CHAPTER 17
CHAPTER 17
INDEX
ii. MIT
iii. SIEMENS
1. 7SR21
2. 7SR12
3. 7SR1003
4. 7SR1053
iv. ABB
1. REB
2. REM
3. RET
4. REF
v. MICOM
1. P120, P121, P122, P123
2. P127
3. P211
4. P220, P225
5. P141, P142, P143, P145.
6. P921, P922, P923.
vi. AREVA
1. P120, P121, P122, P123
2. P127
3. P211
4. P220, P225
5. P141, P142, P143, P145.
6. P921, P922, P923.
vii. SEL
viii. SEPAMP
ix. VAMP
x. GE
xi. SIPROTEC
xii. BECKWORTH
xiii. SFT2841
xiv. Transducers.
Relay purpose:
The static motor protection relays type CTMM and CTMFM measure the load current
and the unbalance current independently, and provide accurate protection against
thermal damage under all operating conditions. The thermal characteristic of the
relay is designed to follow closely the thermal withstand characteristic of typical
motors; this ensures that the relay isolates the motors only when the insulation life is
threatened.
MODELS AVAILABLE:
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE:
Provide the aux supply for the terminals at 5,6 and check the power indication if the
relay is ON. Aux supply will remain the same throughout the testing procedure, also
check if the multiplication factor K is set to 1 (k=1).
Feedback terminals:(3,4)
3. Now for the given service settings calculate the relay trip time.
4. Inject 3.27 times of knob settings and check the tripping g time
for the respected curve.
For example: current to be injected = (1 x 3.27)In [if In=1]
=3.27 A
Current to be injected = (1 x 3.27)In [if In=5]
=16.35 A
6. Now change the top and bottom thermal knob both to 0.65
and check the relay trip for same curve.
=2.12 A
Current to be injected = (0.65 x 3.27)In [if In=5]
=10.6 A
7. Now inject 2.12A (if In=1) at injection terminal the relay will trip
at 32 sec.
For testing phase over current keep all the knobs related to stall and
unbalance to ON position (move all the knob to right side) this is to avoid the
relay to trip in stall and unbalance before it trips in over current.
3. Now for the given service settings calculate the relay trip time.
Note: For further details verify relay manuals, testing kit manuals and related
relay kit operating procedure.
2. O/C AND E/F RELAY DETAILS - Model no: CDG
(INTANTANEOUS, INVERSE, VERY INVERSE, EXTREMLY
INVERSE)
Different relays are used for industrial power system protection are CDG-11,
CDG-12, CDG-13, CDG-14.
Improved version of theses relays CDG21 to CDG64 are also utilized to full fill
different protection requirement. To provides selective over current and earth
fault protections, CDG-11 is used with A.C machine and power systems. It is
characterized by heavily damps inverse definite minimum time/current
characteristic.
CDG 21 is improved version of CDG 21 where CDG 11 equipped with
instantaneous feature.
CDG-31 is the 3 phase version of CDG-11and CDG-61 is the improved
version of CDG-21 for 3 phase supply.
CDG 12 have different characteristic such as it is characterized by long
inverse definite minimum time/ current characteristic.
CDG 22 is improved version of CDG 12 where CDG 12 equipped with
instantaneous feature.
CDG-32 is the 3 phase version of CDG-12 and CDG-62 is the improved
version of CDG-22 for 3 phase supply.
CDG 13 have different characteristic such as it is characterized by very
inverse definite minimum time/ current characteristic.
CDG 23 is improved version of CDG 13 where CDG 13 equipped with
instantaneous feature.
CDG-33 is the 3 phase version of CDG-13 and CDG-63 is the improved
version of CDG-23 for 3 phase supply.
CDG 14 have different characteristic such as it is characterized by extremely
inverse definite minimum time/ current characteristic.
CDG 24 is improved version of CDG 14 where CDG 14 equipped with
instantaneous feature.
CDG-34 is the 3 phase version of CDG-14 and CDG-64 is the improved
version of CDG-24 for 3 phase supply [18].
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
NOTE: For example, CDG11 is a single unit (E/F) and CDG31 is a three unit (2-O/C
& 1-E/F)
TMS: (TMS and PSM can be taken as any equivalent values from the scale given in
the relay)
PSM: (TMS and PSM can be taken as any equivalent values from the scale given in
the relay)
TMS *1.6
NOTE: Relay with instantaneous O/C or E/F unit does not have PSM and TMS and
those relays are based on the current settings knob and these relays will trip
instantaneously.
