0% found this document useful (0 votes)
45 views40 pages

RITZ-Medium Voltage Instrument Transformers Standard ENG 2014 01-1

Uploaded by

Tomasz Wiercioch
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views40 pages

RITZ-Medium Voltage Instrument Transformers Standard ENG 2014 01-1

Uploaded by

Tomasz Wiercioch
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Medium Voltage Instrument Transformers

Standard Transformers
RITZ Instrument Transformers GmbH – Core competency

Under the trading name „RITZ Instrument Transformers GmbH” RITZ has been pooling its activities to gather new strengths
since 01.08.2007.

The tradition and knowledge of the parent company „RITZ Messwandler Hamburg“ and the subsidiary „RITZ ­Messwandler
Dresden (TuR)“ has been united with the companies “Wandler- und Transformatoren-Werk Wirges (WTW) and
­“Messwandlerbau Bamberg (MWB)” under this name. This merger unites a total of more than two hundred years of know-
how in instrument transformers production.

In addition, RITZ has decided to concentrate on the core business of medium voltage and low voltage transformers in
which the high voltage division is sold. The resources gained through this shall now be applied for additional innovations
and quality standards in the medium and low voltage products. RITZ is therefore securing its position on the global market.

The overseas corporations of RITZ Instrument Transformers GmbH in Austria (Marchtrenk), Hungary (Kecskemét), China
(Shanghai) and USA (Hartwell) strengthen the company’s position on the international market.

2
Contents

Introduction 2
1.0 Medium Voltage Instrument Current and Voltage Transformers
1.1 General 4
1.2 Design 5
1.3 Current Transformer 6
1.3.1 Choice limitations of the Rated Burden 7
1.3.2 Definitions 7
1.3.3 Metering Current Transformer 8
1.3.4 Protective Current Transformer 9
1.3.5 Reconnection of Current Transformer 9
1.3.6 Over Current Range 9
1.3.7 Service and Grounding 10
1.3.8 Capacitive Divider 10
1.4 Voltage Transformer 11
1.4.1 V-Connection of Two Double Pole Insulated Voltage Transformer 11
1.4.2 General Design 11
1.4.3 Definitions 12
1.4.4 Service and Grounding 13
1.4.5 Ferroresonances 13
1.5 Service Conditions 14
1.5.1 Altitude 14
1.6 Test Voltages and Insulation Levels for Instrument Transformers 14
1.7 Insulation Class 14s
1.8 Partial Discharge Test 15
1.9 Standards 15

2.0 Products
Product Selection List 16 - 17
2.1 Current Transformer Indoor up to 72,5 kV
2.1.1 Support Type Current Transformer Indoor Block-Type (narrow type) ASS 12 | 17,5 | 24 | 36 | 40,5 18
2.1.2 Support Type Current Transformer Indoor Block-Type GSW 12/0 19
2.1.3 Support Type Current Transformer Indoor Block-Type ASN 12 | 17,5 | 24 | 36 20
2.1.4 Current Transformer Indoor GI 52 | 72,5 21
2.1.5 High Current Transformer Indoor GSSO 12 | 17,5 | 24 22
2.1.6 Bushing Current Transformer with Fixed Bars Indoor GDS 12 | 17,5 | 24 | 36 23
2.2 Current Transformer Outdoor up to 72,5 kV
2.2.1 Support Type Current Transformer Outdoor Compact GIFK 12 | 17,5 | 24 | 36 24
2.2.2 Support Type Current Transformer Outdoor Standard GIFS 12 | 17,5 | 24 | 36 25
2.2.3 Current Transformer Outdoor Head Type GIF 10 | 17,5 | 20 | 30 | 36 | 52 | 72,5 26
2.3 Voltage Transformer Single Pole up to 72,5 kV
Indoor
2.3.1 Voltage Transformer Indoor VES 12 | 17,5 | 24 | 36 27
2.3.2 Voltage Transformer Indoor GSE 12/0 28
2.3.3 Voltage Transformer Indoor VEN 12 | 17,5 | 24 | 36 | 52 | 72,5 29
Outdoor
2.3.4 Voltage Transformer Outdoor VEF 12 | 17,5 | 24 | 36 30
2.3.5 Voltage Transformer Outdoor Head Type VEF 52 | VEF 72,5 31
2.4 Voltage Transformer Double Pole up to 36 kV
Indoor
2.4.1 Voltage Transformer Indoor VZS 12 | 17,5 | 24 32
2.4.2 Voltage Transformer Indoor GSZ 12/0 33
2.4.3 Voltage Transformer Indoor VZN 12 | 17,5 | 24 | 36 34
Outdoor
2.4.4 Voltage Transformer Outdoor VZF 12 | 17,5 | 24 | 36 35
Low Voltage Instrument Transformers 36
Cast Resin Insulated Bus Bar Systems up to 72,5 kV, 6500 A 37
Cast Resin Insulated Power Transformers up to 40,5 kV, 25 MVA 38
Electronic Instrument Transformers & Sensors | Customised Cast Resin Parts 39

Medium Voltage Instrument Transformers 3


1.0. Medium Voltage Current and Voltage Transformers

1.1 General

Instrument transformers are transformers, which convert high currents or voltages into measurable and standardized
currents or voltages, which are proportional and in-phase to the primary signal. They are intended to supply electrical
measuring instruments, meters, relays or other electrical devices.

CT according to DIN-Design PT according to DIN-Design

Current Transformer Voltage Transformer


A current transformer is designed to convert the primary Voltage transformers have only one iron core with attached
rated current which flows through the primary winding. secondary winding (s).

The secondary winding must generally be short circuited at If an open delta circuit (da-dn) is necessary, an ­additional
any time, otherwise dangerous high voltages can occur at ­winding can be provided for single pole insulated
the secondary terminals. ­transformers.

The secondary connected devices are connected in series. It is extremely dangerous to short circuit a voltage
t­ransformer.
Current Transformers can be equipped with one or more
independent magnetic cores with equal or different For single pole insulated transformers the end of the primary
­characteristics for measuring, metering and/or protective winding is grounded as “N” inside of the secondary terminal
purposes. box, and must not be removed during operation.

4
1.2 Design

Instrument transformers can be differentiated into • Bushing types for indoor and outdoor application
different designs through their specification and applica-
tion. The following basic designs exit: • Voltage transformers, single or double pole insulated, for
indoor and outdoor application.
• Supporting types according to DIN 42600 (only for indoor
use) or designed according to customer requirement for
indoor and outdoor application

Support type current transformers for indoor applicationss Single pole voltage transformer for indoor applications

High current bushing type current transformer Outdoor voltage transformer with characteristic shields to extend the
creepage distance

Medium Voltage Instrument Transformers 5


1.3 Current Transformer Tabliczka znamionowa Uzwojenie pierwotne (W1) Odlew żywiczny

Current transformers are transformers which convert high


currents into measurable and standardized currents
proportional and in-phase to the primary signal. Uszczelniona
skrzynka
przyłączeniowa
A current transformer can be equipped with one or more Zacisk
independent ferromagnetic cores made of silicon or nickel uziemiający

iron steel.

