LOAD DISTRIBUTION SCHEDULE OF DB-G (GROUND FLOOR)

WATE
WATE GATE
EMERGENC SMOKE 13A 13A R
INCOM CIRCUIT MCB RATING CCT WIRE SIZE ECC WIRE SIZE LIGHT LIGHT EXHAUST CHAND. BELL SPLIT AC R MOTO
ER
RATING OF ELCB SR#
NO. (A) SQ.MM SQ.MM
AREA/LOCATION
35W 100W FAN 75W 300W
Y LIGHT DETECORS
50W 3000W
SSO DSO HEATE
PUMP R
R Y B REMARKS
20W 20W 200W 400W R
1500W 1000W
1500W

1 R1 10 2.5 2.5 DINING 11 2 985


2 Y1 10 2.5 2.5 MAJLIS 2 600
ELCB 4P-40A 100mA

3 B1 10 2.5 2.5 MAID ROOM+BATH+LAUNDRY 4 1 475


4 R2 10 2.5 2.5 GYM+BATH 8 1 355
5 Y2 10 2.5 2.5 MAJLIS+WASH+BATH 22 1 845
6 B2 10 2.5 2.5 OFFICE 6 600
SECTION-1

7 R3 10 2.5 2.5 HALL 7 1 545


8 Y3 10 2.5 2.5 KITCHEN+STORE 11 3 610
9 B3 10 2.5 2.5 PLAYING ROOM 6 600
ELCB 4P-40A 100mA

10 R4 10 2.5 2.5 ENTRANCE STEPS 4 140


11 Y4 10 2.5 2.5 HALL 9 315
12 B4 10 2.5 2.5 PASSAGE 14 1 565
13 R5 10 2.5 2.5 BOUNDARY WALL 8 280 ARMORED
SECTION-2
4P 63A ISOLATOR

14 Y5 10 2.5 2.5 DOOR BELL 1 50


15 B5 10 2.5 2.5 BOUNDARY WALL 16 560 ARMORED
16 Y6 10 2.5 2.5 STAIRCASE 32 1120
17 R7 20 4 4 DINING 3 600 RADIAL CKT
ELCB 4P-40A

18 Y7 32 4 4 MAJLIS 7 1400 RING CKT


19 B7 20 4 4 MAIDROOM+LAUNDRY+PASS 5 1000 RING CKT
30mA
SECTION-3

20 R8 20 4 4 GYM 4 800 RADIAL CKT


21 Y8 32 4 4 KITCHEN 7 1400 RING CKT
22 B8 20 4 4 OFFICE 3 600 RADIAL CKT
23 R9 20 4 4 HALL 2 800 ONT
ELCB 4P-40A

24 Y9 20 4 4 STORE 3 600 RADIAL CKT


25 B9 20 4 4 PLAYING ROOM 4 800 RADIAL CKT
30mA
SECTION-4

26 R10 20 4 4 BOUNDARY WALL 3 600 RADIAL CKT


27 Y10 32 4 4 KITCHEN+HALL 5 1000 RING CKT
28 B10 20 4 4 BOUNDARY WALL 3 600 ARM+W/P
29 R11 20 4 4 TRANSFER PUMP 1 1500 ARM+W/P
ELCB 4P-40A
SECTION-5

27 Y11 20 4 4 HALL 3 600 RADIAL CKT


30mA

27 B11 20 4 4 GATE MOTOR 1 1500 ARM+W/P


30 Y12 20 4 4 STAIRCASE 2 400 ARM+W/P
TOTAL POINTS 142 16 7 5 0 0 1 0 52 2 0 1 1

CABLE SPECIFICATION CONDUIT SIZE Imax (A) 46.56 A TOTAL POWER W= 6605 8940 7300 22845
LOAD DISTRIBUTION SCHEDULE OF DB-GAC (GROUND FLOOR AC)
WATE
WATE GATE
EMERGENC SMOKE SOUN 13A 13A R
INCOM CIRCUIT MCB RATING CCT WIRE SIZE ECC WIRE SIZE LIGHT LIGHT EXHAUST CHAND. R MOTO
ER
RATING OF ELCB SR#
NO. (A) SQ.MM SQ.MM
AREA/LOCATION
35W 100W FAN 75W 300W
Y LIGHT DETECORS DER DUCT AC SSO DSO HEATE
PUMP R
R Y B REMARKS
20W 20W 50W 200W 400W R
1500W 1500W
1500W
SECTION- SECTION- SECTION- SECTION- SECTION-

