Ieee 622B
Ieee 622B
Sponsor
Energy Development and Power Generation Committee
of the
IEEE Power Engineering Society
© Copyright 1989 by
The Institute of Electrical and Electronics Engineers, Inc
345 East 47th Street, New York, NY 10017, USA
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the
prior written permission of the publisher.
IEEE Standards documents are developed within the Technical Committees of the IEEE Societies and the Standards
Coordinating Committees of the IEEE Standards Board. Members of the committees serve voluntarily and without
compensation. They are not necessarily members of the Institute. The standards developed within IEEE represent a
consensus of the broad expertise on the subject within the Institute as well as those activities outside of IEEE which
have expressed an interest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply that there are no other
ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE
Standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change
brought about through developments in the state of the art and comments received from users of the standard. Every
IEEE Standard is subjected to review at least every five years for revision or reaffirmation. When a document is more
than five years old, and has not been reaffirmed, it is reasonable to conclude that its contents, although still of some
value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership affiliation
with IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with
appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate to
specific applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate
action to prepare appropriate responses. Since IEEE Standards represent a consensus of all concerned interests, it is
important to ensure that any interpretation has also received the concurrence of a balance of interests. For this reason
IEEE and the members of its technical committees are not able to provide an instant response to interpretation requests
except in those
IEEE Standards documents are adopted by the Institute of Electrical and Electronics Engineers without regard to
whether their adoption may involve patents on articles, materials, or processes. Such adoption does not assume
any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the standards
documents.
Foreword
(This Foreword is not a part of IEEE Std 622B-1988. IEEE Recommended Practice for Testing and Startup Procedures for Electric
Heat Tracing Systems for Power Generating Stations).
In a continuing effort to provide pertinent recommended practices to the industry on the design and installation of
electric heat tracing systems (see ANSI/IEEE Std 622-1987 and ANSI/IEEE Std 622A-1984, ANSI IEEE Std 515-
1983, ANSI/IEEE Std 844-1985), the Electric Heat Tracing Working Group of the Power Generation Committee
began an investigation in 1984 into startup and commissioning testing techniques for systems in power generating
stations. This investigation covered such areas as testing of materials and components on receipt at the job site, testing
and verifying design of systems before and after installation, and periodic testing of systems after commissioning.
This recommended practice is a detailed summary of the said techniques and is offered to the user in the installation,
commissioning, and periodic surveillance areas of operation. Electric heat tracing systems play an important part in
the operation of power generating stations and other process industries.
While this recommended practice is written for power generating stations, the techniques presented can be used on
electric heat tracing systems in any application. Since electric heat tracing systems are interrelated with electric power
and alarm systems, other IEEE standards should be referred to when using this recommended practice.
The recommendations herein are not intended to supersede any current IEEE standard-or practice and sound
engineering judgment should always be used when applying this or any other IEEE standard.
This recommended practice correlates industry practices; it is not intended to be an exhaustive compilation or a rigid
procedure manual. The document was prepared by the Working Group on Electric Heat Tracing Systems, Station
Design Subcommittee of the Energy Development and Power Generation Committee. At the time this recommended
practice was approved, the members of the working group were:
At the time this recommended practice was approved, the members of the Enegry Development and Power Generation
Committee were:
iii
S. A. Nikolakakos D. E. Roberts K. L.West
M. I. Olken E. P. Rothong T. R. Whittemore
R. E. Penn D.B. Seely J. P. Whooley
C. R. Pope G. I. Stillman C. J. Wylie
R. Ramakumar J. E. Stoner, Jr T. D. Younkins
R. J. Reiman V. C. Sulzberger R. Zweigler
The following persons were on the balloting committee that approved this document for submission to the IEEE
Standard Board:
When the IEEE Standards Board approved this standard on October 20, 1988, it had the following membership:
*Member Emeritus
iv
CLAUSE PAGE
1. Scope and purpose ..............................................................................................................................................1
2. Reference ............................................................................................................................................................1
3. Definitions...........................................................................................................................................................2
10. Bibliography......................................................................................................................................................10
v
CLAUSE PAGE
Annex A (Informative) Electrical Insulation Resistance Test for Heating Cables .......................................................11
vi
IEEE Recommended Practice for Testing
and Startup Procedures for Electric Heat
Tracing Systems for Power Generating
Stations
1.1 Scope
IEEE Std 622B-1988 provides recommended practices for the testing and startup of electric heat tracing systems in
power generating stations. The recommendations include the testing sequence of materials and components of the
electric heat tracing system, installation, and pre-operational testing of the system, verification of system performance,
and the necessary records to be filed.
