Machine Translated by Google
Compiled all-in-one hardware manual
1. Hardware parameter table
project Specification
model GC-043 series GC-050 series GC-070, GC-070S series
display size 4.3 inches 5 inch 7 inch
Resolution (pixels) 480x272 800x480 800x480
touch panel 4-line high-precision touch screen
Display color 262,144
backlight LED
module 400:1
contrast 400ÿcd/mÿ² 400ÿcd/mÿ² 350ÿcd/mÿ²
brightness memory DDRI 32M/FLASH 128M
FCC compatibility Comply with FCC, CLASS A
Pressure test 1000VAC,1 minute
CE Complies with EN55022 and EN55024 standards
certification protection level Front shell IP65
Shell material PC+ABS
Power supply power 24V
consumption 5W 5W 6W
USB device port Support downloading, online monitoring
U disk port Supports importing and exporting files via USB flash drive
Ethernet port none GC070 None; GC-070S optional
RS232 none
RS485 HMI has 1 channel. HMI and PLC have 1 channel each. HMI and PLC have 1 channel each.
Working environment -10ÿ to 65ÿ
temperature Working 10-90%RH
environment humidity Shock resistance 10-58HE(XYZ direction 2G/30 minutes)
Appearance size 150x93x43.5mm 165×103×56mm 203×145×55mm
Hole Size 141x84mm 157×95mm 192×138mm
Machine Translated by Google
2. HMI interface and PLC terminal description
1. GC-043 series display controller (GC-043-16M4AI-C as an example)
PLC terminal
serial number Interface function
Digital input. Among them, X0 and X1 are high-speed input ports, and 24V and 0V are internal output voltages.
ÿ
interface.
Digital output. Among them, Y0 and Y1 are high-speed output ports, PD is output protection, connected to the output
ÿ
Positive power supply.
ÿ Analog input AI0 - AI3 interface. Among them, NTC and GND are the cold-end thermistor interfaces.
HMI interface
ÿÿÿ ÿ
Serial Interface function
Power input interface
485 communication port
U disk port
number ÿ ÿ ÿ ÿ USB communication port
Machine Translated by Google
2. GC-050 series display controller (GC-050-32MAI-C)
PLC terminal
serial number Interface function
Digital input. Among them, X0 and X1 are high-speed input ports, and 24V and 0V are internal output voltages.
ÿ
interface.
Digital output. Among them, Y0 and Y1 are high-speed output ports, PD is output protection, connected to the output
ÿ
Positive power supply.
ÿAnalog input AI0 - AI3 interface. Among them, NTC and GND are the cold-end thermistor interfaces.
ÿ 485 communication port (COM2)
HMI interface
Serial Interface function
Power input interface
485 communication port
null
U disk port
number ÿ ÿ ÿ ÿ ÿ USB communication port
Machine Translated by Google
3. GC-070 series display controller (GC-070-32MAA-C as an example)
PLC terminal
serial number Interface function
Digital input. Among them, X0 and X1 are high-speed input ports, and 24V and 0V are internal outputs.
ÿ
voltage interface.
Digital output. Among them, COM0 is the common terminal of high-speed output ports Y0 and Y1, and COM1 is
ÿ
The remaining Y points are common terminals; PD0 and PD1 are output protection and are connected to the positive pole of the output power supply.
ÿÿ Voltage/current analog input AI0 - AI3 interface.
ÿÿ Temperature analog input AI4-AI7 interface.
Voltage/current analog output AO0, AO1 interface.
485 communication port (COM2)
HMI interface
Serial Interface function
Power input interface
485 communication port
U disk port
USB communication port
number ÿ ÿ ÿ ÿ ÿ null
Machine Translated by Google
4. GC-070S series display controller (GC-070S-32MAA-C)
PLC terminal
serial number Interface function
Digital input. Among them, X0 - X3 are high-speed input ports, and 24V and 0V are internal output voltages.
ÿ
interface.
Digital output. Among them, COM0 is the common terminal of high-speed output port Y0 - Y3, and COM1 is
ÿ
The remaining Y points are common terminals; PD0 and PD1 are output protection and are connected to the positive pole of the output power supply.
ÿÿ Voltage/current analog input AI0 - AI3 interface.
ÿÿ Temperature analog input AI4-AI7 interface.
Voltage/current analog output AO0, AO1 interface.
485 communication port (COM2)
HMI interface
Serial Interface function
Power input interface
485 communication port
U disk port
USB communication port
number ÿ ÿ ÿ ÿ ÿ Ethernet port
Machine Translated by Google
3. AIAO specifications and wiring instructions
1. Analog input specifications and wiring diagrams of GC-043 and GC-050 series models
GC-043-16M2AI-C, GC-043-16M4AI-C and GC-050-32MAI-C models include 2, 4 and 4 AI input
channels respectively. A+, RA, A- correspond to AI0 channel, B+, RB, B- correspond to AI1 channel, and
so on. There are 4
optional modes for each AI channel: ÿ
Voltage analog input range: 0~5V; ÿ Current
analog input range: 4~20mA; ÿ K-type
thermocouple input, temperature measurement range: -50ÿ ~
900ÿ ; ÿ T-type thermocouple input, temperature measurement range: -250ÿ ~ 400ÿ;
Notes: 1. In
voltage and current mode, the data type of the AI register is a 16-bit unsigned integer; 2. In the temperature mode,
the data type of the AI register is a 16-bit signed integer, and the displayed value is 10 times the actual temperature (for example, 254 is displayed ,
which means the current measured temperature is 25.4ÿ). If the thermocouple or thermistor is disconnected or the temperature measurement value
exceeds the range, the AI register of the corresponding channel displays 32767; 3. In thermocouple mode, the thermistor must be
connected to NTC and GND for measurement. Cold end temperature. The AI30 register displays the cold-junction temperature measurement value
shared by AI0 and AI1 channels, and the AI31 register displays the cold-junction temperature measurement value shared by AI2 and AI3 channels.
