CABLES / WIRING SPECIFICATIONS

A A
POWER WIRING (24VAC) ETHERNET CROSS-OVER CABLE
1 5
14AWG - BELDEN 9495
16AWG - BELDEN 9494 ETHERNET STRAIGHT CABLE
18AWG - BELDEN 9493 6
4 PAIR ScTP, CAT5E, 24AWG SOLID BARE COPPER,
MAXIMUM ALLOWABLE WIRE LENGTH FOR EACH GAUGE: WITH FOIL SHIELD BONDED TO JACKET AND
For 14AWG: Lmax = 1200 / VA (in feet) 24AWG DRAIN WIRE.
For 16AWG: Lmax = 750 / VA (in feet) TDS8PC5 PLUGS.
For 18AWG: Lmax = 462 / VA (in feet)
BELDEN BEL-1533R-XX (PVC) 200MHz
BELDEN BEL-1533P-YY (PLENUM) 350MHz
RS485 I/O NETWORK
B 2 9600 BAUD MAXIMUM CABLE LENGTH : 328 FT OR 100 METERS B

BELDEN 8761 (22AWG, 600V) CPC P/N: 135-0600


BELDEN 8771
MAXIMUM DAISY CHAIN CABLE DISTANCE: 7
4000 FT OR 1219 METERS (FOR 22 AWG) SHIELDED 3-CONDUCTOR CABLE, 22 GA WIRE.

FOR PRESSURE TRANSDUCERS AND HUMIDITY SENSORS.


RS485 CABLE FOR CPC AND DIXELL TEMP. SENSORS
2a *IF LONGER THAN THE PROBE LENGTH SUPPLIED.
RS485 CABLE / BELDEN 8761 EQUIVALENT:
BELDEN 8761 (22AWG, 600V) CPC P/N: 135-0600 BELDEN 8729
8
SHIELDED TWISTED PAIR SHIELDED 4-CONDUCTOR CABLE, 22 GA WIRE.
C 18 - 22 AWG C
RS485 MODBUS NETWORK - (SAME POLARITY)
3 19200 BAUD - FOR ECT MODBUS FOR LIGHT LEVEL SENSORS, AND DEWPOINT SENSORS
CAPACITANCE BETWEEN SIGNAL WIRES :
19200 BAUD - FOR DIXELL MODBUS 31pF/ft OR LESS
(9.45 m) OR LESS
BELDEN 8761 (22AWG, 600V) CPC P/N: 135-0600 BELDEN 9418
CAPACITANCE BETWEEN SIGNAL AND SHIELD :
9
MAXIMUM DAISY CHAIN CABLE DISTANCE: 4-CONDUCTOR CABLE, 18AWG WIRE.
59pF/ft OR LESS
4000 FT OR 1219 METERS (FOR 22 AWG) (17.98 m) OR LESS
FOR ESR VALVES (MAXIMUM OF 150 FT).
MAXIMUM OF 25 DEVICES PER LEG / SEGMENT.
NOMINAL IMPEDANCE: 120 OHMS +/- 50 OHMS
RS485 BACNET NETWORK
3a RS485 MODBUS NETWORK - (REVERSE POLARITY) 10
9600 BAUD - FOR DIXELL MODBUS BACnet MSTP RS485 CABLE SHIIELDED TWISTED PAIR 18-22 AWG
D CPC P/N: 135-0600 D
BELDEN 8761 (22AWG, 600V) CPC P/N: 135-0600
CAPACITANCE BETWEEN SIGNAL WIRES: 30pF/ft (100pF/m) OR LESS
MAXIMUM DAISY CHAIN CABLE DISTANCE:
4000 FT OR 1219 METERS (FOR 22 AWG) CAPACITANCE BETWEEN SIGNAL AND SHIELD: 60pF/ft (200pF/m) OR LESS
MAXIMUM OF 32 DEVICES PER LEG / SEGMENT.
NOMINAL IMPEDENCE: 100 to 300 ohms

RS485 CANBUS NETWORK MAXIMUM DAISY CHAIN CABLE DISTANCE:


4 3000ft at 19200 Baud WITH MAXIMUM OF 35 DEVICES.
BELDEN 8761 (22AWG, 600V) CPC P/N: 135-0600 TERMINIATE AT E2e 3 JUMPERS WITH MOD TERM AND OTHER END WITH 120 ohms.
KEEP SHIELD CONTINUOUS AND DAISY CHAIN,
MAXIMUM DAISY CHAIN CABLE DISTANCE: DO NOT CONNECT TO DEVICE, EARTH GROUND AT ONE END ONLY.
E 4000 FT OR 1219 METERS (FOR 22 AWG) E
EACH DEVICE MUST HAVE AN INTERNAL EARTH GROUND REFERENCE OR
CONNECTED TO EARTH GRPUND USING 100 ohm CURRENT LIMITING RESISTOR.

1 2 3 4 5
TITLE : NOTES / REMARKS : SHEET NO :

COPELAND ELECTRONICS & CONTROLS


CABLE SPECIFICATIONS
PROJECT :
C
COPELAND TYPICAL INSTALLATION DETAILS
NOTED/ REVIEWED BY : CADD BY : FILE NAME: REVISION and DATE:
01
WWW.COPELAND.COM
For Technical Support: [email protected]
JV C01 - CABLE SPECIFICATIONS_rev2 Rev2-050624
MF

You might also like