1.2 Purpose
The purpose of this recommended practice is to provide recommendations that may be used to ensure that an electric
heat tracing system is installed correctly and that it is properly tested and commissioned. The recommendations are
also intended to ensure that the electric heat tracing system will function correctly.
2. Reference
When the standard referred to in this document is superseded by a revision, the revision shall apply.
[1] IEEE Std ANSI/IEEE Std 100-1988. IEEE Standard Dictionary of Electrical and Electronics Terms.1
1ANSI/IEEE publications can be obtained from the Sales Department, American National Standards Institute, 1430 Broadway, New York, NY
10018, or from the Service Center, The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-
1331.
3. Definitions
The following definitions apply specifically to the subject matter in this recommended practice. In some cases, more
than one term or phrase is defined because in industry practice the terms or phrases are used interchangeably.
Additional terms or phrases used in this recommended practice may be found by referencing ANSI/IEEE Std 100-
1988 [1].2
alarm, alarm signal: A signal for attracting attention to some abnormal condition. Alarms associated with electric
heat tracing systems can signal high temperature, low temperature, loss of heater circuit voltage, etc.
calibration error: In operation, the departure under specified conditions, of actual performance from performance
indicated by scales, dials, or other markings on the device.
centralized control/alarm: A common (central) point where multiple control, alarm, or both signals or functions are
brought together. With respect to electric heat tracing systems, centralized control/alarm stations usually consist of
cabinets or panels where remote control, alarm, or both signals are brought together for a common output signal to the
generating unit control room.
components: Items from which a system is assembled; for example, resistors, capacitors, wires, connectors,
transistors, switches, etc.
controller: A device that regulates the state of a system by comparing a signal from a sensor located in the system with
a predetermined value and adjusting its output to achieve the predetermined value. Controllers, as used in electric heat
tracing systems, regulate temperatures on the system and can be referred to as temperature controllers or thermostats.
Controller sensors can be mechanical (bulb, bimetallic) or electric (thermocouple, RTD, thermistor).
critical freeze protection: The use of electric heat tracing systems to prevent the temperature of fluids from dropping
below the freezing point of the fluid in important or critical outdoor (usually) piping systems at nuclear generating
stations. An example of a critical freeze protection system is the heating for the nuclear service water system.
critical process control: The use of electric heat tracing systems to increase or maintain, or both, the temperature of
fluids (or processes) in important or critical mechanical piping systems including pipes, pumps, valves, tanks,
instrumentation, etc, in nuclear power generating stations. An example of an important or critical mechanical piping
system is the safety injection system.
dead band differential: The difference in degrees between the OFF and the ON stage of temperature controllers.
essential freeze protection: The use of electric heat tracing systems to prevent the temperature of fluids from
dropping below the freezing point of the fluid in desirably available or essential outdoor (usually) piping systems at
fossil fueled generating stations. An example of an essential freeze protection system is the heat tracing for the
feedwater system.
essential process control: The use of electric heat tracing systems to increase, maintain, or both, the temperature of
fluids (or processes) in desirably available or essential mechanical piping systems including pipes, pumps, valves,
tanks, instrumentation, etc, in fossil fueled generation stations. An example of an essential process control system is
the heating for the fuel oil system.
freeze protection: The use of electric heat tracing systems to prevent the temperature of fluids from dropping below
the freezing point of the fluid. Freeze protection is usually associated with piping, pumps, valves, tanks,
instrumentation, etc, such as water lines, that are located outdoors or in unheated buildings.
local control/alarm: The locations where control, alarm, or both signal or function take place. With respect to electric
heat tracing systems, these are usually mounted in close proximity to the individual heating circuits that they operate.
modules: Any assembly of interconnected components which constitutes an identifiable device, instrument, or piece
of equipment which can be disconnected, removed as a unit and replaced with a spare, and has definable performance
characteristics which permit it to be tested as a unit. A module can be a card or other subassembly.
