 29
Appendix
11 Appendix
11 --- 30
Appendix
11 --- 38