PROTECTION RELAYS
FMR-Ts
Feeder manager relay
Three-phase Current, Voltage and Earth Fault ■ Diagnostic and functional test with checking
multifunction relay for protection and manage- of program routines and memory contents,
ment of MV/HV distribution lines. Real time running every time the auxiliary power supply
measurement of the primary value of the input is switched on.
quantities are continuously available from relay’s ■ Dynamic functional test running during
display and from the serial communication port. continuously normal operation.
■ Complete Test (including or not including
Relay’s programming and setting can be made output relays) activated by the keyboard or
directly by the front face keyboard or via the serial via the communication bus.
communication ports. Setting, event recording
and oscillography are stored into non volatile Any internal fault detected is indicated by a fault
memory (E2prom). message on the display and by deenergization of
associated I.R.F. output relay.
The relay is fitted with a multivoltage, autoranging
power supply unit self-protected and transformer
isolated.
Besides the normal Watchdog and Powerfail
functions, a comprehensive program of self-test
and self-diagnostic provides:
Protective Functions Technical Characteristics
■ F49 : One Thermal Image element ■ Graphic Display 4.3” (480x262 dots)
■ F50/51/67 : Three levels for phase overcurrent ■ 10 Leds programmable
independentely programmable as directional ■ Multilanguage Display (English/Italian standard,
or non directional available - other on request)
■ F50N/51N/67N : Three levels for Earth Fault
independentely programmable as directional Power Supply Ratings
or non directional ■ Autoranging multivoltage power supply
■ F27/59 : Two over/under voltage levels ■ Type 1 : 24V(-20%) / 110V(+15%) a.c. -
■ F81 : Two over/under frequency levels 24V(-20%) / 125V(+20%) d.c.
■ F46 : Two Negative Sequence current levels ■ Type 2 : 80V(-20%) / 220V(+15%) a.c. -
■ F59Uo : Zero sequence overvoltage level 90V(-20%) / 250V(+20%) d.c.
■ F51BF : Breaker Failure protection
■ F27U1 : One Positive Sequence Communications
overvoltage level ■ 1 RS485 Serial communication port on rear side
■ F59U2/47 : One Negative Sequence ■ 1 RS232 Serial communication port on front
undervoltage level panel
■ F79 : Four shot autoreclosing ■ Modbus RTU / IEC870-5-103 Communication
(optional- FMR-R-Ts) Protocols
■ Two Reactive Power (VAR) control levels ■ Canbus port for external additional modules
(optional) (optional)
■ Two complete setting programs switchable ■ 1 Ethernet 10/100 (RJ45) Serial communication
locally or remotely port on rear side
■ IEC61850 Communication Protocol (Modbus
Recording over TCP-IP optional)
■ Event Recording (last 100 events)
■ Trip Recording (last 20 trips) complete with Expansion Modules (optional)
cause of tripping and values of the input ■ “UX10-4” 10 Digital Inputs and 4 Output Relays
quantities at the moment of trip ■ “14DI” 14 Digital Inputs
■ Oscillographic recording of input quantities ■ “14DO” 14 Output Relays
(8 channels, 32 sample/cycle, 3 sec each)
Execution
Control ■ 2 Module box. (3 modules with 1 expansion,
■ 6 Output Relays user programmable 4 modules with 2 expansion)
■ 4 Digital Inputs user programmable ■ IP44 protection case (on request IP54)
■ Blocking input and output for pilot wire ■ Totally draw-out execution
selectivity coordination
■ Time tagging resolution 1ms. Software
■ Trip circuit supervision ■ MSCom2 Program interface for device
■ Associated Circuit Breaker control management
(OPEN / CLOSE)
■ Breaker interruption energy ∑i2t
■ Complete autodiagnostic program with
dedicated relay
Real Time Measurements
Pa, Qa = Active, Reactive +Wh,+Rh =Active, Reactive
Ia = current of phase A Va = Voltage of phase A
Power of phase A Exp. Energy
Pb, Qb = Active, Reactive Wh,-Rh =Active, Reactive
Ib = current of phase B Vb= Voltage of phase B
Power of phase B Imp. Energy