2
The numbers in brackets correspond to the references listed in Section 2. of this standard.
monitoring: To check the operation and performance of an equipment or system by sampling the results of the
operation. Monitoring with respect to electric heat tracing systems usually consists of checking system temperatures or
operation of the heater circuits; voltage, current, etc.
process control: The use of electric heat tracing systems to increase or maintain, or both, the temperature of fluids (or
processes) in mechanical piping systems including pipes, pumps, valves, tanks, instrumentation, etc, in power
generating stations.
range: The capability span of an instrument, or the region between the lower and upper limits of a measured or
generated function. With respect to electric heat tracing systems, range is usually defined as the difference between the
lowest available set point and the highest available set point.
repeatability: The closeness of agreement among a number of consecutive measurements of the output for the same
value of the input under the same operating conditions approaching from the same direction. With respect to electric
heat tracing systems, repeatability is usually associated with temperature controllers and is the difference in degrees
for repeated operation at a specific temperature setting.
resettability: The restoring of a mechanism, electrical circuit, or device to the prescribed state. Resettability is usually
associated with temperature controllers and is the difference in degrees when returning to original temperature setting.
sensitivity: The ratio of the magnitude of a device response to the magnitude of the quantity measured. In electric heat
tracing the systems sensitivity is usually associated with temperature controls and alarms and addresses their response
function.
sensor, sensing element: The first system element that responds quantitatively to the measure and and performs the
initial measurement operation. Sensors, as used in electric heat tracing systems, respond to the temperature of the
system and may be directly connected to controllers, alarms, or both. Sensors can be mechanical (bulb, bimetallic) or
electrical (thermocouple, RTD, thermistor).
set point: A fixed or constant (for relatively long time periods) command. With respect to electric heat tracing
systems, set points are usually associated with temperature controllers or alarms and are the position of the dials, taps,
levels, scales, etc, so as to secure the desired operating characteristics.
The philosophy and reasons for using different testing procedures for different components and materials that make up
electric heat tracing systems are important for the comprehension of the rest of this recommeded practice.
While there can be a number of different tests at virtually all the steps that occur in the design, procurement,
installation and startup of an electric heat tracing system, this document recommends four major test categories,
namely:
As noted elsewhere in this recommeded practice, the exact testing procedures and timing for electric heat tracing
systems should be left up to engineering management of the project.
Incoming inspection should be done as materials are received at the job site. This should include a general inspection
to check for correct quantities and types of material as well as inspection for any damage during shipping and
handling. Material and component testing should be carried out as prescribed in 5.1, 6.1, 7.1, 8.1, and 9.1.
This testing should be done after the electric heat tracing materials and components are installed but before thermal
insulation is installed. The materials and components should be tested before power is turned on. Tests to be performed
are discussed in 5.2, 6.2, 7.2, 8.2, and 9.2.
NOTE — Electric heat tracing materials and components should not be installed on piping systems until after all hydrostatic
testing has been successfully completed.
This testing should be done after the thermal insulation has been installed and the electric heat tracing system has been
energized. This testing should include both component and system operational testing. It is at this time that the design
maintenance temperature should be verified. This testing should be done on a circuit by circuit basis as discussed in
5.3, 6.3, 7.3, 8.3, and 9.3.
This activity should be performed at regular intervals after the electric heat tracing system has been commissioned.
Operational checks, including review of the performance data to verify properly insulated heat sinks and no
overheating, are essential for reliable operation of the system. Also, a visual inspection should be made to check for
damaged insulation. This activity is discussed in 5.4, 6.4, 7.4, 8.4, and 9.4. A sample periodic testing and surveillance
form is provided in Appendix B.
Each of these testing categories for the following five component classes are discussed in the remaining portions of this
document. These classes are:
This section defines the recommended procedures that should be used for testing and commissioning series resistance
heating systems.
A procedure for logging in material and a process for testing the materials should be developed. All paperwork
associated with these processes should be properly filed as base line data.