TESTING PROCEDURE
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
For example: This will be almost same for all relay with over current and earth
fault units combined (CDG33 relay testing is mentioned as example)
Steps
Move the SET KNOB pin for another value, need to take four values.
SUPPLY TERMINALS (FOR ALL FLAG TRIP): +ve =3 & -ve =12 or +ve =3 & -ve
=8 [contacts may vary]
For flag trip rotate the disc from initial position by hand until it touches the contact,
when it touches contact flag will get trip.
CONNECTION DIAGRAM FOR CDG 11 (almost same for all single unit variant
relays):
CONNECTION DIAGRAM FOR CDG 31 (almost same for all three unit variant
relays):
NOTE: CDG
While testing single unit earth fault relay types (for example CDG11) follow only the
earth fault unit testing procedure. Here we have given the CDG11 and CDG33
connection diagram whereas other relay types will be the variants of these two relays
as mentioned below the introduction part.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
CT SEC = 1AMP,50HZ
Model no:CAG14
SCALE: 0.1-0.15-0.2-0.25-0.3-0.35-0.4
CT TERMINALS: 9 & 10
TESTING PROCEDURE
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
2. CAG14 is a single CT input restricted earth fault relay. Hence provide a CT
input from the kit at 9 & 10 terminals.
3. (1,2) or (3,4) can be used as feedback terminals set the values in the scale as
0.1 for the relay to trip when 0.1A injected through kit.
4. Vary the scale for two to three readings.
For example:
Current injected from the kit – 0.15 (at this condition relay will trip and the NO
contacts becomes NC).
NOTE: CAG14
Vary the current settings in the scale and similarly check for relay operation.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
CT SEC = 1AMP,50HZ
SCALE: 0.1-0.15-0.2-0.25-0.3-0.35-0.4
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
2. CAG34 is a three CT input relay. Hence provide a three CT input (R, Y, B)
from the kit at 5-Rph, 7-Yph, 9-Bph and 6,8,10 are CT neutral terminals.
3. (1,2) or (3,4) can be used as feedback terminals set the values in the scale as
0.1 for the relay to trip when 0.1A injected at any one phase through kit.
4. Vary the scale for two to three readings.
For example:
Current injected from the kit – 0.15 (at this condition relay will trip and the NO
contacts becomes NC)
NOTE: CAG34
Vary the current settings in the scale and similarly check for relay operation.
5.AUXILIARY RELAY (VAA) DETAILS - Model no: VAA 11
VAA relays are voltage operated relays, designed for industrial control duties
requiring respective switching operations. VAA relays are voltage operated
relays.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
TESTING PROCEDURE
2. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil (A OR B) terminal. & measure
the respective pickup voltage of coil and drop off voltage of coil by raising &
decreasing the voltage.
For example:
1. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
2. (before that need to reset the coil) From that set voltage reduce the voltage
level slowly, at one-point coil drop off.
NOTE: VAA11
NOTE: VAA21/22/23 are double pole versions of VAA 11/12/13 respectively. VAA
31/33 are Triple pole versions of VAA 11/12/13 respectively.
6.AUXILIARY RELAY (VAA) DETAILS - Model no: VAA 12
VAA relays are voltage operated relays, designed for industrial control
duties requiring respective switching operations. VAA relays are voltage
operated relays.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
3. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal. & measure the
respective pickup voltage of coil and drop off voltage of coil by raising &
decreasing the voltage.
For example:
3. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
4. (before that need to reset the coil) From that set voltage reduce the voltage
level slowly, at one-point coil drop off.
Let: Drop off voltage: 24V.
NOTE: VAA12
VAA relays are voltage operated relays, designed for industrial control
duties requiring respective switching operations. VAA relays are voltage
operated relays.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
4. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil (A OR B) terminal. & measure
the respective pickup voltage of coil and drop off voltage of coil by raising &
decreasing the voltage.
For example:
5. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
6. (before that need to reset the coil) From that set voltage reduce the voltage
level slowly, at one-point coil drop off.
NOTE: VAA21
VAA relays are voltage operated relays, designed for industrial control duties
requiring respective switching operations. VAA relays are voltage operated
relays.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
NO Contacts: (1,2),(3,4),(13,14),(15,16),(17,18),(19,20).