If the temperature measurement value of the cold end thermistor is abnormal, the AI30/AI31 register displays -32767; 4. When installing the
temperature sensor,
the temperature measurement part of the thermocouple should avoid contact with objects that are not temperature measurement targets. At the
same time, the length of unshielded wires should be minimized to avoid exposure of wires to reduce external interference and reduce the impact on
temperature measurement accuracy.
•Analog voltage input type •Analog current input type
B- B-
250ÿ 250ÿ
-
RB RB
+
B+ B+
A- A-
250ÿ -
250ÿ
DA DA
+
A+ A+
Samkoon Controller
Samkoon Controller
Machine Translated by Google
•K/T type thermocouple analog input
B-
250ÿ
RB
+
B+
A-
250ÿ
DA
+
A+
Samkoon Controller
Machine Translated by Google
2. Analog input and output specifications and wiring diagrams of GC-070 and GC-070S series models
(1) Voltage/current analog input
GC-070-24MAA-C, GC-070-32MAA-C, GC-070S-32MAA-C have 4 voltage/current modes
Quasi-quantity input channels AI0~AI3. A+, RA, A- correspond to AI0 channel, B+, RB, B- correspond to AI1 channel
Tao, and so on.
There are three optional modes for AI0~AI3:
ÿ Voltage analog input range: 0~5V
ÿ Voltage analog input range: 0~10V
ÿ Current analog input range: 4~20mA
Precautions:
In voltage and current mode, the data type of the AI register is 16-bit unsigned integer.
•Analog voltage input type •Analog current input type
D- D-
250ÿ 250ÿ
-
RD RD
+
D+ D+
C- C-
250ÿ -
250ÿ
RC RC
+
C+ C+
B- B-
250ÿ 250ÿ
-
RB RB
+
B+ B+
A- A-
250ÿ -
250ÿ
DA DA
+
A+ A+
Samkoon Controller Samkoon Controller
Machine Translated by Google
(2) Temperature analog input
GC-070-24MAA-C, GC-070-32MAA-C, GC-070S-32MAA-C has 4 temperature analog input channels AI4~AI7. A0,
A1, and A3 correspond to the AI0 channel, B0, B1, and B3 correspond to the AI1 channel, and so on. There are 4
optional modes for AI4~AI7: ÿ PT100 thermal resistance
input, temperature measurement range: -200ÿ ~ 850ÿ; ÿ NI120 thermal
resistance input, temperature measurement range: -80ÿ ~ 260ÿ; ÿ K-type
thermocouple Input, temperature measurement range: -50ÿ ~ 900ÿ; ÿ
T-type thermocouple input, temperature measurement range: -250ÿ ~ 400ÿ;
Precautions:
1. In temperature mode, the AI register data type is a 16-bit signed integer, and the displayed value is 10 times the actual temperature.
(If 254 is displayed, it means the current measured temperature is 25.4ÿ). If a thermocouple, RTD or built-in cold junction thermistor
In case of abnormal situations such as disconnection and temperature measurement value exceeding the range, the AI register of the corresponding channel displays 32767;
2. The AI30 register displays the cold-junction temperature measurement value shared by AI0 and AI1 channels, and the AI31 register displays the cold-junction temperature
measurement value shared by AI2 and AI3 channels. If the temperature measurement value of the cold junction thermistor is abnormal, the AI30/AI31 register will display
-32767. There is no need to refer to the cold junction temperature in thermal resistance
mode; 3. When a certain temperature measurement channel is not in use, it is best to turn it off to avoid affecting other channels;
4. When installing the temperature sensor, the temperature measurement part of the thermocouple should avoid contact with objects that are not temperature measurement targets. At the same time, try your best to
Reduce the length of unshielded wires and avoid exposed wires to reduce external interference and reduce the impact on temperature measurement accuracy.
•K type thermocouple temperature analog input type •PT100 temperature analog input type (three-wire connection method)
A3 A3
NC NC
A1 A1
RTD
A0 + A0
B3 B3
NC NC
B1 B1
RTD
B0 + B0
C3 C3
NC NC
C1 C1
RTD
C0 + C0
D3 D3
NC NC
D1 D1
RTD
D0 + D0
Samkoon Controller Samkoon Controller
Machine Translated by Google
(3) Analog output
GC-070-24MAA-C, GC-070-32MAA-C and GC-070S-32MAA-C have 2 analog output channels AO0 and
AO1. M0, V0, and I0 correspond to the AO0 channel, and M1, V1, and I1 correspond to the AO1 channel.
There are 3 optional modes for AO0 and
AO1: ÿ Voltage analog output range: 0~5V
ÿ Voltage analog output range: 0~10V ÿ
Current analog output range: 4~20mA
•Output voltage type •Output current type
V0- I0-
M0 M0
V0+
V0 V0
I0+
I0 I0
V1- I1-
M1 M1
V1+
V1 V1
I1+
I1 I1
M2 M2
V2 V2
I2 I2
M3 M3
V3 V3
I3 I3
Samkoon Controller Samkoon Controller