Series resistance heater cables are usually designed, tagged and marked for specific pipe segments. Permanent metal
tags are usually attached to the cold lead of each cable. These tags should contain the cable catalog number, circuit
designation, and manufacturer's serial identification number. Other circuit information may be on the tags such as
length, voltage, current and power. The metal tags should not be removed from the heater cables. After each heater
cable or circuit has been physically inspected for any shipping and handling damage, each cable should receive a
continuity check and an appropriate insulation resistance tests3. Any cable that tests less than the manufacturer's
3
Commonly referred to as “Megger” (trade name of James G. Biddle Co).
minimum insulation resistance value should be rejected for use. In each continuity and insulation resistance test,
measurement values should be recorded as part of the base line data file.
After the series resistance heater cables have been installed on the piping systems, but before any thermal insulation
has been installed, the heater circuits should have a continuity check and an insulation resistance test. These tests can
be performed on individual heater cables or on multiple cables that make up individual circuits. If a lower than
manufacturer's recommended megohm reading exists on the cables or circuits, a check should be made of all
associated junction boxes and pigtail leads to ensure they are free of moisture, and the test should be repeated to isolate
the defect.
The heating cable should be checked for signs of mechanical damage. If damage is seen, either replace the entire cable
or replace the damaged section and install a connection splice as per manufacturer's recommendations. An inspection
should also be made of all connections, including those to the power source, to be sure they are correctly assembled
and installed. Inspect the temperature probe to ensure that the heating cable is not touching the prove or is in too close
of proximity to it. Preinsulation testing should be repeated.
As a final check after the thermal insulation has been installed but before energizing the electric heat tracing circuits,
a insulation resistance test should be performed on the cables. This ensures that no damage to the heating cables has
occurred during the insulation process. After the final insulation resistance tests, the electric heat tracing system
should be energized. At this time, each circuit should be checked and voltage and current recorded and checked against
the design data for the circuit. Values recorded should be within manufacturer's recommendation of the design values.
After the electric heat tracing circuits have been energized, a suitable amount of time should be allowed for the system
to heat up and stabilize. Empty piping should be up to minimum temperature within 24 h. Filled piping may take as
long as two to three days to stabilize depending on the fluid and if any specific heat up requirements were designed into
the system.
After the electric heat tracing system has stabilized, the formal temperature performance test should be performed.
This involves estimating or actually measuring temperatures on the system. There are several ways to approach this as
follows:
A rough method of estimating pipe temperaturecan be accomplished by using the line sensing temperature controller.
The set point knob can be slowly rotated back and forth while observing the on and off clicks. The temperature on the
pipe can be assumed to be in the range of these clicks (unless the sensor has been incorrectly installed too close to a
heating cable).
A more accurate method of test for pipe temperature is to insert a contact thermometer or pyrometer through the
insulation to a point where it touches the pipe. Care should be taken to ensure that pipe temperature and not heater
cable temperature is being measured. Also, care must be taken to ensure that the hole created by the probe is properly
sealed after the probe is removed to prevent moisture intrusion to the thermal insulation.
An accurate evaluation of system temperatures can be accomplished by installing permanent sensor test points along
the pipe at periodic spacings. These test points are installed at the same time as the heater cables are installed. The test
points are thus readily available for temperature measurements at any time and without the need to disturb the thermal
insulation.
After the electric heat tracing system has stabilized, a full test and recording of pipe temperatures should be performed.
This should verify the design based on the ambient temperature the system to which the system is exposed.
Temperature readings including ambient temperatures and pipe temperatures should be recorded in the base line data
files along with current and voltage measurements for each heating circuit.
If the electric heat tracing system fails to come up to temperature, and the circuit voltage and current reading agree
with the design data, likely sources of a problem may be wet thermal insulation, gaps in the insulation, or additional
heat sinks not included in the original design.
A periodic visual inspection of the piping system should be made to confirm the thermal insulation integrity and detect
possible heater damage. Testing should include measuring and recording of voltage, current, and temperature on a per
circuit basis. Freeze protection electric heat tracing systems should be surveyed and tested prior to the winter season.
Process control systems and critical process control systems should be checked more frequently.
This section defines the recommended procedures that should be used for testing and commissioning parallel
resistance heating systems which include constant wattage and variable wattage heating cables.
Receipt and inspection of parallel resistance heating cable should be performed per the recommendations of the
manufacturer. Logging of materials should be in accordance with 5.1.