The secondary winding (W2) is symmetrically wound around


the iron core. This causes a very intensive magnetic coupling
of the primary to the secondary winding. The number of
turns of the secondary winding depends on the ratio between
the primary and the secondary rated current. The iron core(s) Przepust kablowy Zaciski strony wtórnej Rdzeń 1 Rdzeń 2 Płyta podstawy
(W2) (W2)
and the secondary winding must be grounded.
General design sample of a current transformer
Depending on the primary rated current and the short time
current (Ith), the primary winding (W1) consists of one solid
winding (primary conductor) or a number of turns.
The resin body is mounted on a metal plate. The secondary
The primary winding is designed for the full rated current terminals are embedded in the resin body and protected by
and has the same potential as the busbar. a plastic box. The cover of the box is removable and can be
sealed. Each secondary terminal can be separately grounded
The highest system voltage (phase to phase voltage) has to inside the secondary terminal box. The grounding screw is
be considered for the design of the transformer with respect connected to the bottom plate. The terminal box is equipped
to its insulation between the primary and the secondary with two or three removable cable plugs, which makes
winding. wiring easy.

The windings W1 and W2 as well as the iron core(s), together The ends of the primary winding are provided with flat
with the secondary winding(s) are completely resin-embedded terminals (“P1/P2”), made of copper or brass alloy, and
and casted in a single production step by using a pressure located at the top of the resin body.
gelation casting process.
A M8 grounding screw is available on the bottom plate for
grounding the current transformer. Grounding can take
place directly on the frame of the switchgear or on a separate
grounding bar.

6
1.3.1 Choice Limitations of the Rated Burden 1.3.2.2 Rated Continuous Thermal Current
Especially for small rated primary currents, and high rated This is the value of the current which can be permitted to
short time thermal currents (Ith), the rated burden of a flow continuously through the primary winding while the
­current transformer is limited due to the maximum p­ ermissible secondary winding is connected to the rated burden, without
kAW-value (ampere turns). In this case, information should the rise in temperature exceeding the values specified.
be requested from the manufacturer.
It is common practice that the rated continuous thermal
If the rated burden of a current transformer is calculated ­current is equal to the rated current but a higher current
according to the formula can also be defined.

1.3.2.3 Rated Short Time Thermal Current


(AW) 2 . QFe. K The r.m.s value of the primary current is the value which a
PN = [VA] transformer will withstand for one or three seconds without
lFe
suffering harmful effects, should the secondary wiring be
short circuited.
AW primary ampere turns
QFe iron cross section (mm2) 1.3.2.4 Rated Dynamic Current
K constant The peak value of the primary current is the value which a
lFe ferromagnetic circuit (cm) transformer will withstand, without being damaged electri-
cally or mechanically by the resulting electromagnetic forces,
it becomes evident that, if the ampere turns (AW) can be should the secondary winding be short circuited.
doubled, a burden which is four times higher can be ­achieved.
Physically speaking, however, this is not always feasible, 1.3.2.5 Burden
because the ampere turns are limited by the rated dynamic Burden is the impedance of the secondary circuit and power
current (Idyn). The reason for this is the force of the magnetic factor in ohms. The burden is usually expressed as the
field intensity which, in case of a short circuit, attempts to ­apparent power in volt amperes (VA) at a specified power
mutually balance the individual primary windings. factor and at the rated secondary current.
Furthermore, the maximum rated burden depends on the
size of the resin body. 1.3.2.6 Rated Burden
The value of the burden is based on the accuracy require-
1.3.2 Definitions ments of this specification.

1.3.2.1 Rated Primary and Secondary Current


The value of the primary and secondary current indicates
the performance rating of the transformer. A common
practice is to use a secondary rated current of 1 or 5 A.
The primary rated current depends on the network and is
defined by the end user.

Economically speaking, a secondary rated current of 1A


should be chosen in order to keep the rated burden low,
especially for long wiring distances.
PN = I² · R+PB

Medium Voltage Instrument Transformers 7


1.3.2.7 Error Limits 1.3.3 Metering Current Transformer
The composite error for metering cores has to be h ­ igher than This is a current transformer intended to supply indication
10% to protect the connected metering devices in case of instruments, integrating meters and similar apparatus.
over currents. In the opposite the composite error for
­protection cores at the rated accuracy limit of the primary 1.3.3.1 Accuracy Class
current should be smaller or equal 5% (5P) or 10% (10P) to This is the limit of the permissible percentage of current
secure a proper tripping of the connected protection devices. error at the rated current. In general, the limits of current
error are calculated for a range between 1% up to 120%
1.3.2.8 Instrument Security Factor of rated current.
In the event of a system fault when a current is flowing
through the primary winding of a current transformer, the
apparatus is offered the highest level of protection by the
transformer when the security factor value (FS) of the rated
instrument is small.

Permissible limits for current error (Fi) and phase displacement (δi) according to IEC 60044-1
± percentage of current ± phase displacement in minutes at
Accuracy Class error at percentage of rated current percentage of rated current
1 5 20 100 120 1 5 20 100 120
Measuring Current Transformers
0,1 - 0,4 0,2 0,1 0,1 - 15 8 5 5
0,2S 0,75 0,35 0,2 0,2 0,2 30 15 10 10 10
0,2 - 0,75 0,35 0,2 0,2 - 30 15 10 10
0,5S 1,5 0,75 0,5 0,5 0,5 90 45 30 30 30
0,5 - 1,5 0,75 0,5 0,5 - 90 45 30 30
1 - 3,0 1,5 1,0 1,0 - 180 90 60 60
Protective Current Transformers
5P - - - 1 - - - - 60 -
10P - - - 3 - - - - - -

Instrument Transformer Error Limits for Instrument Transformer Error Limits for
Accuracy Class 0.1 Accuracy Class 0.2s; 0.2
Error F [%]

Error F [%]

Rated Current IN [%] Rated Current IN [%

Instrument Transformer Error Limits for Instrument Transformer Error Limits for
Accuracy Class 0.5s; 0.5 Accuracy Class 1
Error F [%]

Error F [%]

Rated Current IN [%] Rated Current IN [%]

8
1.3.4 Protective Current Transformer 1.3.5.2 Secondary Tapping
A current transformer intended to supply protective relays. For secondary tapping the secondary winding is wound on
Protective current transformers are marked with the letter the iron core in two or more separate sections. The ends of
“P”. these are connected to the secondary terminals. ­Changeover
will be performed at the secondary side. In the case that the
1.3.4.1 Special Request primary rated current should be changed to the lower ­current,
On request current transformers can be designed for higher the accuracy class between 0.2 and 3 will decrease at
extended current ratings than the standard value of 120%. ­approximately the square value of the reduction in primary
Additional typical values are for example 150% and 200%. current. The ratings of the protective cores of class 5P or
This means that accuracy is guaranteed at 150% or 200% 10P decrease almost proportionally to the reduction of the
of the rated primary current. primary current.
The values of the rated short time thermal current, as well
1.3.5 Reconnection of Current as the dynamic current, remains the same at all ratios.
Transformer P1 P2
In case of changeable ratios, for example extension of nominal
rated current, it is possible to design the transformer with
primary reconnection or secondary tapping.
S1 S2 S3
S1 – S3 high rated current S1 – S2 low rated current
1.3.5.1 Primary Reconnection Circuit Diagram Secondary Tapping
The primary reconnection can only be used for primary
­currents up to 2 x 600A and for current transformers which 1.3.6 Over Current Range
have a primary winding consisting of several primary turns. In the event of a system fault, the secondary rated current
The ratio of the reconnection is always 1:2. increases in proportion to the primary rated current up to
the limit of the primary current.
C1 C2 The error limits will only be observed of the secondary ­burden
is equal to the rated burden. If the burden is different to the
P1 P2
rated burden, the instrument security factor will be changed.

