EW
N
A-XT
Extinguishant
Control Panel
Shield A-XT is a new
generation extinguishant
releasing panel which is
UL,FM listed
The simple, programmable
configuration options and
easy to install construction
make Shield A-XT panels the
ideal choice for small to
medium sized systems
using all extinguishant Features Product Overview
agents.
UL864 and FM listed Designed and manufactured to t he highest
standards in a quality controlled environment and
Programmable Three initiation circuits as standard with UL & FM approvals, the Shield A-XT
Functions releasing panel offers outstanding value
and performance for all small to medium fixed
Any single zone or any firefighting installations
combinations of zones can
Access Level 2
be configured to release
Test Zones 1 to 3 With t hree detection zones as standard,
Disable Zones 1 to 3 extinguishant release can be configured to
Configurable first stage
Disable 1st Stage Alarms activate from any combination of detection zone
NAC delays
Disable Pre-activated 1st Stage Relay inputs to a llow ( among other combinations) any
Disable Pre-activated 2nd Stage Relay
Configurable detection delays two from three type activations such as would be
Disable Extract Fan Output
required for detection in ceiling void, room and
Disable Manual Release Input
Zero time delay upon floor void applications.
Disable Extinguishant Sub System
manual release option
Activate Extract Fan Output
Activate Alarm Delays The extensive configuration options o f the Shield
Compatible with I.S. barriers A-XT allow the functionality of t he system to be
Access Level 3 extensively modified
Non-latching zone input
Sounder Delay option to receive signals The panel contains a large LED display to enable
Coincidence Detection from other systems such easy configuration and control which also displays
Disable Panel Features as aspirating equipment
Zone Alarm Delays (Detectors) the time remaining until extinguishant release for
Zone Alarm Delay (Call Points) added user safety.
Configurable extinguishant
Configure Zone for I.S Barrier Use delays up to 60 seconds The countdown timer is duplicated on up to seven
Zone Short Circuit Alarm in 5 second steps remote status units to p rovide local i ndication of
Zone Non Latching
the system status.
Zone Inputs Delay Configurable extinguishant
Extinguishant Release Time Delay duration up to 5 minutes With a ll o f the electronics m ounted on a single,
Extinguishant Release Duration Timer in 5 second steps easily removable, steel plate Shield A-XTpanels are
Extinguishant Reset Delay Timer
both robust and easy to install.
Countdown timer shows
time remaining until release Shield A-XT is supplied in an enclosure that matches
the design and colour of the elite RS range and is
Supports up to seven, available in standard red or optional grey.
four wire status indicators
Built in Extract Fan control
The manufacturer reserves the right to amend specifications without prior notice
Releasing Solenoid / Impulse
Extinguishant Released
Remote Auto / Maual
Remote Abort Switch
Extinguishant Low
Pressure Switch
Pressure Switch
Release Switch
Remote Maual
Select Switch
Extract Fan Power
Specifications
Valve
Peripheral
Detectors
Detectors
Releasing
Stop Air Conditioning
Shutdown Power
Technical
Construction - 1.2mm mild sheet steel
IP Rating - IP30
Finish - Epoxy powder coated
Colour - lid & box - Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Mains supply - 230V AC or 115V AC
Mains supply fuse - 1.6 Amp (F1.6A L250V)
Power supply rating - 3 Amps total including battery charge 28V +/- 2V
Maximum ripple current - 200 millivolts
Battery type (Yuasa NP) - Two 12 Volt 7Ah sealed lead acid in series
Battery charge voltage - 27.6VDC nominal (temperature compensated)
Battery charge current - 0.7A maximum
Battery fuse - 20mm, 3.15A glass
Maximum current draw from batteries - 3 Amps
Quiescent current of panel in mains fail - 0.095A
R0V output - Fused at 500mA with electronic fuse
Sounder outputs - 24V Fused at 500mA with electronic fuse
Fault relay contact rating - 30VDC 1A Amp maximum
Fire relay contact rating - 30VDC 1A Amp maximum
- 30VDC 1A Amp maximum
First stage contact rating - 30VDC 1A Amp maximum
Second stage contact rating - 30VDC 1A Amp maximum
Extract contact rating - 30VDC 1A Amp maximum
Zone quiescent current - 2mA maximum
Terminal capacity - 12 AWG
Number of detectors per zone - Dependent on type (maximum 32)
NAC rating - 0.5A per circuit
Detection circuit end of line - 6K%5 8 ½ Watt resistor
Monitored input end of line - 6K%5 8 ½ Watt resistor
Sounder circuit end of line - 10K %5 ¼ Watt resistor
Extinguishant output EOL - 1N4004 Diode
No. of initiating circuits - 3
No. of NAC circuits - 2 x 1st Stage, 1 x 2nd Stage
Extinguishant release output - Fused at 1 Amp
Extinguishant release delay - Adjustable 0 to 60 seconds (in 5 second steps)
Extinguishant release duration - Adjustable 60 to 300 seconds (in 5 second steps)
SIL, AL, FLT, RST inputs - Switched -ve, max resistance 100 Ohms
Zone normal threshold - 8K ohms to 1K ohm
Detector alarm threshold - 999 ohms to 400 ohms
Call point alarm threshold - 399 ohms to 100 ohms
Short circuit threshold - 99 ohms to 0 ohms
Monitored inputs normal threshold - 8K ohms to 1K ohm
Monitored inputs alarm threshold - 999 ohms to 100 ohms
Monitored inputs Short circuit threshold - 99 ohms to 0 ohms
Status unit/Ancillary board connection - Two wire RS485 connection
Status unit power output - Fused at 500mA with electronic fuse
Panels
Product Code Description Size (mm)
SHIELD FIRE, SAFETY
S115R-EXT Surface mounting panel - Red 115V 368 x 310 x 90
AND SECURITY LTD S230R-EXT Surface mounting panel - Red 230V 368 x 310 x 90