After the heating cable and connectors have been installed on the pipe, but before the installation of the thermal
insulation, the following procedures should be followed:
The heating cable should be checked for signs of mechanical damage. If damage is seen, the entire cable should be
replaced or the damaged section should be cut out and a connection splice installed per manufacturer's
recommendations. Inspect the temperature probe to ensure that the heating cable is not touching the prove or is in too
close of proximity to it. An inspection should also be made of all connections, including those to the power source, to
be sure they are correctly assembled and installed.
A visual check should be made to inspect the piping, thermal insulation, weather barrier, and electrical connections.
This check is to ensure that no physical damage has occurred. Each circuit should be tested in accordance with
Appendix A.
After the circuit megohm tests, the system may be energized and tested as follows:
If the ambient temperature is higher than the desired temperature controller setting, the setting should be turned up
high enough to turn the system on. Care should be taken not to exceed system temperature limits. Then, each circuit
should be measured for voltage, current, ambient temperature and temperature controller set point. These
measurements should be recorded in the base line data file and compared to the design parameters. After the entire
system has been checked out, all temperature controller set points should be returned to the design temperature.
The temperature controller should be set to the design temperature or to a setting high enough to turn the circuits on if
the pipe temperature is higher than the control temperature. Each circuit should then be measured for voltage and
current. It is recommended that actual pipe temperature be measured using the contact probe method described in
5.3.2. Voltage and current readings along with ambient and pipe temperature measurements should be recorded as part
of the base line data file and compared against the design requirements.
Periodic inspections of each circuit's voltage and current should be made, along with ambient and pipe temperatures,
to confirm the performance of the heating systems. Data obtained should be placed on file. Freeze protection systems
should be surveyed and tested prior to the winter season. Process control systems should be checked more frequently.
This section covers receipt of materials testing, preinsulation testing, temperature performance testing, and periodic
testing and surveillance methods for mechanical temperature controllers. These include bulb and bellows or bimetallic
thermostats.
On receipt of the temperature controllers, the controllers should be checked against the applicable specification and
procurement documents, and also a verification should be made that applicable and complete instruction manuals have
been received. A detailed review of the instruction manuals should be made to determine any special handling or
storage requirements. Each mechanical temperature controller should be visually inspected and checked for any
physical damage, rust, or corrosion.
After the temperature controller has been installed along with its associated sensor, verification should be made that
the components have been located, mounted and connected in accordance to the latest approved drawings and
instruction manual. Sensor capillaries should be inspected to ensure they have not been coiled too tightly and that they
do not have any kinks in them. Inspect the temperature probe to ensure that the heating cable is not touching the probe
or is in too close of proximity to it. Inspection should be made of heater cable leads entering the controller to ensure
that they are properly connected. The heating controller and circuit can then be energized. The controller setting, if
adjustable, should then be set high enough to turn on the circuit. A current reading should then be taken to verify that
power has been applied to the heating cable. After this verification has been made, the controller setting should be
lowered until power to the heating cable is turned off.
The mechanical temperature controller should then be set to the design temperature of the circuit. If the ambient is
lower than the temperature setting, energize the circuit and apply heat to the sensor until the power is removed from the
heating cable. If the ambient is above the temperature setting, energize the circuit by cooling the sensor until power is
turned on to the circuit. This verifies that the thermostat responds to changing temperatures. Heating of the sensors
should be by hot air gun, cooling should be by water, by ice bath or by freon spray.
At this point in the testing sequence, the temperature controllers should be checked for any physical damage that might
have occurred during thermal insulation of the lines. The remaining testing of the controller is done in conjunction
with the circuit testing as outlined in 5.3 and 6.3.
Temperature controllers should be inspected for damage and proper operation as their respective heating circuits are
checked.
Like mechanical temperature controllers, electronic controllers should be handled and tested to ensure a reliable
installation.
The inspections and testing criteria for receipt of electronic controllers should be the same as outlined in 7.1. At no
time should electronic temperature controllers be tested with a megohm meter.
After the electronic temperature controllers have been installed along with their associated sensor, verification should
be made that the components have been located, mounted and connected in accordance with the latest approved
drawings and instruction manual. Inspect the temperature probe to ensure that the heating cable is not touching the
prove or is in too close of proximity to it. The heating controller sensors can then be checked as follows:
RTD sensors should be measured for continuity and resistance. Pipe temperature should be measured with a calibrated
thermometer. The measured resistance reading should then be compared to the appropriate resistance to temperature
conversion table to verify RTD performance.