1 R1 1550
ELCB 4P- ELCB 4P- ELCB 4P- ELCB 4P- ELCB 4P-

100mA
40A

2 Y1 32A TP 4Cx6 1Cx6 MAJLIS 1 1550 UVR+T+CONT.


3 B1 1550
1

4 R2 1667
100mA
40A

5 Y2 32A TP 4Cx6 1Cx6 DINING + GYM 1 1667 UVR+T+CONT.


4P 40A ISOLATOR

6 B2 1666
2

7 R3 1250
100mA
40A

8 Y3 32A TP 4Cx6 1Cx6 KITCHEN 1 1250 UVR+T+CONT.


9 B3 1250
3

10 R4 1000
100mA
40A

11 Y4 32A TP 4Cx6 1Cx6 MAIDROOM + LAUNDRY 1 1000 UVR+T+CONT.


12 B4 1000
4

13 R5 1134
100mA
40A

14 Y5 32A TP 4Cx6 1Cx6 OFFICE + PLAYING ROOM 1 1133 UVR+T+CONT.


15 B5 1133
5

TOTAL POINTS 0 0 0 0 0 0 0 5 0 0 0 0 0

CABLE SPECIFICATION CONDUIT SIZE Imax (A) 34.38 A TOTAL POWER W= 6601 6600 6599 19800
LOAD DISTRIBUTION SCHEDULE OF DB-F (FIRST FLOOR)
WATE
WATE GATE
EMERGENC SMOKE SOUN 13A 13A R
INCOM CIRCUIT MCB RATING CCT WIRE SIZE ECC WIRE SIZE LIGHT LIGHT EXHAUST CHAND. SPLIT AC R MOTO
ER
RATING OF ELCB SR#
NO. (A) SQ.MM SQ.MM
AREA/LOCATION
35W 100W FAN 75W 300W
Y LIGHT DETECORS DER
3000W
SSO DSO HEATE
PUMP R
R Y B REMARKS
20W 20W 50W 200W 400W R
1500W 1500W
1500W
ELCB 4P-40A 100mA

1 R1 10 2.5 2.5 BEDROOM 3+DRESS+BATH 16 1 1 935


2 Y1 10 2.5 2.5 BEDROOM 1+DRESS+BATH 16 1 1 935
3 B1 10 2.5 2.5 M.BEDROOM+DRESS+BATH 23 1 1 1180
4 R2 10 2.5 2.5 BEDROOM 2+DRESS+BATH 15 1 1 900
5 Y2 10 2.5 2.5 HALL 7 245
SECTION-1

6 B2 10 2.5 2.5 BEDROOM 4+DRESS+BATH 22 1 1 1145


7 R3 10 2.5 2.5 PASSAGE 4 140
4P 40A ISOLATOR

8 Y3 10 2.5 2.5 HALL 8 1 1300


9 B3 10 2.5 2.5 PASSAGE 3 105
10 R4 32 4 4 BEDROOM 3+DRESS 5 1000 RING CKT
ELCB 4P-40A

11 Y4 32 4 4 BEDROOM 1+DRESS 5 1000 RING CKT


SECTION-2

30mA

12 B4 32 4 4 M.BEDROOM+DRESS 5 1000 RING CKT


13 R5 32 4 4 BEDROOM 2+DRESS 5 1000 RING CKT
14 Y5 20 4 4 HALL 4 800 RADIAL CKT
15 B5 32 4 4 BEDROOM 4+DRESS 6 1200 RING CKT
16 R6 20 4 4 BEDROOM 3 BATH 1 200 SHAVER SOCKET
ELCB 4P-
40A 10mA
SECTION-2

17 Y6 20 4 4 BEDROOM 1 BATH 1 200 SHAVER SOCKET


18 B6 20 4 4 M.BEDROOM BATH 1 200 SHAVER SOCKET
19 R7 20 4 4 BEDROOM 2 BATH 1 200 SHAVER SOCKET
20 B7 20 4 4 BEDROOM 4 BATH 1 200 SHAVER SOCKET
TOTAL POINTS 106 8 5 6 0 0 0 0 35 0 0 0 0

CABLE SPECIFICATION CONDUIT SIZE Imax (A) 26.20 A TOTAL POWER W= 4375 4480 5030 13885
LOAD DISTRIBUTION SCHEDULE OF DB-FAC (FIRST FLOOR AC)
WATE
WATE GATE
EMERGENC SMOKE SOUN 13A 13A R
INCOM CIRCUIT MCB RATING CCT WIRE SIZE ECC WIRE SIZE LIGHT LIGHT EXHAUST CHAND. R MOTO
ER
RATING OF ELCB SR#
NO. (A) SQ.MM SQ.MM
AREA/LOCATION
35W 100W FAN 75W 300W
Y LIGHT DETECORS DER DUCT AC SSO DSO HEATE
PUMP R
R Y B REMARKS
20W 20W 50W 200W 400W R
1500W 1500W
1500W
SECTION- SECTION- SECTION- SECTION- SECTION- SECTION-