1S1 1S2
C1 – C2 low rated current P1/C1 – P2/C2 high rated current IS/ISN
Circuit Diagram Primary Reconnection
Protection core 5P10

For primary reconnection, the primary winding consists of 10 Fg < 5 %


two winding sections (P1-C2 & C1-P2) which can either be
connected in series or parallel. The changeover will be done
at the primary side by using joint bars. In case of p
­ rimary
reconnection the rated burden, the accuracy, and the
­instrument security factor remains unchanged. 5 Fg > 10 %

Measurement core Cl. 1Fs5

51 0 IP/IPN

Medium Voltage Instrument Transformers 9


1.3.7 Service and Grounding All supporting type current transformers can be equipped
The secondary winding must generally be connected with a capacitive divider.
to a burden or be short circuited at all times; otherwise The capacitive divider is embedded in the resin body. The
dangerous high voltages can occur in the secondary capacity C2W is connected to the terminal CK inside of the
­terminals. One end of the secondary winding as well as ­secondary terminal box. A surge arrester is connected
all other metal parts of the transformer must be groun­ ­between the terminals CK and earth and is intended to limit
ded. the output voltage.

Secondary terminal with grounding screw of a current transformer


type ASS.

Circuit diagram capacitive divider


1.3.8 Capacitive Divider
With reference to the guidelines of the modern switch gear C2A voltage indicator
it is required, and it is common practice with respect to safe C1 upper capacity
handling of the switch gear, that the doors and all coverings C2W lower capacity
can only be opened after the panel is de-energized. This will C2L lead capacity
be achieved by using a voltage indicator which is mounted Ck terminal
in the front door of the panel. L high voltage
U line to ground voltage
The voltage indicator consists of a capacitive divider splitting U1 partial voltage at C1
the voltage U between phase and ground into two voltages, U2 partial voltage at C2 (C2W + C2L+ C2A)
namely U1 and U2. An indicating device, which is connected V surge arrester
between the terminal CK inside of the secondary terminal
box and earth.

Indication range:
Smaller than 0,1 x UN no indication
Equal or greater than 0,4 x UN safe indication

10
1.4 Voltage Transformer

Voltage transformers are transformers which convert 1.4.1 V-Connection of Two Double Pole
high voltages into measurable and standardized voltages Insulated Voltage Transformers
­proportional and in-phase to the primary signal. When using two double pole insulated transformers con­
Voltage transformers have only one magnetic iron core with nected in „V-connection”, it must be strictly observed that
attached secondary winding (s). the secondary winding(s) of only one of the two transformers
Voltage transformers can be provided either as single pole is grounded. This is in order to avoid a short circuit between
or double pole insulated designs. An additional winding can these two transformers.
be provided for single pole insulated transformers (da-dn)
if necessary for an open delta circuit.

A N

Schematic V-connection
a n da dn
Schematic single pole insulated voltage transformer with an 1.4.2 General Design
open delta winding Voltage transformers have only one magnetic iron core.
For single pole insulated voltage transformers the secondary
winding(s) are attached directly to the grounded iron core.
A B In single pole insulated transformers the secondary winding(s)
are directly attached to the grounded iron core. In double
pole insulated voltage transformers the insulation between
primary and secondary winding(s) has to be designed for
one half of the phase to ground voltage.
The secondary windings are designed to withstand a test
a b voltage of 3 kV against each other.

Schematic double pole insulated voltage transformer

It is extremely dangerous to short circuit a voltage


­transformer.

The end of the primary winding in single pole insulated


t­ransformers is grounded as „N” inside of the secondary
terminal box, and must not be removed during operation.

General design sample of a single pole voltage transformer

Medium Voltage Instrument Transformers 11


The high voltage winding as well as the secondary winding(s) 1.4.3.3 Rated Transformation Ratio
are completely embedded in resin and casted in a single The ratio of the rated primary voltage to the rated secondary
­production step by using a pressure gelation casting process. voltage.

The resin body is mounted on a metal plate. The secondary 1.4.3.4 Limits of Voltage Error and Phase
terminals are embedded in the resin body and protected by
Displacement
a plastic box. The cover of the box is removable and can be
The voltage error (Fu) and phase displacement (δu) at the
sealed. Each secondary terminal can be separately grounded
rated frequency shall not exceed the values given in the
inside the secondary terminal box. The grounding screw is
f­ollowing table at any voltage between 80% and 120% of
connected to the bottom plate. The terminal box is e­ quipped
rated voltage, and with burdens between 25% and 100%
with two or three removable cable plugs, which makes
of the rated burden and a power factor of 0.8.
wiring easier.

The end(s) of the primary winding are provided with inserts


accuracy ± voltage ± phase displacement
(M10) made of copper or brass alloy, and located at the top
class error (%) (minutes)
of the resin body.
0,2 0,2 10
0,5 0,5 20
A M8 grounding screw is available on the bottom plate for
1 1 40
grounding the voltage transformer. Grounding can take
place directly on the frame of the switchgear or on a separate
grounding bar. 1.4.3.5 Rated Output
The value of the apparent power (in VA at a specified power
factor), which the transformer is intended to supply to the
1.4.3 Definitions secondary circuit at the rated secondary voltage, and with
rated burden connected to it.
1.4.3.1 Highest Voltage for Equipment
The highest r.m.s. phase to phase voltage for which a
­transformer is designed with respect to its insulation. 1.4.3.6 Rated Burden
The apparent resistance of the connected burden including
the wiring on which the accuracy requirements are based.
1.4.3.2 Rated Primary and Secondary Voltage
The value of the primary and secondary voltage, which
appears in the designation of the transformer, and on which 1.4.3.7 Thermal Limiting Output
its performance is based. The values are indicated in the The value of the apparent power with reference to the rated
transformer rating plate. voltage, which can be taken from a secondary winding at
the applied rated primary voltage, without exceeding the
limitations of the rise in temperature.

