electrical-engineering-portal.com http://electrical-engineering-portal.

com/electrical-thumb-rules-you-must-follow-part-6

Electrical Thumb Rules You MUST Follow (Part 6)


jiguparmar

Electrical Thumb Rules You MUST Follow, Part 6 (On photo: View in the Transformer Room in the underground area during White House
renovation on March 26, 1952 - via trumanlibrary.org)

Continued from: Electrical Thumb Rules You MUST Follow (Part 5)

12 electrical thumb rules to follow:


1. Transformer earthing wire / Strip size
2. Motor earthing wire / Strip size
3. Panel earthing wire / Strip size
4. Electrical equipment earthing
5. Earthing wire (As per BS 7671)
6. Area for transformer room: (As per NBC-2005)
7. Span of transmission line (Central electricity authority)
8. Max. lock rotor amp for 1-phase 230V motor (NEMA)
9. Three phase motor code (NEMA)
10. Service factor of motor
11. Type of contactor
12. Contactor coil

1. Transformer earthing wire / Strip size

Size of T.C or DG Body Earthing Neutral Earthing

<315 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip

315 KVA to 500 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip

500 KVA to 750 KVA 25×3 mm Cu / 40×6 mm GI Strip 40×3 mm Cu Strip

750 KVA to 1000 KVA 25×3 mm Cu / 40×6 mm GI Strip 50×3 mm Cu Strip

Go back to Rules ↑

2. Motor earthing wire / Strip size

Size of Motor Body Earthing

< 5.5 KW 85 SWG GI Wire

5.5 KW to 22 KW 25×6 mm GI Strip

22 KW to 55 KW 40×6 mm GI Strip

>55 KW 50×6 mm GI Strip

Go back to Rules ↑

3. Panel earthing wire / Strip size

Type of Panel Body Earthing

Lighting & Local Panel 25×6 mm GI Strip

Control & Relay Panel 25×6 mm GI Strip

D.G & Exciter Panel 50×6 mm GI Strip

D.G & T/C Neutral 50×6 mm Cu Strip

Go back to Rules ↑

4. Electrical equipment earthing

Equipment Body Earthing

LA (5KA,9KA) 25×3 mm Cu Strip


HT Switchgear 50×6 mm GI Strip

Structure 50×6 mm GI Strip

Cable Tray 50×6 mm GI Strip

Fence / Rail Gate 50×6 mm GI Strip

Go back to Rules ↑

5. Earthing wire (As per BS 7671)

Cross Section Area of Phase, Neutral Conductor(S) Minimum Cross Section area of Earthing Conductor
mm2 (mm2)

S<=16 S (Not less than 2.5 mm2)

16<S<=35 16

S>35 S/2

Go back to Rules ↑

6. Area for transformer room: (As per NBC-2005)

Transformer Min. Transformer Min. Total Sub Station Area( Incoming HV,LV Min. Space
Size Room Area (M2) Panel, T.C Roof) (M2) Width (Meter)

1 x 160 14 90 9

2 x 160 28 118 13.5

1 x 250 15 91 9

2 x 250 30 121 13.5

1 x 400 16.5 93 9

2 x 400 33 125 13.5

3 x 400 49.5 167 18

2 x 500 36 130 14.5

3 x 500 54 172 19

2 x 630 36 132 14.5

3 x 630 54 176 19

2 x 800 39 135 14.5

3 x 800 58 181 14

2 x 1000 39 149 14.5

3 x 1000 58 197 19
- The capacitor bank should be automatically switched type for substation of 5MVA and higher.
- Transformer up to 25 KVA can be mounted direct on pole.
- Transformer from 25 KVA to 250KVA can be mounted either on “H” frame of plinth.
- Transformer above 250 KVA can be mounted plinth only.
- Transformer above 100 MVA shall be protected by drop out fuse or circuit breaker.

Go back to Rules ↑

7. Span of transmission line (Central electricity authority)

Voltage Normal Span

765 KV 400 to 450 Meter

400 KV 400 Meter

220 KV 335,350,375 Meter

132 KV 315,325,335 Meter

66 KV 240,250,275 Meter

Go back to Rules ↑

8. Max. lock rotor amp for 1-phase 230V motor (NEMA)

HP Amp

1 HP 45 Amp

1.5 HP 50 Amp

2 HP 65 Amp

3 HP 90 Amp

5 HP 135 Amp

7.5 HP 200 Amp

10 HP 260 Amp

Go back to Rules ↑

9. Three phase motor code (NEMA)

HP Code

<1 HP L

1.5 to 2.0 HP L,M

3 HP K
5 HP J

7 to 10 HP H

>15 HP G

Go back to Rules ↑

10. Service factor of motor

HP Synchronous Speed (RPM)

3600 RPM 1800 RPM 1200 RPM 900 RPM 720 RPM 600 RPM 514 RPM

1 HP 1.25 1.15 1.15 1.15 1 1 1

1.5 to 1.25 HP 1.15 1.15 1.15 1.15 1.15 1.15 >1.15

150 HP 1.15 1.15 1.15 1.15 1.15 1.15 1

200 HP 1.15 1.15 1.15 1.15 1.15 1 1

> 200 HP 1 1.15 1 1 1 1 1

Go back to Rules ↑

11. Type of contactor

Type Application

AC1 Non Inductive Load or Slightly Inductive Load

AC2 Slip Ring Motor, Starting, Switching OFF

AC3 Squirrel Cage Motor

AC4,AC5,AC5a, AC5b,AC6a Rapid Start & Rapid Stop

AC 5a Auxiliary Control circuit

AC 5b Electrical discharge Lamp

AC 6a Electrical Incandescent Lamp

AC 6b Transformer Switching

AC 7a Switching of Capacitor Bank

AC 7b Slightly Inductive Load in Household

AC 5a Motor Load in Household

AC 8a Hermetic refrigerant compressor motor with Manual Reset O/L Relay

AC 8b Hermetic refrigerant compressor motor with Automatic Reset O/L Relay

AC 12 Control of Resistive Load & Solid State Load


AC 13 Control of Resistive Load & Solid State Load with Transformer Isolation

AC 14 Control of small Electro Magnetic Load (<72 VA)

AC 15 Control of Electro Magnetic Load (>72 VA)

Go back to Rules ↑

12. Contactor coil

Coil Voltage Suffix

24 Volt T

48 Volt W

110 to 127 Volt A

220 to 240 Volt B

277 Volt H

380 to 415 Volt L

Go back to Rules ↑