1 R1 1250
ELCB 4P- ELCB 4P- ELCB 4P- ELCB 4P- ELCB 4P- ELCB 4P-

100mA
40A

2 Y1 32A TP 4Cx6 1Cx6 M.BEDROOM 1 1250 UVR+T+CONT.


3 B1 1250
1

4 R2 1000
100mA
40A

5 Y2 32A TP 4Cx6 1Cx6 BEDROOM 1 1 1000 UVR+T+CONT.


6 B2 1000
2
4P 40A ISOLATOR

7 R3 1000
100mA
40A

8 Y3 32A TP 4Cx6 1Cx6 BEDROOM 2 1 1000 UVR+T+CONT.


9 B3 1000
3

10 R4 1000
100mA
40A

11 Y4 32A TP 4Cx6 1Cx6 BEDROOM 3 1 1000 UVR+T+CONT.


12 B4 1000
4

13 R5 1290
100mA
40A

14 Y5 32A TP 4Cx6 1Cx6 BEDROOM 4 1 1290 UVR+T+CONT.


15 B5 1290
5

16 R6 2083
100mA
40A

17 Y6 32A TP 4Cx6 1Cx6 HALL 1 2084 UVR+T+CONT.


18 B6 2083
6

TOTAL POINTS 0 0 0 0 0 0 0 6 0 0 0 0 0

CABLE SPECIFICATION CONDUIT SIZE Imax (A) 39.71 A TOTAL POWER W= 7623 7624 7623 22870
LOAD DISTRIBUTION SCHEDULE OF DB-S (SECOND FLOOR)

WATE GATE
EMERGENC SMOKE SOUN 13A 13A CENTR
INCOM CIRCUIT MCB RATING CCT WIRE SIZE ECC WIRE SIZE LIGHT LIGHT EXHAUST CHAND. R MOTO
ER
RATING OF ELCB SR#
NO. (A) SQ.MM SQ.MM
AREA/LOCATION
35W 100W FAN 75W 300W
Y LIGHT DETECORS DER DUCT AC SSO DSO AL WH
PUMP R
R Y B REMARKS
20W 20W 50W 200W 400W 3000W
1500W 1500W

1 R1 10 2.5 2.5 CINEMA ROOM 2 600


ELCB
4P-40A 100mA

2 Y1 10 2.5 2.5 STORE 2 70


SECTION-1

3 B1 10 2.5 2.5 HALL+PANTRY 8 1 355


4 R2 10 2.5 2.5 CINEMA ROOM 15 525
5 Y2 10 2.5 2.5 OUTSIDE 6 210 ARMORED
SECTION-

6 R3 1667
ELCB 4P-

100mA
4P 40A ISOLATOR

40A

7 Y3 32A TP 4Cx6 1Cx6 CINEMA ROOM + PANTRY 1 1666 UVR+T+CONT.


8 B3 1667
2

9 R4 32 4 4 CINEMA ROOM 5 1000 RING CKT


ELCB
4P-40A 30mA

10 Y4 20 4 4 STORE 3 600 RADIAL CKT


SECTION-3

11 B4 20 4 4 PANTRY 3 600 RADIAL CKT


12 R5 20 4 4 OUTSIDE 3 600 ARM+W/P
13 Y5 20 4 4 OUTSIDE 3 600 ARM+W/P
SECTIO SECTIO

14 R6 20 4 4 CIRCULATION PUMP 1 1500 ARM+W/P


2P-40A 4P-40A
ELCB

30mA
N-4

15 Y6 20 4 4 ROOF BOOSTER PUMP 1 1500 ARM+W/P


ELCB

30mA

16 B7 32 6 6 CENTRAL WATER HEATER 1 3000 ARM+W/P


N-5

TOTAL POINTS 31 0 1 2 0 0 0 1 17 0 1 2 0

CABLE SPECIFICATION CONDUIT SIZE Imax (A) 30.69 A TOTAL POWER W= 5892 4646 5622 16160
MDB
RED PHASE YELLOW PHASE BLUE PHASE TOTAL
LOAD IN kW LOAD IN kW LOAD IN kW LOAD IN kW
DB-G 6.605 8.940 7.300 22.845
DB-GAC 6.601 6.600 6.599 19.800
DB-F 4.375 4.480 5.030 13.885
DB-FAC 7.623 7.624 7.623 22.870
DB-S 5.892 4.646 5.622 16.160
LIFT ISO 2.000 2.000 2.000 6.000
CAR CHARGER 6.000 6.000 6.000 18.000
TOTAL LOAD IN KW 39.096 40.290 40.174 119.560
DIVERSITY FACTOR 0.8
MAX.DEMAND LOAD IN KW 95.648
Imax MCCB RATING
IN AMPS IN AMPS
46.562 4P 63A 56.5625
34.380 4P 40A 44.380208333333
26.198 4P 40A 36.197916666667
39.708 4P 40A 49.708333333333
30.688 4P 40A 40.6875
10.417 4P 40A 20.416666666667
31.250 4P 40A 41.25
209.844 4P 225A 219.84375
0.8
95.648 MDB BAL