12
1.4.3.8 Rated Thermal Limiting Output of the
Residual Voltage Winding
The thermal limiting output of the residual winding shall be
specified in volt ampere (VA) in relation to the secondary
voltage with the unit power factor. The preferred values are
given in the IEC-Standard.
Since the residual windings are connected in an open delta
circuit, these windings are only loaded under fault conditions.
Therefore, a maximum duration of 8 hours for example, can Secondary part with earthing terminal of the voltage transformer types
be chosen. VES/VEN

1.4.3.9 Rated Voltage Factor 1.4.5 Ferroresonances


The rated voltage factor is determined by the maximum In electrical installations ferroresonances can occur if the
operating voltage depending on the system grounding following criteria are present:
­conditions. In single pole insulated transformers, it is ­common • Use of single pole insulated voltage transformer
practice to use a rated voltage factor of 1,9 x the rated • The network is ungrounded (insulated neutral starpoint)
­voltage for a load duration of 8 hours. The rated factor is • Voltage surges caused by prior switching operations
defined as 1,2 . UN for all other types.
In such a case an oscillating circuit between the earth ­capacity
(Ce) and the transformer inductance (Lw) will occur, which
1.4.3.10 Reconnection of Voltage
will lead to a very intensive voltage increase and subsequently,
Transformer
saturation of the iron core of the transformer. Overheating
Due to dielectric reasons the reconnection of a voltage
of the iron core as well as the materials used inside the
­transformer is only possible by secondary tapping.
primary winding is the consequence. The high temperature
A N leads to the destruction of the resin matrix. Flashover of the
high voltage to the grounded iron core and the secondary
winding will occur. The resulting pressure increase inside
the resin body leads to bursting of the resin body.

To avoid such damage the transformers can be equipped


a1 a2 n with a residual winding connected in an open delta circuit
and equipped with a dumping device (resistor, reactor or a
The ends of the winding are connected to the secondary
combination of the two). The design of this device depends
­terminals. Changeover will be performed at the ­secondary
on the thermal limiting output of the residual winding.
side. In the case that the primary rated voltage is to be
changed to the lower voltage, the accuracy class remains
unchanged. The rated burden decreases at approximately
the square value of the reduction in the primary voltage.
da dn da dn da dn
1.4.4 Service and Grounding
Contrary to current transformers, voltage transformers must
RD
never be short circuited to the secondary side. The “N”
t­erminal is grounded to the bottom plate in the secondary Attention: To avoid a secondary short circuit it must be
terminal box and may never be removed when in service. strictly observed that the open delta circuit is only grounded
once.
Each secondary terminal can be grounded inside the
­secondary terminal box.

Medium Voltage Instrument Transformers 13


1.5 Service Conditions

All current and voltage transformers are designed in accor­ Formula


dance with the conditions described in the international
standards.

The transformers are classified in two categories as given in U BIL under atmospheric reference
the following table. Uk BIL under service location
Ka altitude correction factor according to the above graph
Transformers for indoor applications
• Lowest temperature - 5°C Example:
• Highest temperature + 40°C For a BIL of 75 kV (1,2/50 µs) at 2500 meters above sea level a
• Relative humidity/24 hours 95% ­corrected value of 90 kV must be chosen. (75 kV ·1,2 = 90 kV)
• Relative humidity/months 90%
1.6 Test Voltages and Insulation Levels
Transformers for outdoor applications
for Instrument Transformers
• Lowest temperature -25/-40°C
In order to guarantee safe operation of an instrument
• Highest temperature + 40°C
­transformer throughout its designed lifetime, the following
• Relative humidity 100%
test must be carried out during type tests and routine tests.

1.5.1 Altitude • Rated lightning impulse withstand voltage test (type test)
For an installation at an altitude higher than 1000 meters • Power frequency withstand voltage test on primary and
the arcing distance under the standardized reference atmos­ secondary windings (routine test)
pheric conditions shall be determined by multiplying the • Partial discharge test (routine test)
withstand voltages required at the service location by a • Determination of errors (routine test)
factor „Ka” in accordance with the following table.
Highest voltage Power frequency Lightning
for equipment voltage impulse voltage
1,6
[kV] [kV] [kV]
1,5 7,2 20 60
12 28 75
1,4
Correction factor

17,5 38 95
1,3 24 50 125
36 70 170
1,2

1,1 1.7 Insulation Class

1 Most of the instrument transformers are designed for the


1000 1500 2000 2500 3000 3500 4000 4500
insulation class „E” as described in the IEC-standard, whereby
Altitude at side
the absolute maximum temperature is 115 °C.
Altitude correction factor
The maximum temperature increase must not exceed 75° K
at an ambient temperature of 40 °C.

14
1.8 Partial Discharge Test

In spite of a safety view of the dielectric of an instrument


transformer, a partial discharge test has to be carried out.
Such a test is required for all transformers with a rated
­voltage higher than 3.6 kV. The max. permissible levels are
listed in the following table.

Instrument Transformer Test Voltage Partial Discharge


Type 1 Minute Level (pC)
Current Transformer 1,2 . Um 50
Single Pole
1,2 . Um/√3 20
Voltage Transformer
Double Pole
1,2 . Um 20
Voltage Transformer

1.9 Standards

Current and voltage transformers are generally designed in


accordance with the following standards:

• IEC 60044-1 “current transformers”


• IEC 60044-2 “inductive voltage transformers”
• ANSI/IEEE-standard
• All other relevant worldwide standards

Handling after Receipt:


All transformers are suitably packed for transportation.
The packaging should be inspected immediately upon receipt
for any damages caused in during transportation.
Should any external damage(s) be found or any signs of
improper handling are present, please notify
Ritz Instrument Transformers GmbH immediately.

Safety Advice
Hazardous voltage occurs in this electrical equipment during
operation. Violation of the service instructions can result in
property damage, severe personal injury or even death.
Only qualified personnel should work on or around this
equipment, and only after becoming thoroughly familiar
with warnings, safety notices, and maintenance procedures.

The successful and safe operation of this equipment depends


on proper handling, installation, operation, and maintenance.

Medium Voltage Instrument Transformers 15


2.0 Products

Design Um (kV) Type Page

Current Transformer for Indoor Applications


Support Type Current Transformer 12 | 17,5 | 24 | 36 | 40,5 ASS 12 | 17,5 | 24 | 36 | 18
Indoor 40,5
Block Type
Narrow Type
DIN 42600, Part 8, available as Size 1, 2, 3
Support Type Current Transformer 3,6 | 7,2 | 12 GSW 12/0 19
Indoor
Block Type
Small Type
DIN 42600, Part 4
Support Type Current Transformer 12 | 17,5 | 24| 36 ASN 12 | 17,5 | 24 | 36 20
Indoor
Block Type
Large Type
DIN 42600, Part 5
Current Transformer 52 | 72,5 GI 52 | 72,5 21
Indoor
Head Type

High Current Transformer 12 | 17,5 | 24 GSSO 12 | 17,5 | 24 22


Indoor

Bushing Type Current Transformer 12 | 17,5 | 24| 36 GDS 12 | 17,5 | 24 | 36 23


Indoor

Current Transformer for Outdoor Applications


Support Type Current Transformer 12 | 17,5 | 24 | 36 GIFK 12 | 17,5 | 24 | 36 24
Outdoor
Compact Type

