Product datasheet
Specifications
Circuit breaker, EasyPact MVS, 3
Poles, 3200A, 50kA, MF, ET2, fixed,
manual
MVS32N3MF2L
Main
Range EasyPact
Product name MVS32N
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name MVS32N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
[In] rated current 3200 A at 40 °C
Network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET2I
Trip unit technology Electronic
Trip unit rating 3200 A
Complementary
Network frequency 50/60 Hz
Control type Manually operated
Mounting mode Fixed
Mounting support Base plate
Rail
Connection position Vertical
Horizontal
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand 12 kV conforming to IEC 60947-2
voltage
Circuit breaker CT rating 3200 A
Breaking capacity 50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
capacity
Dec 26, 2024 1
AD
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC
60947-2
Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC
60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
capacity
[Icw] rated short-time withstand 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
current 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
Protection type Overload protection (long time)
Instantaneous short-circuit protection
Fault indication Short-circuit
Overload
Internal fault
Long time pick-up adjustment Adjustable 9 settings
type Ir
Long time pick-up adjustment 0.4...1 x In
range
Long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment 0.5…24 s at 6 x Ir
range
Thermal memory 20 minutes before and after tripping
Instantaneous pick-up adjustment Adjustable 9 settings
type Ii
Instantaneous pick-up adjustment 1.5...10 x Ir
range
Zone selective interlocking ZSI With
Current sensor rating range 1000/4000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 352 mm
Width 422 mm
Depth 297 mm
Net weight 60 kg
Environment
Standards IEC 60947-2
Product certifications CCS
CCC
IEC
GOST
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
Ambient air temperature for -5…70 °C
operation
Ambient air temperature for -40…85 °C without control unit
storage -25…85 °C with control unit
Packing Units
2 Dec 26, 2024
AD
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 42.0 cm
Package 1 Width 35.0 cm
Package 1 Length 50.0 cm
Package 1 Weight 38.0 kg
Contractual warranty
Warranty 18 months
Dec 26, 2024 3
AD
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain
partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use
Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg.eq.CO2
5424
per CR, Total Life cycle)
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled
Yes
cardboard
Packaging without single use
No
plastic
EU RoHS Directive Compliant with Exemptions
SCIP Number 3f2d539a-6ab5-46aa-8603-9354f4ae3294
REACh Regulation REACh Declaration
China RoHS Regulation China RoHS declaration
PVC free Yes
Use Again
Repack and remanufacture
4 Dec 26, 2024
AD
Circularity Profile End of Life Information
Take-back No
Dec 26, 2024 5
AD
Product datasheet MVS32N3MF2L
Dimensions Drawings
6 Dec 26, 2024
AD
Product datasheet MVS32N3MF2L
Assembly
Dec 26, 2024 7
AD
Product datasheet MVS32N3MF2L
Performance Curves
8 Dec 26, 2024
AD
Product datasheet MVS32N3MF2L
Offer Marketing Illustration
Product benefits / Features
Dec 26, 2024 9
AD
Product datasheet MVS32N3MF2L
Offer Marketing Illustration
Product benefits / Features
10 Dec 26, 2024
AD
Product datasheet MVS32N3MF2L
Offer Marketing Illustration
Product benefits / Features
Dec 26, 2024 11
AD
Product datasheet MVS32N3MF2L
Offer Marketing Illustration
Product benefits / Features
12 Dec 26, 2024
AD