3.

Connect power supply and external devices to the terminal blocks on the When the concentration of the detected gas reaches the LOW alarm level,
Description
PCB according to the connection diagram below. the control LED starts blinking and the buzzer starts beeping with 1 Hz
Hydrogen detector-transmitter E2611-H2 is intended for early detection of frequency. When the HI alarm level is reached, the frequency of
leakages or accumulation of hydrogen in confined spaces. Input 1 4-20 mA / 0-10 V blinking/beeping is 2 Hz. The alarm signal turns off automatically, if gas
Controller OUT1
The instrument is based on fully calibrated and temperature compensated Input 2 4-20 mA / 0-10 V J3
OUT2 concentration decreases to 80% of the alarm setpoint.
0V / GND Control LED
semiconductor metal-oxide (MOS) gas sensor with high repeatability, 0V
Fieldbus A Configuring
stability and long lifetime. The sensor exhibits high sensitivity and selectivity B
RS485
- Gas detector E2611 shares all functionalities of the PluraSens®
to methane. Pellistor (catalytic bead) sensor is available as an option. PSU 24 VDC +U = 11...30 VDC
E2611 provides two independent analog outputs OUT1 and OUT2, user- + L
multifunctional transmitter platform. The features and options include:
90...265 VAC
selectable to 4-20 mA or 0-10 V, proportional either to gas concentration or N - digital output change rate limiting filter
230 VAC - digital integrating (averaging) filter
temperature. RS485 Modbus RTU digital communication interface allows RE1
easy instrument configuration and integration into various automation J1 J2 - temperature measurement channel with internal sensor
RE2
systems. Two relays RE1 and RE2 with closing contacts can be used to S - free assignment of each analog output to chosen parameter
switch 24 V or 230 V powered alarm sirens, ventilation fans, shut-off valves - flexible setting of analog output scales for each output
or other actuators. - output shift and slope adjustment for calibration
To power the instrument from an external 24 VDC source, connect terminals
- free assignment of each of two relays to chosen parameter
Safety requirements 0 V and +U to the source. If an integrated mains power supply module is
- several relay control logic modes (HI or LO with hysteresis, U or П)
used, connect terminals L and N to the mains.
Always adhere to the safety provisions applicable in the country of use. Do - switch delays and minimum on/off state durations for each relay
To use analog outputs, connect the terminals OUT1 and/or OUT2 and 0 V
not perform any maintenance operation with the power on. Do not let water - Modbus controlled forced state option for analog outputs and relays.
to the input of the secondary instrument (indicator or controller).
or foreign objects inside the device. E2611 can be configured through its RS485 interface by Modbus RTU
NB! The outputs are not galvanically isolated from 24 V power supply and
commands. A standard configuration kit includes Model E1087 USB-RS485
share common 0 V. Allowed load resistance limits are stated in
Operating conditions converter and E26XX Configurator software. Please contact your Seller or
Specifications table.
• The device should be used in explosion-safe (non ATEX -rated) indoor the Manufacturer for more information.
The type of each analog output can be independently selected with the
areas at the atmospheric pressure ±10%, <95 %RH, without condensation, appropriate jumper (J1 for OUT1 and J2 for OUT2). With jumper open, the Return to default settings
and temperature within the range -30...+70 °C for MOS-type devices / output type is 4-20 mA. With jumper closed, the output type is 0-10 V. To reset the device’s Slave ID, baudrate and sbit number to factory settings,
-20...+60 °C for pellistor type. proceed as follows:
To use relay outputs, connect the chosen actuators to the relay terminals
• Metal-oxide and pellistor sensors cannot properly operate in a zero or low
RE1 and/or RE2. 1. De-energize the device 2. Connect the J3 jumper
oxygen content atmosphere. Normal ambient oxygen concentration is
NB! Actuator short-circuits shall be avoided, to protect the instrument relays 3. Turn on the device 4. De-energize the device
recommended.
use external fuses or safety switches. 5. Disconnect the J3 jumper 6. Turn on the device
• Avoid exposure to highly corrosive gases (H2S, SO2, HCl, Cl2 etc), and
volatile silicon containing materials. Calibration
• Avoid mechanical shock or strong vibrations. 4. Turn on the power. It may take up to five minutes after switching on for
the sensor to stabilize. During this period relays, analog outputs and E2611-H2 has been calibrated by Manufacturer with standard gas mixtures
• Avoid sources of electromagnetic interference before delivery. The semiconductor gas sensor exhibits high stability and >
Modbus interface are off. A LED placed on the PCB of the device allows to
Installation and connections control the connection process. The LED response to different processes is 5 years lifetime. However, as the gas sensor is directly exposed to
presented in the table below. environment, the instrument requires at least annual field recalibration with
The gas detector should be mounted on a wall at a place located not more
a portable calibration kit. The catalytic sensor is more sensitive to the
than 5 m from possible gas leakage source and not very close to ventilation Process LED mode environment and requires calibration every 3...6 months.
openings, with the sensor pointing downwards. As hydrogen is much lighter Sensor heating period Blinking 0.5 Hz (50% on, 50% off) The calibration should be performed by qualified specialist. Please contact
than air, it is advisable to place the device near the ceiling. The device Sensor absence or malfunction Blinking 0.5Hz (90% off, 10% on) your dealer for more information.
should be available for maintenance and repair. Relay 1 turned on Blinking 1 Hz (50% on, 50% off)
1. Detach the base of the enclosure by gently pulling along four guiding Warranty
Relay 2 turned on Blinking 2 Hz (50% on, 50% off)
pins. Modbus response The signal is modulated with short onoff This product is warranted to be free from defects in material and
2. Fix the base on the wall with two screws. (see drawing below). pulses, even single Modbus cycle is traceable* workmanship for a period of one year from the date of original sale. During
Normal measurement Continuous light this warranty period Manufacturer will, at its option, either repair or replace
product that proves to be defective. This warranty is void if the product has
5. Push enclosure to the base. been operated in conditions outside ranges specified by Manufacturer or
Operation damaged by customer error or negligence or if there has been an
63
For best stability the gas detector should be powered permanently. If the unauthorized modification.
85