Support Type Current Transformer 12 | 17,5 | 24 | 36 GIFS 12 | 17,5 | 24 | 36 25


Outdoor
Standard Type

Head Type 10 | 17,5 | 20 | 30 | 36| GIF 10 | 17,5 | 20 | 30 | 26


Outdoor 52 | 72,5 36 | 52 | 72,5
GOST certificate available

16
Design Um (kV) Type Page

Voltage Transformer Single Pole


Indoor
Indoor 12|17,5|24 VES 12|17,5|24 27
Single Pole
Narrow Type
DIN 42600, Part 9

Indoor 3,6|7,2|12 GSE 12/0 28


Single Pole
Small Type
DIN 42600, Part 7

Indoor 12|17,5|24|36 VEN 12|17,5|24|36 29


Single Pole
Large Type
DIN 42600, Part 3
VEN 52 and 72,5 not according DIN 52 | 72,5 VEN 52 |72,5

Outdoor
Outdoor 12|17,5|24|36 VEF 12|17,5|24|36 30
Single Pole
GOST Certificate available

Outdoor 52 | 72,5 VEF 52 | 72,5 31


Single Pole
Head Type

Voltage Transformer Double Pole


Indoor
Indoor 12 |17,5 | 24 VZS 12|17,5|24 32
Double Pole
Narrow Type
DIN 42600, Part 9

Indoo 3,6 | 7,2 | 12 GSZ 12/0 33


Double Pole
Small Type
DIN 42600, Part 7

Indoor 12| 17,5 | 24 | 36 VZN 12|17,5|24|36 34


Double Pole
Large Type
DIN 42600, Part 3

Outdoor
Outdoor 12|17,5|24|36 VZF 12|17,5|24|36 35
Double Pole
GOST Certificate available

Medium Voltage Instrument Transformers 17


ASS
2.1 Current Transformer Indoor up to 72,5 kV
2.1.1 Support Type Current Transformer Indoor Block Type
ASS 12 | 17,5 | 24 | 36 | 40,5

TYPE ASS Dimensions mm


ASS 12 ASS 17,5 ASS 24 ASS 36 ASS 40,5
A 270 270 280 300 300
B 125 125 150 225 225
a 360 360 355 403 403
b 148 148 178 249 249
d1 12 12 14 14 14
H 220 220 280 390 450

TYPE ASS
ASS 12 ASS 17,5 ASS 24 ASS 36 ASS 40,5
Um kV 12 17,5 24 36 40,5
Test voltages kV 28|75 38|95 50|125 70|170 95|200
Rated Primary Current – IPN A up to 2500 up to 2500 up to 2500 up to 2500 up to 2500
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 1000 x IPN | max. 100 kA

Rated Peak Current – Idyn 2,5 x Ith


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Weight kg 20 20 28 70 70
Subject to Technical Changes

18
GSW 12/0
2.1.2 Support Type Current Transformer Indoor Block Type
GSW 12/0 3,6 | 7,2 | 12

TYPE GSW 12/0 Dimensions mm


Size 1 2 3 DIN
A 135 180 220 155
B 125 125 125 155
a 238 283 323 279
DIN - Bottom plate
b 148 148 148 178
H1 160 160 160 160
H2 180 180 180 180
L 175 220 260 220
I1 105 128 148 124
I2 82 105 125 100
I3 125 148 168 144

TYPE GSW 12/0


Size 1 2 3 DIN
Um kV 12 12 12 12
Test voltages kV 28|75 28|75 28|75 28|75
Rated Primary Current – IPN A 5 up to 800 5 up to 800 5 up to 800 5 up to 800
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 600 x IPN | max. 60 kA

Rated Peak Current – Idyn 2,5 x Ith


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden.
Frequency Hz 50|60
Weight kg 6 7 8 8
Subject to Technical Changes

Medium Voltage Instrument Transformers 19


ASN
2.1.3 Support Type Current Transformer Indoor Block Type
ASN 12 | 17,5 | 24 | 36

TYPE ASN Dimensions mm


ASN 12 ASN 17,5 ASN 24 ASN 36
A 225 225 250 300
B 175 175 200 225
a 330 330 330 403
b 198 198 198 249
d1 11 11 14 14
H 240 240 300 390

TYPE ASN
ASN 12 ASN 17,5 ASN 24 ASN 36
Um kV 12 17,5 24 36
Test voltages kV 28|75 38 | 95 50 | 125 70 | 170
Rated Primary Current – IPN A up to 1500 up to 1500 up to 1500 up to 1500
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5
Rated Secondary Current – Ith up to 1000 x IPN | max. 100 kA
Rated Peak Current – Idyn 2,5 x Ith
Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Weight kg 24 24 38 70
Subject to Technical Changes

20
GI
2.1.4 Current Transformer Indoor Head Type
GI 52 | 72,5

TYPE GI Dimensions mm
GI 52 GI 52 GI 52 GI 52
GI 52 GI 72,5 up to 600 A
725
600 A -
1250 A
1250 A -
2000 A
2000 A -
3000 A

A 175 300 L
d 622 682 722
1322
742

B 300 175 GI 72,5 GI 72,5 GI 72,5


a 230 500 L
up to 1250 A
750
2000 A -
790
3000 A
810

b 350 500 d 30 42 48

C 452 520
H1 725 900
H2 1002 1217
H3 557,5 745

TYPE GI
GI 52 GI 72,5
Um kV 52 72,5
Test voltages kV 95 | 250 140 | 325
Rated Primary Current – IPN A up to 3000
Rated Secondary Current – ISN A 1|5
Rated Short Time Thermal
Current – Ith bis 1000 x IPN | max. 100 kA

Rated Peak Current – Idyn 2,5 x Ith


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Weight kg 147 180
Subject to Technical Changes

Medium Voltage Instrument Transformers 21


GSSO
2.1.5 High Current Transformer Indoor
GSSO 12 | 17,5 | 24

TYPE GSSO Dimensions mm


Size 0 3 4
A 135 155 305
B 155 155 155
a 207 269 419
b 180 180 180
l1 150 300+2 450+3 Design d
01 102
l2 105 145 220 02 130
l3 82 102 177
l4 125 167 242

TYPE GSSO
Size 0 3 4
Um kV 12 | 24 12 | 24 12 | 24
Test voltages kV 50 | 125 50 | 125 50 | 125
Rated Primary Current – IPN A 100 up to 4000
Rated Secondary Current – ISN A 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 1000 x IPN | max. 200 kA

Rated Peak Current – Idyn 2,5 x Ith


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Weight kg 21 34 70
Subject to Technical Changes

22
GDS
2.1.6 Bushing Type Current Transformer Indoor
GDS 12 | 17,5 | 24 | 36

TYPE GDS Dimensions mm


GDS 12 GDS 24 GDS 36
Size 0 1 2 3 1 2 1
a 50 60 115 195 60 140 60
d1 180
d2 185
1500 A 190 190 255 315 255 315 315
e1 2000 A 195 195 260 320 260 320 320
2500 A 215 215 280 340 280 340 340
1500 A 150 210 270 330 270 330 330
e2 2000 A 155 215 275 335 275 335 335
2500 A 175 235 295 355 295 355 355
Weigh [kg] 12-18 16-22 28-32 34-40 28-32 35-40 35-40