Pc, Qc = Active, Reactive
Ic = current of phase C Vc = Voltage of phase C
Power of phase C
P, Q = Average of Active,
Io = neutral current cosφ =Power Factor A,B,C
Reactive Power
F49 (T>): Thermal Image element with prealarm
Function enabling Disable / Enable
Operation Mode Opmod = (I1 I2 / Imax)
Temperature prealarm Tal =(10 ÷ 100)%Tn step 1 %Tn
Continuous admissible current Is = (0.5 ÷ 1.5) step 0.01
Time constant Kt = (1 ÷ 600)min step 0.01min
1F - 67/50/51/51V (1I>): 1st Overcurrent Element
Function enabling ON - OFF
Time current curves f(t) = Indep.Definite Time (D), IEC (A/B/C), IEEE (MI/VI/I/EI/SI)
Operation Mode f(a) = Non Directional - Directional Supervision - Total Directional
Voltage restraint f(U) = ON - OFF
Setting range Is = (0.1 ÷ 4)In step 0.01In
Characteristic sensitivity direction a = (0 ÷ 359)° step 1°
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
2F & 3F - 67/50/51 (2I> & 3I>): 2nd & 3rd Overcurrent Elements - Individually Programmable
Function enabling ON - OFF
Operation Mode f(a) = Non Directional - Directional Supervision - Total Directional
Voltage restraint f(U) = ON - OFF
Current setting range Is = (0.1 ÷ 40) In step 0.01 In
Characteristic sensitivity direction a = (0 ÷ 359)° step 1°
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
Stabilization on Inrush current
Automatic doubling of the operation level 2I> and/or 3I> 2x1I> = Disable / Enable
Activation level di/dt = ≥25 In/s
Revert level I< 1.25In
1F - 67N/50N/51N (1Io>): 1st Earth Fault Element
Function enabling Disable / Enable
Time current curves f(t) = Indep.Definite Time (D), IEC (A/B/C), IEEE (MI/VI/I/EI/SI)
Operation Mode f(ao) = Non Directional - Total Directional
Setting range Is = (0.01 ÷ 4)On step 0.01On
Minumum level of residual voltage for
Vo = (0 ÷ 20)%Un step 0.1%Un
directional element
Characteristic sensitivity direction ao = (0 ÷ 359)° step 1°
Trip sector amplitude az = (0 ÷ 359)° step 1°
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
2F & 3F - 67N/50N/51N (2Io> & 3Io>): 2nd & 3rd Earth Fault Elements - Individually programmable
Function enabling Disable / Enable
Operation Mode f(ao) = Non Directional - Total Directional
Characteristic sensitivity direction ao = (0 ÷ 359)° step 1°
Trip sector amplitude az = (0 ÷ 359)° step 1°
Setting range Is = (0.01 ÷ 9.99)On step 0.01On
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F - 46 (1Is>): 1st Negative Zero Sequence Element
Function enabling Disable / Enable
Time current curves f(t) = Indep.Definite Time (D), IEC (A/B/C), IEEE (MI/VI/I/EI/SI)
Setting range Is = (0.1 ÷ 4)In step 0.01In
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
2F - 46 (2Is>): 2nd Negative Zero Sequence Element
Function enabling Disable / Enable
Setting range Is = (0.1 ÷ 4)In step 0.01In
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F & 2F - 59 (1U> & 2U>): 1st & 2nd Maximum Voltage Elements - Individually programmable
Function enabling Disable / Enable
Setting range Us = (10 ÷ 190)%Un step 1%Un
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F & 2F - 27 (1U< & 2U<): 1st & 2nd Minimum Voltage Elements - Individually programmable
Function enabling Disable / Enable
Setting range Us = (10 ÷ 190)%Un step 1%Un
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F & 2F - 81> (1f> & 2f>): 1st & 2nd Maximum Frequency Elements - Individually programmable
Function enabling Disable / Enable
Setting range fs = (40 ÷ 70)Hz step 0.01Hz
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 1000)s step 0.01s
1F & 2F - 81< (1f< & 2f<): 1st & 2nd Minimum Frequency Elements - Individually programmable
Function enabling Disable / Enable
Setting range fs = (40 ÷ 70)Hz step 0.01Hz
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 1000)s step 0.01s
1F & 2F - 59Uo (1Uo> & 2Uo>): 1st & 2nd Maximum Zero Sequence Overvoltage Elements -
Individually programmable
Function enabling Disable / Enable
Setting range Us = (1 ÷ 100)%Un step 1%Un