Thermocouple output voltage should be measured with a millivoltmeter. Pipe temperature should be measured with a
calibrated thermometer. The measured voltage reading should be compared to the appropriate voltage to temperature
conversion table to verify thermocouple performance.
Thermistor sensors should be measured for continuity and resistance. Pipe temperature should be measured with a
calibrated thermometer. The measured thermistor resistance should be compared to the appropriate resistance to
temperatures conversion table to verify thermistor performance.
A final step to the preinsulation testing is to set the electronic temperature controller to energize the heating circuit.
This should be verified by a current measurement on the circuit. The temperature controller should then be returned to
the design setpoint.
At this point in the testing sequence, the temperature controllers should be checked for any physical damage that might
have occurred during installation of thermal insulation. The remaining testing of the controller is done in conjunction
with the circuit testing as outlined in 5.3 and 6.3.
Temperature controllers should be inspected for damage and proper operation as their respective heating circuits are
checked.
Since electric heat tracing system control, monitoring and alarm panels are the focal point for system activity, proper
handling and testing of the panels is important to ensure correct system operation.
Upon receipt of control, monitoring and alarm panels, they should immediately be checked for any damage that might
have occurred during shipping and handling. They should also be checked against any specifications and procurement
documents to ensure that they are complete. A visual inspection should then be made of the panels to ensure that all
components are securely mounted and clearly marked. The latest approved drawings should be used to check the panel
layouts and wire termination points to ensure they agree.
This test is not applicable for control and alarm panels, as their installation sequence may be different than for heater
cable and individual controller installations. Ensure temperature sensors to be used have been checked and have been
properly installed. Inspect the temperature probe to ensure that the heating cable is not touching the prove or is in too
close of proximity to it.
A visual check of the panel should be made for physical damage and proper electrical connections. The panel can then
be energized and each circuit can be energized. A check should be made on all controller set points to ensure that they
are at design temperature. The entire electric heat tracing system being controlled from the panel should then be
allowed to stabilize. After stabilization, each individual circuit should be measured for voltage, current, ambient
temperature, and pipe temperature, and this data should be compared with the design data and entered into the base
line data file. Note that pipe temperature may be measured using the methods described in 5.3.
Control, monitoring and alarm panels should be periodically checked for trash, or foreign material. This process
should also include a check of proper relay and indicating light operation along with a check of all electrical
connections. Freeze protection panels should be checked prior to the winter season. Process control systems and
critical process control systems should be checked more frequently.
10. Bibliography
[B1] ANSI/ASME NQA-2-1986. Quality Assurance Requirements for Nuclear Power Plants.
[B2] IEEE Std ANSI/IEEE Std 622-1987. IEEE Recommended Practice for the Design and Installation of Electric
Heat Tracing Systems for Nuclear Power Generating Stations.
[B3] IEEE Std ANSI/IEEE Std 622A-1984. IEEE Recommended Practice for the Design and Installation of Electric
Pipe Heating Control and Alarm Systems for Power Generating Sttions.
[B4] IEEE Std 515-1983. IEEE Recommended Practice for the Testing Design, Installation, and Maintenance of
Electrical Resistance Heat Tracing for Industrial Applications.
(Informative)
(These Appendixes are not a part of IEEE Std 622B-1988, IEEE Recommended Practice for Testing and Startup Procedures for
Electric Heat Tracing Systems for Power Generating Stations, but are included solely for the purposes of information.)
Step 1: Visually inspect the heater cable for signs of mechanical damage. If damage is seen, either replace the heater
cable, or repair the heater cable.
Step 2: Inspect the insulation resistance of the circuit using a megohm meter4. 500 VDC is recommended. Always
perform this test at the power connections using the following procedure:
NOTE — Insulation resistance testing may damage solid state components. Ensure that they are disconnected before this test if
performed.
4
Commonly referred to as “Megger” (trade name of James G. Biddle Co).
(Informative)
(Informative)
Parallel heater,
Replace or repair
Open element
High system temperature Controller w/fail close mode Replace sensor or controller
High fluid temperature controller of Reset high alarm for fluid condition