TYPE GDS
GDS 12 GDS 17,5 GDS 24 GDS 36
Um kV 12 17,5 24 36
Test voltage kV 28 | 75 38 | 95 50 | 125 70 |170
Rated Primary Current – IPN A 150 A up to 2500 A | on request 3000 A
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5
Rated Short Time Thermal
up to 1000 x IPN | max. 100 kA
Current – Ith
Rated Peak Current – Idyn 2,5 x Ith
Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Subject to Technical Changes

Medium Voltage Instrument Transformers 23


GIFK
2.2 Current Transformer Outdoor up to 72,5 kV
2.2.1 Support Type Current Transformer Outdoor Compact Type
GIFK 12 | 17,5 | 24 | 36

TYPE GIFK Dimensions mm


GIFK 12| 17,5 | 24 GIFK 36
A 100 100
B 200 200
a 140 140
b 240 240
C 235 235
H 335 419

TYPE GIFK
GIFK 12 GIFK 17,5 GIFK 24 GIFK 36
Um kV 12 17,5 24 36
Test voltages kV 28|75 38|95 50|125 70|170
Rated Primary Current – IPN A up to 1250
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 1000 x IPN | max. 63 kA

Rated peak Current – Idyn 2,5 x Ith, max. 100 kA


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Creepage Distance mm 486 486 486 650
Weight kg 22 22 22 30
Subject to Technical Changes

24
GIFS
2.2.2 Support Type Current Transformer Outdoor Standard Type
GIFS 12 | 17,5 | 24 | 36

TYPE GIFS Dimensions mm


GIFS 12| 17,5 | 24 GIFS 36
A 150 150
B 300 300
a 190 190
b 335 335
C 335 335
H 355 439

TYPE GIFS
GIFS 12 GIFS 17,5 GIFS 24 GIFS 36
Um kV 12 17,5 24 36
Test voltages kV 28 | 75 38 | 95 50 | 125 70 |170
Rated Primary Current – IPN A up to 1250
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 1000 x IPN | max. 63 kA

Rated peak Current – Idyn 2,5 x Ith, max. 100 kA


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Creepage Distance mm 575 575 575 926
Weight kg 40 40 40 55
Subject to Technical Changes

Medium Voltage Instrument Transformers 25


GIF
2.2.3 Current Transformer Outdoor Head Type
GIF 10 | 17,5 | 20 | 30 | 36 | 52 | 72,5

TYPE GIF Dimensions mm


GIF 10|17,5 GIF 20 GIF 30 GIF 36 GIF 52 GIF 72,5
A 175 175 175 175 175 175
B 300 300 300 300 300 300
a 230 230 230 230 500 500
b 350 350 350 350 500 500
C 380 430 430 452 520 520
H1 437 527 527 725 910 1015
H2 5921 707 707¹ 1002 1217 1322
H3 268 358 358 557,5 745 850
up to 600 A 550 600 600 622 750 750
600 A up to 1250 A 610 660 660 682 750 750
L
1250 A up to 2000 A 650 700 700 722 790 790
2000 A up to 3000 A 670 720 720 742 810 810
¹ Without primary reconnection

TYPE GIF
GIF 10 GIF 17,5 GIF 20 GIF 30 GIF 36 GIF 52 GIF 72,5
Um kV 12 17,5 24 36 36 52 72,5
Test voltages kV 28|75 38|95 50|125 70|170 70|170² 95|250 140| 325
Rated Primary Current – IPN A up to 3000
Rated Secondary Current – ISN A 1|5 1|5 1|5 1|5 1|5 1|5 1|5
Rated Short Time Thermal
Current – Ith up to 1000 x IPN | max. 63 kA

Rated Peak Current – Idyn 2,5 x Ith, max. 100 kA


Core(s), Number of Cores Must be determined on the basis of the requirements
accuracy class, over-current value, burden
Frequency Hz 50|60
Creepage Distance mm 665 665 800 800 1290 1823 2150
Weight kg 65 65 100 115 147 180 255
² Increased BIL possible 70/200
Subject to Technical Changes

26
VES
2.3 Voltage Transformer Single Pole up to 72,5kV
2.3.1 Voltage Transformer Indoor
VES 12 | 17,5 | 24

TYPE VES Dimensions mm


VES 12 VES 17,5 VES 24
A 270 270 280
B 125 125 150
a 320 320 354
b 148 148 178
H 220 220 280

TYPE VES
VES 12 VES 17,5 VES 24
Um kV 12 17,5 24
Test voltages kV 28|28 | 75 38 | 38 | 95 50 | 50 | 125
Rated Primary Current – IPN V 10000/√3 13800/√3 20000/√3
11000/√3 15000/√3 22000/√3
Rated Secondary V
100/√3 | 110/√3
Voltage – USN
Rated Secondary Voltage V
for the Earthing Corens 100/3 | 110/3

Rated Output in Accuracy 0,2 VA 20 20 20


Class (IEC) 0,5 VA 50 50 50
1,0 VA 100 100 100
Thermal Limit Current A 6 6 6

Thermal Limit Current at A 6 6 6


1,9 x Un / 8h
Frequency Hz 50|60
Weight kg 19 19 27
Subject to Technical Changes

Medium Voltage Instrument Transformers 27


GSE
2.3.2 Voltage Transformer Indoor
GSE 12/0 3,6 | 7,2 |12

DIN - Bottom plate

TYPE GSE Dimensions mm


GSE 12/0 GSE 12/0 DIN
A 260 155
B 140 155
a 312 286
b 188 188
H 160 160
l1 152 152
l2 102 102
l3 171 171
l4 140 100

TYPE GSE
GSE 12|0
Um kV 2
Test voltages kV 28|75
Rated Primary Voltage – UPN V 3000/√3 | 5000/√3
6000/√3 | 10000/√3
Rated Secondary V
100/√3 | 110/√3
Voltage – USN
Rated Secondary Voltage V
for the Earthing Core (en) 100/3 | 110/3

Rated Output in Accuracy 0,2 VA 30


Class (IEC) 0,5 VA 90
1,0 VA 180
Thermal Limit Current A 7

Thermal Limit Current at A 6


1,9 x Un / 8h
Frequency Hz 50|60
Weight kg 18
Subject to Technical Changes

28
VEN
2.3.3 Voltage Transformer Indoor
VEN 12 | 17,5 | 24 | 36 | 52 | 72,5

TYPE VEN Dimensions mm


VEN 12 VEN 17,5 VEN 24 VEN 36 VEN 52 VEN 72,5
A 225 225 250 300 300 300
B 175 175 200 225 225 225
a 355 355 355 400 400 400
b 200 200 230 250 280 280
H 240 240 273 321 522 722