instrument is left for a long time in unpowered state, then after initial power- Delivery set
on the metal-oxide gas sensor needs some time to heat up and burn – Methane detector-transmitter E2611-H2
adsorbed contaminants. So for first tens of seconds of few minutes an – Mounting accessories: 2 screws and 2 plastic dowel plugs
alarm activation may be possible. After this heating-up period the
37 85 instrument turns into normal mode.
RS485 communication interface E2611-H2_UM_EN Rev 05.03.2018
Databits: 8 Supported Modbus functions:
Parity: none 03 - read multiple registers Specifications PluraSens®
Stop bits: 1 or 2 06 - write single register Sampling method Diffusion
Metal oxide
Modbus registers (0-based, decimal format) Sensor type Pellistor (catalytic)
semiconductor
Reg Description Supported values Detection range Up to 100% LEL
1 Hardware version read only Resolution 0,1% LEL 0,1% LEL
2 Software version read only Response time ~ 60 seconds ~ 10 seconds
3 Product serial number read only Sensor lifetime > 5 years > 2 years
4 Slave ID (network address)* 1...247, default 1
Calibration interval 12 months 3...6 months
5 Baudrate* 1200...57600 baud, default 9600
-30...+70 °C -20...+60°C
6 Response delay, ms 1...255 ms, default 10
<95 %RH, without condensation, non-ATEX
7 Stop bits* 1 / 2, default 1 Operating Normal ambient oxygen level/
17 Restart write ‘42330’ for soft restart conditions Avoid strong mechanical shock, vibrations or EMI
162 Temperature shift adjustment -32000...+32000 T units (0,01 °C) Avoid exposure to corrosive gases or silicon containing
165 Gas channel shift adjustment -32000...+32000 gas units, default 0 products
166 Gas channel slope adjustment 1...65535, default 512 up to 1 minute, depending on unpowered period and
Warm-up time
167 Output change rate limit 1...32000 gas units/s, 0=no limit atmosphere
168 Integrating filter time constant 1...32000 s, 0=no, integrating filter 11...30 VDC/VAC
Power supply
201 Parameter assigned to OUT1 0=none, 1=T, 2=gas, 9=forced by 203 with integrated mains supply module 90...265 VAC
202 Parameter assigned to OUT2 0=none, 1=T, 2=gas, 9=forced by 204 Power consumption < 2 VA
203 Forced value for OUT1 0...1000 (0.0...100.0% of full scale) Analog outputs 2 × 4-20 mA or 0-10 V
204 Forced value for OUT2 0...1000 (0.0...100.0% of full scale) for 4-20 mA output mode: RL < (Us - 2V) / 22 mA
Load resistance
211 Parameter assigned to RE1 0=none, 1=T, 2=gas, 9=forced by 213 for 0-10 V output mode: RL > 250 kOhm
212 Parameter assigned to RE2 0=none, 1=T, 2=gas, 9=forced by 214 Digital interface RS485, Modbus RTU protocol
213 Forced state for RE1 0=off, 1=on (relay control by Modbus) Relay outputs 2 × SPST, max 5 A, 30 VDC / 250 VAC
214 Forced state for RE2 0=off, 1=on (relay control by Modbus) Alarm Buzzer 85 dBi
215 Switch delay for RE1 0...1000 s, default 0 ABS plastic with ventilation slots, wall-mount,
216 Switch delay for RE2 0...1000 s, default 0 Enclosure
protection class IP20
217 Min on/off time for RE1 0...1000 s, default 0 Dimensions 85 × 85 × 37 mm
218 Min on/off time for RE2 0...1000 s, default 0 Electromagnetic according to 2014/30/EU, 2014/35/EU and EN61321-1
0:_, 1:_↓↑ P, 2: P↑↓_, 3:_↑ P↓_, compatibility standard requirements
219 Control logic for relay RE1