TESTING PROCEDURE
5. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil (A OR B OR C) terminal. &
measure the respective pickup voltage of coil by raising the voltage.
For example:
7. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
Let: Pickup voltage: 58V for COIL A
8. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
9. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
NOTE: VAA33
APPROPRIATE KIT – OMICRON (Three phase relay testing kit), KINGSINE (Three
phase relay testing kit), EPSEE (Three phase relay testing kit).
Model no:VTX31
TESTING PROCEDURE
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal& measure the
respective pickup voltage of coil by raising the voltage.
2. Give the three phase CT input from the kit at 7-Rph, 8-Yph, 9-Bph and 10- CT
neutral.
3. First inject same current in all the three phase CT and AUX supply through kit,
at this point the relay will not act since the CT sec current is same (which
means CT is healthy).
4. Now vary the current in between the three CT phases through the kit, at this
point the relay will operate at the time delay set.
5. When the relay is operated NO contacts (1,2) or (3,4) will become NC which
is used as feedback to kit.
6. Change the time delay settings and check if the relay is operated after the set
time delay or not.
For example:
After varying the current in the CT phases check if the relay is operated after 3 sec
delay, now change time delay setting and check few more operations to ensure the
relay is healthy.
NOTE: VTX31
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
1. Connect the kit as per proper terminals, ensure proper earthing, and Switch
on the kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
2. Provide AUX supply through kit at 9 & 10 terminals when the terminal 5 & 6
becomes closed (shorted) the timer starts.
3. So once AUX supply given and feedback taken from any NO contacts (1,2) or
(3,4) relay will operate at the set time delay.
4. Relay de-energize once the 5 & 6 terminal short is removed or opened.
For example:
Switch ON the AUX supply and once the terminal 5 & 6 is shorted, the relay will
operate after 3 sec.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TIME DELAY: 0.05 - 0.5/ 0.10 - 1.0/ 0.50 - 5.0/ 1.00 - 10.0/ 2.50 - 25.0 (DELAY
TYPES)
TESTING PROCEDURE
1. Connect the kit as per proper terminals, ensure proper earthing, and Switch
on the kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
2. Provide AUX supply through kit at 9 & 10 terminals when the terminal 5 & 6 is
kept open the timer starts.
3. So once AUX supply given and feedback taken from any NO contacts (1,2) or
(3,4) relay will operate at the set time delay.
4. Relay de-energize once the 5 & 6 terminal is shorted or closed.
For example:
Switch ON the AUX supply and once the terminal 5 & 6 is opened, the relay will
operate after 3 sec.
For VTT12 initially keep the terminal 5 & 6 shorted and provide AUX supply for the
relay to stay un-operated. Once the short is opened after the time delay the relay will
operate.
14. INVERSE TIME OVER CURRENT RELAY DETAILS - Model no: VDG 11
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TMS: 5 (TMS and PSM can be taken as any equivalent values from the scale given
in the relay).
PSM: 1 (TMS and PSM can be taken as any equivalent values from the scale given
in the relay, for example we are 5 as TMS & 1 as PMS since 5&1 are the exact
opposite values in the scale).
TESTING PROCEDURE
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal& measure the
respective pickup voltage of coil by raising the voltage.
2. Now before switching on the coil supply plug in the voltage setting knob at any
one voltage values between 110-120-130-140-150-160-170-180.
For example: Here we set at 120V
Voltage to be injected: 120 x 1(PSM)= 120V
NOTE: VDG11
TMS, PSM and voltage settings may vary based on the relay types.
15. INVERSE TIME OVER CURRENT RELAY DETAILS - Model no: VDG 13
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
Model no:VDG11
TMS: 5 (TMS and PSM can be taken as any equivalent values from the scale given
in the relay).
PSM: 1 (TMS and PSM can be taken as any equivalent values from the scale given
in the relay, for example we are 5 as TMS & 1 as PMS since 5&1 are the exact
opposite values in the scale).
TESTING PROCEDURE
1. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal& measure the
respective pickup voltage of coil by raising the voltage.
2. Now before switching on the coil supply plug in the voltage setting knob at any
one voltage values between 50-60-70-80-90.
For example: Here we set at 90V
Voltage to be injected: 90 x 1(PSM)= 90V
NOTE: VDG13
TMS, PSM and voltage settings may vary based on the relay types.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TMS: 5 (TMS and PSM can be taken as any equivalent values from the scale given
in the relay).