VEN up to 36 kV VEN up to 72,5 kV

TYPE VEN
VEN 12 VEN 17,5 VEN 24 VEN 36 VEN 52 VEN 72,5
Um kV 12 17,5 24 36 52 72,5
Test voltages kV 28|75 38|95 50|125 70|170 95|250 140 | 325
Rated Primary Voltage –UPN V 10000/√3 13800/√3 20000/√3 30000/√3 45000/√3 60000/√3
11000/√3 15000/√3 22000/√3 33000/√3 50000/√3 66000/√3
Rated Secondary V
Voltage –USN 100/√3 | 110/√3

Rated Secondary Voltage V


for the Earthing Core(en) 100/3 | 110/3

Rated Output in Accuracy 0,2 VA 30 30 30 30 45 45


Class (IEC) 0,5 VA 100 100 100 100 100 100
1,0 VA 200 200 200 200 200 200
Thermal Limit Current A 10 10 10 10 10 10

Thermal Limit Current at A 9 9 9 9 9 9


1,9 x Un / 8h
Frequency Hz 50|60
Weight kg 24 24 32,5 50 75 85
Subject to Technical Changes

Medium Voltage Instrument Transformers 29


VEF
2.3.4 Voltage Transformer Outdoor
VEF 12 | 17,5 | 24 | 36

TYPE VEF Abmessungen mm


VEF 12 VEF 17,5 VEF 24 VEF 36
A 270 270 270 270
B 160 160 160 200
a 310 310 310 320
b 185 185 185 240
H 380 490 490 622

TYPE VEF
VEF 12 VEF 17,5 VEF 24 VEF 36
Um kV 12 17,5 24 36
Test voltages kV 28|75 38|95 50|125 70|170
Rated Primary Voltage – UPN 10000/√3 13800/√3 20000/√3 30000/√3
V
11000/√3 15000/√3 22000/√3 33000/√3
Rated Secondary
Voltage –USN V 100/√3 | 110/√3

Rated Secondary Voltage


for the Earthing Core (en) V 100/3 | 110/3

Rated Output in Accuracy 0,2 VA 40 40 40 50


Class (IEC) 0,5 VA 100 100 100 100
1,0 VA 200 200 200 200
Thermal Limit Current
A 6 9 9 10

Thermal Limit Current at


1,9 x Un / 8h A 6 6 6 10

Frequency Hz 50|60
Creepage Distance mm 400 745 745 950
Weight kg 33,5 35,5 35,5 51
Subject to Technical Changes

30
VEF
2.3.5 Voltage Transformer Outdoor Head Type
VEF 52 | 72,5

TYPE VEF Dimensions mm


VEF 52 VEF 72,5
A 300 300
B 175 175
a 500 500
b 500 500
D1 450 450
H 1217 1322

TYPE VEF
VEF 52 VEF 72,5
Um kV 52 72,5
Test voltages kV 95|250 140 | 325
Rated Primary Voltage – UPN 45000/√3 60000/√3
V
50000/√3 66000/√3
Rated Secondary
Voltage –USN V 100/√3 | 110/√3

Rated Secondary Voltage


for the Earthing Core (en) V 100/3 | 110/3

Rated Output in Accuracy 0,2 VA 80 60


Class (IEC) 0,5 VA 200 160
1,0 VA 400 320
Thermal Limit Current
A 12 12

Thermal Limit Curre nt at


1,9 x Un / 8h A 9 9

Frequency Hz 50|60
Creepage Distance mm 1910 2350
Weight kg 170 200
Subject to Technical Changes

Medium Voltage Instrument Transformers 31


VZS
2.4 Voltage Transformer Double Pole up to 36 kV
2.4.1 Voltage Transformer Indoor
VZS 12 | 17,5 | 24

TYPE VZS Dimensions mm


VZS 12 VZS 17,5 VZS 24
A 270 280 280
B 125 150 150
a 320 354 354
b 148 178 178
C 100 165 165
d 110 130 130
H 220 230 280

TYPE VZS
VZS 12 VZS 17,5 VZS 24
Um kV 12 17,5 24
Test voltages kV 28|28|75 38|38|95 50|50|125
Rated Primary Voltage – UPN 10000 13800 20000
V
11000 15000 22000
Rated Secondary
Voltage – USN V 100 | 110

Rated Secondary 0,2 VA 20 20 20


Voltage Class (IEC) 0,5 VA 50 50 50
1,0 VA 100 100 100
Thermal Limit Current A 4 4 4
Frequency Hz 50|60
Weight kg 19 27 27
Subject to Technical Changes

32
GSZ
2.4.2 Voltage Transformer Indoor
GSZ 12/0 3,6 | 7,2 | 12

DIN - Bottom plate

TYPE GSZ Dimensions mm


GSZ 12/0 GSZ 12/0 DIN
A 255 155
B 140 150
a 312 286
b 188 188
C 150 150
H 160 160
l1 152 152
l2 102 100
l3 171 171
l4 140 100

TYPE GSZ
GSZ 12
Um kV 12
Test voltages kV 28|28|75
Rated Primary Voltage – UPN
V 3000 | 5000 | 6000 | 10000

Rated Secondary
Voltage – USN V 100 | 110

Rated Secondary 0,2 VA 10


Class (IEC) 0,5 VA 45
1,0 VA 150
Thermal Limit Current A 4
Frequency Hz 50|60
Weight kg 18
Subject to Technical Changes

Medium Voltage Instrument Transformers 33


VZN
2.4.3 Voltage Transformer Indoor
VZN 12 | 17,5 | 24 | 36

TYPE VZN Dimensions mm


VZN 12 VZN 17,5 VZN 24 VZN 36
A 225 225 250 300
B 175 175 200 225
a 355 355 355 400
b 200 200 230 349
d 150 150 210 320
H 240 240 273 390

TYPE VZN
VZN 12 VZN 17,5 VZN 24 VZN 36
Um kV 12 17,5 24 36
Test voltages kV 28|28|75 38|38|95 50|50|125 70|70|170
Rated Primary Voltage – UPN 10000 13800 20000 30000
V
11000 15000 220003 33000
Rated Secondary
Voltage – USN V 100 | 110

Rated Secondary Voltage 0,2 VA 30 30 30 30


Class (IEC) 0,5 VA 100 100 100 100
1,0 VA 200 200 200 200
Thermal Limit Current A 6 6 6 6
Frequency Hz 50|60
Weight kg 26 26 32,5 70
Subject to Technical Changes

34
VZF
2.4.4 Voltage Transformer Outdoor
VZF 12 | 17,5 | 24 | 36

TYPE VZF Dimensions mm


VZF 12 VZF 17,5 VZF 24 VZF 36
A 270 270 270 270
B 160 160 160 200
a 310 310 310 320
b 185 185 185 240
C 190 320 320 400
H 380 490 490 622

TYPE VZF
VZF 12 VZF 17,5 VZF 24 VZF 36
Um kV 12 17,5 24 36
Test voltages kV 28|28|75 38|38|95 50|50|125 70|70|170
Rated Primary Voltage –UPN 10000 13800 20000 30000
V
11000 15000 220003 33000
Rated Secondary
Voltage –USN V 100 | 110

Rated Output in Accuracy 0,2 VA 40 40 40 50


Class (IEC) 0,5 VA 100 100 100 100
1,0 VA 200 200 200 200
Thermal Limit Current
A 6 6 6 6

