0% found this document useful (0 votes)
83 views12 pages

Schneider Electric - EasyPact-MVS - MVS32N3MF2L

Uploaded by

anwar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views12 pages

Schneider Electric - EasyPact-MVS - MVS32N3MF2L

Uploaded by

anwar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Product datasheet

Specifications

Circuit breaker, EasyPact MVS, 3


Poles, 3200A, 50kA, MF, ET2, fixed,
manual
MVS32N3MF2L

Main
Range EasyPact

Product name MVS32N

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name MVS32N

Product or component type Circuit breaker

Device application Distribution

Poles description 3P

Protected poles description 3P 3d

[In] rated current 3200 A at 40 °C

Network type AC

[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code N

Suitability for isolation Yes conforming to IEC 60947-2

Utilisation category Category B

Trip unit name ET2I

Trip unit technology Electronic

Trip unit rating 3200 A

Complementary
Network frequency 50/60 Hz

Control type Manually operated

Mounting mode Fixed

Mounting support Base plate


Rail

Connection position Vertical


Horizontal

Location of connection Rear

[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 12 kV conforming to IEC 60947-2


voltage
Circuit breaker CT rating 3200 A

Breaking capacity 50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
capacity

Dec 26, 2024 1


AD
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2

Electrical durability Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC
60947-2
Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC
60947-2

Connection pitch 115 mm without spreader

Contact position indicator Yes

[Icm] rated short-circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
capacity
[Icw] rated short-time withstand 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
current 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2

Trip unit protection functions LI

Protection type Overload protection (long time)


Instantaneous short-circuit protection

Fault indication Short-circuit


Overload
Internal fault

Long time pick-up adjustment Adjustable 9 settings


type Ir
Long time pick-up adjustment 0.4...1 x In
range
Long time delay adjustment type Adjustable 9 settings

[tr] long-time delay adjustment 0.5…24 s at 6 x Ir


range
Thermal memory 20 minutes before and after tripping

Instantaneous pick-up adjustment Adjustable 9 settings


type Ii
Instantaneous pick-up adjustment 1.5...10 x Ir
range
Zone selective interlocking ZSI With

Current sensor rating range 1000/4000 A

Maximum breaking time 25 ms

Maximum closing response time 70 ms

Height 352 mm

Width 422 mm

Depth 297 mm

Net weight 60 kg

Environment
Standards IEC 60947-2

Product certifications CCS


CCC
IEC
GOST

Pollution degree 4 conforming to IEC 60664-1

IP degree of protection IP40

Ambient air temperature for -5…70 °C


operation
Ambient air temperature for -40…85 °C without control unit
storage -25…85 °C with control unit

Packing Units

2 Dec 26, 2024


AD
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 42.0 cm

Package 1 Width 35.0 cm

Package 1 Length 50.0 cm

Package 1 Weight 38.0 kg

Contractual warranty
Warranty 18 months

Dec 26, 2024 3


AD
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain
partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use
Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint (kg.eq.CO2


5424
per CR, Total Life cycle)

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled


Yes
cardboard

Packaging without single use


No
plastic

EU RoHS Directive Compliant with Exemptions

SCIP Number 3f2d539a-6ab5-46aa-8603-9354f4ae3294

REACh Regulation REACh Declaration

China RoHS Regulation China RoHS declaration

PVC free Yes

Use Again

Repack and remanufacture

4 Dec 26, 2024


AD
Circularity Profile End of Life Information

Take-back No

Dec 26, 2024 5


AD
Product datasheet MVS32N3MF2L

Dimensions Drawings

6 Dec 26, 2024


AD
Product datasheet MVS32N3MF2L

Assembly

Dec 26, 2024 7


AD
Product datasheet MVS32N3MF2L

Performance Curves

8 Dec 26, 2024


AD
Product datasheet MVS32N3MF2L

Offer Marketing Illustration

Product benefits / Features

Dec 26, 2024 9


AD
Product datasheet MVS32N3MF2L

Offer Marketing Illustration

Product benefits / Features

10 Dec 26, 2024


AD
Product datasheet MVS32N3MF2L

Offer Marketing Illustration

Product benefits / Features

Dec 26, 2024 11


AD
Product datasheet MVS32N3MF2L

Offer Marketing Illustration

Product benefits / Features

12 Dec 26, 2024


AD

You might also like