PSM: 10(TMS and PSM can be taken as any equivalent values from the scale given
in the relay, for example we are 5 as TMS & 10 as PMS since 5&10 are the exact
opposite values in the scale).
TESTING PROCEDURE
6. Connect the kit as per proper terminals, ensure proper earthing, and Switch
on the kit. Give supply voltage to the respective coil terminal& measure the
respective pickup voltage of coil by raising the voltage.
7. Now before switching on the coil supply plug in the voltage setting knob at any
one voltage values between 5.4/7.5/12.5/20.
For example: Here we set at 5.4V
Voltage to be injected: 5.4 x 10(PSM)= 54V
4. Now apply 54V from the kit at 9 & 10 terminal the relay will trip at 5sec.
5. Similarly repeat the procedure for different times between 0.1-1.0 and calculate
the exact theoretical time and note down the practical value (from the feedback
used for kit).
NOTE: VDG14
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
8. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
9. Now reduce the voltage to check drop off voltage.
For example:
1. Increase the voltage level slowly, at one-point coil will get energies.
Pick up voltage: 63V (approximate value).
2. Decrease the voltage level slowly, at one-point coil will get de-energies.
Pick up voltage: 33V (approximate value).
NOTE: VAG11
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
NO Contacts: (1,2)
SCALE: 44-51.3-58.6-65.9-73.2-80.5-88
TESTING PROCEDURE
10. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal & measure the
respective pickup voltage of coil by raising the voltage.
For example:
3. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
4. Decrease the voltage level slowly, at one-point coil will get energies & drop-off
the contact.
NOTE: VAGM22
VAJC Relays are fast operating multi contact attracted relays with a high
degree of mechanical stability for control duties where a number of
simultaneous switching operations are required.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
NO Contacts: (1,2),(3,4),(5,6),(7,8),
NC Contacts: (13,14),(15,16),(17,18),(19,20),
TESTING PROCEDURE
11. Connect the kit as per proper terminals, ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal for (trip and reset). &
measure the respective pickup voltage of coil by raising the voltage and reset
voltage of coil by raising the voltage.
For example:
5. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
6. Increase the voltage level slowly, at one-point coil will get energies & reset the
contact.
NOTE: VAJC11
The VAJH tripping relay interfaces the protection to provide the higher contact
capacity, additional contacts for tripping multiple circuit breakers, control
functions, signaling and interlocking.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
MATERIALS NEEDED – CROCODILE PINS, CONNECTING CLIPS, BANANA
PINS (OR) BRASSES PIN, AND CONNECTING CABLE.
TESTING PROCEDURE
12. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal. & measure the
respective pickup voltage of coil by raising the voltage.
For example:
7. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
NOTE: VAJH23
The VAJH tripping relay interfaces the protection to provide the higher
contact capacity, additional contacts for tripping multiple circuit breakers,
control functions, signaling and interlocking.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
Connect the kit as per proper terminals, Ensure proper earthing, Switch on the kit.
Give supply voltage to the respective coil (A OR B) terminal. & measure the
respective pickup voltage of coil by raising the voltage.
For example:
1. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
NOTE: VAJH23
The VAJH tripping relay interfaces the protection to provide the higher
contact capacity, additional contacts for tripping multiple circuit breakers,
control functions, signaling and interlocking.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
NO Contacts: (1,2), (3,4), (5,6), (11,12), (13,14), (15,16), (17,18), (19,20), (25,26),
(27,28), (33,34), (35,36), (41,42), (43,44).
NC Contacts: (21,22), (23,24), (29,30), (31,32), (37,38), (39,40).
TESTING PROCEDURE
13. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal. & measure the
respective pickup voltage of coil by raising the voltage.
For example:
8. Increase the voltage level slowly, at one-point each coil will get energies &
pickups the contact.
NOTE: VAJHM53
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
14. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil terminal. & measure the
respective pickup voltage of coil by raising the voltage.
For example:
9. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
NOTE: VAJH23
The VAJH tripping relay interfaces the protection to provide the higher contact
capacity, additional contacts for tripping multiple circuit breakers, control
functions, signaling and interlocking.
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
TESTING PROCEDURE
15. Connect the kit as per proper terminals, Ensure proper earthing, Switch on the
kit. Give supply voltage to the respective coil (A OR B) terminal. & measure
the respective pickup voltage of coil by raising the voltage.