Frequency Hz 50|60
Creepage Distance mm 400 745 745 900
Weight kg 34 37 37 57
Subject to Technical Changes

Medium Voltage Instrument Transformers 35


RITZ Product Overview

Low Volta­ge In­stru­m­ent Trans­­for­mers

Low-Voltage Instrument Transformers up to 1.2 kV


c.t.s for measuring and protection purposes
• Wound primary c.t. • Auxiliary c.t.
• Summation c.t. • Window type c.t.
• C.t.s for switch fuses • Tube type c.t.
• Multi-range c.t. • Split-core c.t.
• Window type c.t.s for high currents
• Split core types for earth fault protection

36
RITZ Product Overview

Cast Resin Bus Bar Systems up to 72,5 kV & 6500 A

The Alternative to Parallel-Connected Cables 1 5 2 4 3

The RITZ Solid Insulated Bus Bar System especially


offers for transmission of higher currents and/or limited
space requirements a cost-effective and safe alternative to
parallel-connected cable systems, metal-enclosed bus bar or
bus duct systems.

RITZ Service 1. Conductor


• Minimized project engineering for YOU as customer 2. Epoxy-impregnated paper
wrapping
due to complete engineering service for bus bar routing 3. Earth layer
Bus Bar Design Principle 4. Capacitive grading
including fixation system as 3D CAD model. 5. End ring – Metal ring
• Providing complete Installation documentation
• Supervisor support on request available
• Installation team on request available

System Specific Benefits


• Compact design
• Reduced requirements for the installation space
• Small bending radii
• 3-dimensional geometric shape is possible
• Natural cooling due to effectual conductor design
• High opererational reliability due to factory routine
test of each bus bar
• No maintenance A

Safety Benefits
• Touch Safe 3
• Fully insulated and capacitive graded system
2
• High thermal and dynamic short circuit current withstand
capabilities
• Excluded phase to phase short-circuits Section A-B
• No toxic fumes in case of fire - self extinguishing 1

• High operating reliability due to routine tests for each 1. Plastic fixing clamps
bus bar element Bus Bar Fixing 2. Aluminium
3. Aluminium fixing angles

Installation
• Easy installation due to standardized installation and
fixing parts

Medium Voltage Instrument Transformers 37


RITZ Product Overview

Cast Resin Insulated Power Transformers up to 40,5 kV

Cast Resin Power Transformers 50 kVA up to 25 MVA Characteristics


RITZ produces transformers in Glass Fibre reinforced • mpulse voltage proof
Vacuum Technology (GVT) for ratings up to 25 MVA and • Partial discharge free
for a maximum system voltage of 40,5 kV voltage class • Short circuit proof
• Highest mechanical strength
Applications • Cooling channels in HV&LV coils
• Power Distribution • Traction Power Systems • Pre-galvanised steel frame
• Rectifier Drives (Streetcar, Tram, Metro, Railway)
• Oil Platforms / Vessels • Generator Excitation RITZ transformers are designed according to the required
• Injection Systems • Transmitter Systems international specifications like DIN/VDE or IEC.
• Grounding Systems • Laboratory Systems Further more they fulfil all climatic, environmental and fire
protection requirements:
Customer oriented package solutions • Enviromental class E2
• Transformer Installation • Climate class C2
• Disposal of existing oil and PCB transformers • Fire protection class F1
• Start-up • Basic impulse level List 2
The requirements of the environmental protection is taken
Glass Fibre reinforced Vacuum Technology (GVT) is used for Glass Fibre reinforced Vacuum Technology (GVT) is used for
High Voltage coils and optionally for Low Voltage coils in into account for design of the RITZ cast resin transformers.
order to guarantee the highest possible quality and reliability
to avoid cracks or voids during manufacturing and service. Special Transformers
• Injection transformers for ripple control applications
• Reactors for ripple control applications
• High current transformers
• Earthing transformers
• Medium frequency transformers
• Filter and blocking reactors
• Smoothing and interphase reactors

38
RITZ Product Overview

Electronic Instrument Transformers and Sensor


Voltage-Sensoric Current-Sensoric Block-Type Multi Sensor
• Voltage up to 90 kV • Current up to 24000 A The sensor provides signals for current and voltage
• Accuracy of 0,2 % • Accuracy of 0,01 % measurement as well as voltage reference for electronic
• Frequen y from a to 10kHz • Frequency from a to 10kHz protection relays.

Applications Current measurement


• Power Engineering • Grid Analyse • Using a Rogowski coil
• Protection Technology • Electrochemistry
• Switchgear Systems • Automobile Industry Voltage measurement
• Environment Engineering • Research • Using an ohmic voltage divider
• Rail Transportation Power Supply
Voltage reference
• Using a coupling electrode

Cast Resin Parts


We develop and formulate casting resin molding materials
for electrical applications in the low and medium voltage
range and for electronics, We sketch and produce casting
resin-isolated devices and shaped parts for application in
electrical energy engineering for example special bushings.
fuse housings etc.

Medium Voltage Instrument Transformers 39


Sales
HAMBURG

Cast Resin Insulated Bus Bar Systems

Cast Resin Power Transformers


Low Voltage Instrument Transformers

Medium Voltage Instrument Transformers

Customised Cast Resin Parts


Electronic Insrtument Transformers and Sensor
Instrument Transformers GmbH
Wandsbeker Zollstraße 92-98
22041 Hamburg
GERMANY
Tel +49 40 51123-0
Fax +49 40 51123-333 Medium Voltage
Fax +49 40 51123-111 Low Voltage

WIRGES
Instrument Transformers GmbH
Siemensstraße 2
56422 Wirges
GERMANY
Tel +49 2602 679-0
Fax +49 2602 9436-00

DRESDEN
Instrument Transformers GmbH
Bergener Ring 65–67
01458 Ottendorf-Okrilla
GERMANY
Tel +49 35205 62-0
Fax +49 35205 62-216

KIRCHAICH
Instrument Transformers GmbH
Mühlberg 1
97514 Oberaurach-Kirchaich
GERMANY
Tel +49 9549 89-0
Fax +49 9549 89-11

MARCHTRENK
Instrument Transformers GmbH
Linzer Straße 79
4614 Marchtrenk
AUSTRIA
Tel +43 7243 52285-0
Fax +43 7243 52285-38

KECSKEMÉT
Instrument Transformers Kft.
Technik-Park Heliport
6000 Kecskemét-Kadafalva
HUNGARY
Tel +36 76 5040-10
Fax +36 76 470311

SHANGHAI
Instrument Transformers
Shanghai Co. Ltd.
99 Huajia Road, Building 1-3, Huabin Industrial Park
Songjiang Industrial Zone
Shanghai, 201613
P.R. China
Tel +86 21 67747698
Fax +86 21 67747678

HARTWELL
Instrument Transformers Inc.
25 Hamburg Avenue
Lavonia, GA 30553
USA
Tel +1 706-356-7180
Fax +1 866-772-5245

[email protected] www.ritz-international.com

Rev_2014-01 | JSW

You might also like