TNBJ GF1 Unit 2 Outage Valve Service Report (TMS)
TNBJ GF1 Unit 2 Outage Valve Service Report (TMS)
Prepared By :-
Reported Complaint(s);-
Valve Passing
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Valve Passing
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Valve Passing
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
The valve has been dismantled for further inspection and servicing works
Found minor scratches with carbon stain on the valve plugs and seats contact surface
There's no unsual findings on the other valve parts
QP29.078R2
SERVICE REPORT PAGE 3 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
Lapping works was performed on the plugs and seats contact surface
Contact check for the valve plug and seat was done with client representative
New pressure seals and gland packing were installed as replacements
The valve was reassembled to its original position and orientation
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Valve Passing
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
The motorized unit has been detached before dissamble valve works
The valve has been dismantled for further inspection and servicing works
Found light scratches on the valve plug contact surface area
Discovered a flaw on the valve seat contact surface
QP29.078R2
SERVICE REPORT PAGE 3 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Valve Passing
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
The valve plug and seat contact surface has been performed polishing works
The steam cut area on the seat ring pocket has been fixed
Contact check for the valve plug and seat was done with client representative
New spiral wound gaskets and gland packing were installed as replacements
The valve was reassembled to its original position and orientation
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Valve Jerking
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
Lapping works was performed on the plug and seat contact surface
Grinding works has been carried out on the internal of the nozzle cap
Contact check for the valve plug and seat was done with client's representative
New gland packing and flange gaskets were installed as replacements
The valve was reassembled to its original position and orientation
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Gland Leak
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
The old gland packing has been removed from the valve gland
QP29.078R2
SERVICE REPORT PAGE 3 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
REPACKING WORKS
The valve gland area has been cleaned from any debris before repacking works
New gland packing has been installed to adequate numbers
The gland packing follower nuts were tightened accordingly
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :
Reported Complaint(s);-
Gland Leak
Available Available
1. Inspection 4. Testing
1. Serenia Workshop
Service Location
2. Other Location (specify) Unit 2 Turbine Area
Remark(s)
QP29.078R2
SERVICE REPORT PAGE 2 of 4
The old gland packing has been removed from the valve gland
QP29.078R2
SERVICE REPORT PAGE 3 of 4
Other(s)
Applicable
B. ACTUATOR
Not Applicable
Actuator Parts Qty Actuator Parts Qty
N/A N/A
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
N/A N/A
Touch up /
Blasting Machining
Refurbish Painting
*Please select if applicable: Required/ Not Required
Required
Testing
Not Required
Other(s)
Applicable
C. INSTRUMENTATION CONTROLS
Not Applicable
Instrumentation Parts Qty Instrumentation Parts Qty
Parts To Be N/A N/A
Replaced N/A N/A
N/A N/A
Required
Testing
Not Required
Other(s)
QP29.078R2
SERVICE REPORT PAGE 4 of 4
REPACKING WORKS
The valve gland area has been cleaned from any debris before repacking works
New gland packing has been installed to adequate numbers
The gland packing follower nuts were tightened accordingly
QP29.078R2
SERVICE REPORT PAGE 4 of 4
APPENDIX (ATTACHED) :