For example:
10. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
11. Increase the voltage level slowly, at one-point coil will get energies & pickups
the contact.
NOTE: VAJH23
WCD11 is a reverse power protection relay usually used for generators, this
relay operates when the forward power produced by the generator becomes reverse
power WCD11 will trip the generator. For testing of this relay we need aux supply,
3ph CT supply, 3ph VT supply and feedback from 1 output.
APPROPRIATE KIT – OMICRON (Three phase relay testing kit), KINGSINE (Three
phase relay testing kit), EPSEE (Three phase relay testing kit).
CONNECTION DIAGRAM:
VT SUPPLY: R-13/Y-16/B-18
FEEDBACK: 11, 12
AUX SUPPLY: 3, 4
TESTING PROCEDURE:
1. Connect the kit as per proper terminals, ensure proper earthing and Switch
on the kit. Give supply voltage to terminal 3 and 4.
4. Start injecting the current and voltage the relay will trip since it seems to be a
reverse power (current angle is changed so it becomes reverse power).
RELAY WILL NOT TRIP AT THIS CONDITION (low forward power):
16. Connect the kit as per proper terminals, ensure proper earthing and Switch on
the kit. Give supply voltage to terminal 3 and 4.
17. Now fix the VT supply as R-63.5V @ 0’
Y-63.5V @ -120’
B-63.5V @ 120’.
18. Now fix the CT supply as R-3mA @ 0’
Y-3mA @ -120’
B-3mA @ 120’.
19. Start injecting the current and voltage the relay will not trip since it seems to
be a low forward power.
i.e CT – 2500/1
Isec – 3mA
Iprim –7.5 A
Power – 1.732 x 6600 x 7.5 x 0.87 = 75KW approx (which is a low forward
power)
NOTE: we have to change current angles since we are testing reverse power, if we
change the angles(current) to normal angles then the relay should not trip.
WCD13 is a low forward power protection relay usually used for generators,
this relay operates when the forward power produced by the generator become low
below a particular set point WCD13 will trip the generator. For testing of this relay we
need aux supply, 3ph CT supply, 3ph VT supply and feedback from 1 output
APPROPRIATE KIT – OMICRON (Three phase relay testing kit), KINGSINE (Three
phase relay testing kit), EPSEE (Three phase relay testing kit).
CONNECTION DIAGRAM:
VT SUPPLY: R-13/Y-16/B-18
FEEDBACK: 11,12
TESTING PROCEDURE
1. Connect the kit as per proper terminals, ensure proper earthing and Switch
on the kit. Give supply voltage to terminal 3 and 4.
4. Start injecting the current and voltage the relay will not trip since it seems to
be a high forward power.
i.e CT – 2500/1
Isec – 30 mA
Iprim – 75 A
Power – 1.732 x 6600 x 75 x 0.87 = 753KW approx (which is a high forward power)
1. Connect the kit as per proper terminals, ensure proper earthing and Switch
on the kit. Give supply voltage to terminal 3 and 4.
4. Start injecting the current and voltage the relay will not trip since it seems to be a
low reverse power (current angle is changed so it becomes reverse power).
NOTE: we have not changed any current angles since we are testing forward
power. If we change the angles, then also it will not trip because it is low forward
power relay.
Materials needed – Crocodile clamp connected 16sqmm cable (red and black), milli
amps AC clamp meter
Purpose of primary injection – Primary injection test is mainly carried out to ensure
the healthiness of the CT by injecting the primary current using the kit and measuring
the secondary current using milli amp clamp meter.
There are three methods you can measure the secondary current of the CT.
METHOD 1 – Short the secondary terminals of the CT(s1&s2) using a loop
wire and measure the current using milli amps clamp meter on the looped
wire.
METHOD 2 – In case the CT is connected to the relay, find the CT terminal
wires connected in the relay and measure the current using milli amps clamp
meter.
METHOD 3 – If the CT is connected to a numerical relay then the secondary
current can also be checked in the metering menu of the relay.
NOTE: In case the CT is used for transducer instead of relay and the same
method1 & method2 can be used and also secondary current can be seen by
communicating the transducer with the laptop and select DISPLAY
MEASURED option in MXX software.
Connect the crocodile clamp of the 16sqmm cables one before the CT and
one after the CT.
Now connect the other end of the cable one with the neutral current injection
terminal of single phase kit and other cable to (0-100)range kit’s current
injection terminal.