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F - 27U1 (U1<): Positive Sequence Undervoltage Element
Function enabling Disable / Enable
Setting range Us = (10 ÷ 190)%Un step 1%Un
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F - 59U2/47 (U2>): Negative Sequence Overvoltage Element
Function enabling Disable / Enable
Setting range Us = (10 ÷ 190)%Un step 1%Un
Instantaneous output ≤0.03s
Independent time delay ts = (0.02 ÷ 100)s step 0.01s
1F - (Wi): Circuit Breaker Energy Maintenance
Function enabling Disable / Enable
Conventional interruption current Ii = (0.1 ÷ 99)In step 0.1In
Max Energy before maintenance Wi = (1 ÷ 9990) step 1
Breaker Failure Element
Alarm time delay tBF = (0.05 ÷ 0.75)s step 0.01s
Trip Circuit Supervision Element
Function enabling Disable / Enable
Independent time delay ts = (0.1 ÷ 100)s step 0.01s
Trip circuit voltage = (24 ÷ 250)Vdc
F79 : Autoreclose(option FMR-R)
Selection of function “initiating” the autoreclose shot (t1I> - t2I> - t3I> - t4I> - t1Io> - t2Io> - t3Io> - t4Io>):
First shot Sh1 (t1I> - t2I> - t3I> - t4I> - t1Io> - t2Io> - t3Io> - t4Io>); any combination
Second shot Sh2 (t1I> - t2I> - t3I> - t4I> - t1Io> - t2Io> - t3Io> - t4Io>); any combination
Third shot Sh3 (t1I> - t2I> - t3I> - t4I> - t1Io> - t2Io> - t3Io> - t4Io>); any combination
Fourth shot Sh4 (t1I> - t2I> - t3I> - t4I> - t1Io> - t2Io> - t3Io> - t4Io>); any combination
Reclosing time delay for each shot:
First shot Sht1 (0.1 ÷ 300)s step 0.1s
5
Second shot Sht2 (0.1 ÷ 300)s step 0.1s
Third shot Sht3 (0.1 ÷ 300)s step 0.1s
Fourth shot Sht4 (0.1 ÷ 300)s step 0.1s
Reset (Reclaim) time : tr = (0.1 - 300)s, step 1s
Protection Relays
Connection Diagram
FMR-Ts
Connection Diagram
FRONT - USB
Typical Characteristics
Accuracy at reference value of influencing factors 1% In - 0.1%On for measurements
2% + to (to=20 ¸ 30ms @ 2xIs) for times
Rated current In = 1A or 5A - On = 1A or 5A
Current overload 80In for 1 sec; 4In continuous
Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral : 0.01VA at On = 1A; 0.2VA at On = 5A
Rated voltge Un = (100 ¸ 125)V
Voltage overload 2Un continuous
Typical Characteristics
Accuracy at reference value of influencing factors 1% In - 0.1% On for measure
2% + to (to=20 ÷ 30ms @ 2xIs) for times
Rated Current In = 1 or 5A - On = 1 or 5A
Current overload 80 In for 1 sec; 4 In continuous
Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral : 0.01VA at In = 1A ; 0.2VA at In = 5A
Rated Voltage Un = 100 ÷ 125V
Voltage Overload 2Un continuous
Burden on voltage input 0.1 VA at Un
Averange power supply consumption <10 VA
Output Relays rating 5 A; Vn = 380 V
A.C. resistive swictching = 1100W (380V max)
make= 30 A (peak) 0.5 sec.
break = 0.3 A, 110 Vcc,
Order Code - Example
FMR-Ts or FMR-R-Ts 1 2 1 1 1
Communication
Power Supply Configuration 1st Expansion 2nd Expansion
Protocol
R1 (14-25) module module
1 = ModbusRTU
1 = Type 1 1 = N.O. 1 = None 1 = None
(standard)
2 = Type 2 2 = N.C. 2 = UX10-4 2 = UX10-4 2 = Modbus TCP-IP
3 = 14DI 3 = 14DI 3 = IEC61850
4 = 14DO 4 = 14DO
The technical specifications reported are not binding and they should be agreed in the contract.
For further technical information on our
products visit www.microelettrica.com
Microelettrica Scientifica S.p.A.
20090 Buccinasco (MI) , Via Lucania 2, Italy
TS03-ING-R0-FMR-Ts
Tel.: +39 02 575731
E-mail:
[email protected]www.microelettrica.com
This publication may be subject to alteration without prior notice. Therefore, a printed copy of this document may not be the late st revision. Please contact your local representative for the latest update. The trademarks K Microelettrica, Knorr and Knorr-Bremse as well as the figurative
mark “K” are registered. Copyright © Knorr-Bremse AG and Microelettrica Scientifica S.p.A. - all rights reserv ed, including industrial property rights application. Knorr-Bremse AG and Microelettrica Scientifica S.p.A. retain any power of dispo sal, such as for copying and transferring