C01 - CABLE SPECIFICATIONS - Rev2
C01 - CABLE SPECIFICATIONS - Rev2
A A
POWER WIRING (24VAC) ETHERNET CROSS-OVER CABLE
1 5
14AWG - BELDEN 9495
16AWG - BELDEN 9494 ETHERNET STRAIGHT CABLE
18AWG - BELDEN 9493 6
4 PAIR ScTP, CAT5E, 24AWG SOLID BARE COPPER,
MAXIMUM ALLOWABLE WIRE LENGTH FOR EACH GAUGE: WITH FOIL SHIELD BONDED TO JACKET AND
For 14AWG: Lmax = 1200 / VA (in feet) 24AWG DRAIN WIRE.
For 16AWG: Lmax = 750 / VA (in feet) TDS8PC5 PLUGS.
For 18AWG: Lmax = 462 / VA (in feet)
BELDEN BEL-1533R-XX (PVC) 200MHz
BELDEN BEL-1533P-YY (PLENUM) 350MHz
RS485 I/O NETWORK
B 2 9600 BAUD MAXIMUM CABLE LENGTH : 328 FT OR 100 METERS B
1 2 3 4 5
TITLE : NOTES / REMARKS : SHEET NO :