4: P↓_↑ P
Factory settings


0:_, 1:_↓↑ P, 2: P↑↓_, 3:_↑ P↓_,


220 Control logic for relay RE2 Hydrogen detector-transmitter


4: P↓_↑ P Target gas Hydrogen




221 LOW setpoint for relay RE1 -32000...+32000, gas or T units Gas unit 0,1 % LEL
222 HIGH setpoint for relay RE1 -32000...+32000, gas or T units OUT1 assignment and scale 2: gas, 0 - 100% LEL
223 LOW setpoint for relay RE2 -32000...+32000, gas or T units OUT2 assignment and scale 2: gas, 0 - 100% LEL E2611-H2
224 HIGH setpoint for relay RE2 -32000...+32000, gas or T units RE1 assignment and logic 2: gas, 1: on at high values
258 Measured temperature -4000...+12500 T units (0,01 °C) RE1 HIGH setpoint (set) 20% LEL
259 Gas concentration 0...65535 gas units RE1 LOW setpoint (release) 16% LEL User manual
261 0% value of OUT1 -32000...+32000 gas units / integer °C RE2 assignment and logic 2: gas, 1: on at high values
262 100% value of OUT1 -32000...+32000 gas units / integer °C RE2 HIGH setpoint (set) 50% LEL
263 0% value of OUT2 -32000...+32000 gas units / integer °C RE2 LOW setpoint (release) 40% LEL
264 100% value of OUT2 -32000...+32000 gas units / integer °C
* - the new value is applied after restart 0
Broadcast ID=0 may be used to assign a new ID to device with unknown ID Evikon MCI OÜ Teaduspargi 7, Tartu [email protected]