Now power on the kit and change the inject range to (0-100) in the kit using
SEL button (red indication across the ranges will change).
Select ON using the buttons in kit and vary the current using the variable
knob.
Now the current start to inject on the CT primary (current injected can be
observed through display).
Measure the CT ratio with primary current injected and secondary current
measured.
For example – If we inject 50 amps in primary and 0.25 amps
measured in the secondary then the CT ratio is 50/0.25 amp which is nothing
but 200/1 amps
Note: CT secondary will be 1 amp or 5 amp.
Kit used – MEGGER (Single phase relay testing kit), OMICRON (Three phase relay
testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three phase relay
testing kit).
Materials needed –Secondary Injection cable for kit’s, multimeter, connecting clips
and pins.
SECONDARY INJECTIONPROCEDURE
29 SYNCHROSCOPE TESTING
1. Check the coil resistances (two coils) – Coil resistance should be low. (1
Ohm)
2. Apply both sides 110V AC, 50 HZ, 0 PHASE SEQ.
3. If there is no difference between two coils in voltage, phase sequence,
frequency, the pointer will remain motion less at the 12 o’ clock position
on the dial.
4. If frequency same, but difference in phase angle, the pointer deflects in
one direction.
5. When the frequency of both coils same, the pointer becomes stationary.
When their frequency differs then the pointer deflects in one direction.
6. If frequency differs, but phase sequence is same, the pointer will rotate
continuously.
7. If voltage, frequency, phase sequence on both coils equal, Then the
pointer shows 12’0 clock positon, then synchro scope is in working
condition.
Materials needed – Injection cable for kit’s, multimeter, connecting clips and pins.
Kit used – MEGGER (Single phase relay testing kit), OMICRON (Three phase relay
testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three phase relay
testing kit).
Materials needed – Injection cable for kit’s, multimeter, connecting clips and pins.
Relay purpose:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and binary output relay contacts BO3 and other BO (7&8
in compartment `B’ NO contacts) can be used for feedback of tripping; now check
the protection that are enabled and note down the settings. Usually for motor
protection five protections will be enabled as follows.
Note: Protection mentioned here are the general protections used, for other
protection testing verify the manufacturing manuals.
SIEMENS 7SR21 & 7SR22 TESTING PROCEDURE
Relay purpose:
SIEMENS 7SR21 is a commonly used non direction & 7SR22 is commonly used as
a directional feeder protection relay. Which can be used for both HT and LT incomer
feeders. For testing for this relay we need aux supply, 3ph CT supply, 3ph VT supply
and feedback from 1 binary output.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and binary output relay contacts BO4 and other BO
(17&19 in compartment `B’ NO contacts) can be used for feedback of tripping; now
check the protection that are enabled and note down the settings. Usually for motor
protection five protections will be enabled as follows.
Note: Protection mentioned here are the general protections used, for other
protection testing verify the manufacturing manuals.
Relay purpose:
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and binary output relay contacts BO3 and other BO (7&8
in X4 NO contacts) can be used for feedback of tripping; now check the protection
that are enabled and note down the settings. Usually for motor protection five
protections will be enabled as follows.
Relay purpose:
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and binary output relay contacts BO3 and other BO (7&8
in X4 NO contacts) can be used for feedback of tripping; now check the protection
that are enabled and note down the settings. Usually for motor protection five
protections will be enabled as follows.
Relay purpose:
ABB REB 611, REB 650 & REB 670 are commonly used as a Bus bar
protection relay. Which can be used for both HT and LT Bus couplers. For testing of
this relay we need aux supply, 3ph CT supply and feedback from 1 binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts can be
used for feedback of tripping, now check the protection that are enabled and note
down the settings. Usually for motor protection five protections will be enabled as
follows.
Relay purpose:
ABB REF 615, REF 610 & REF 601 are commonly used as a feeder
protection relay. Which can be used for both HT and LT motors. For testing of this
relay we need aux supply, 3ph CT supply and feedback from 1 binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts can be
used for feedback of tripping, now check the protection that are enabled and note
down the settings. Usually for motor protection five protections will be enabled as
follows.
REF 610 – xk2 / (1,2) for E/F & (3,4) for O/C
Note: All these feeder protection relay protections can be used as both
directional and non-directional with instantaneous as well as time delayed
protection the above mentioned protections are the general protection, for
further protection details verify relay manuals, testing kit manuals and related
relay kit operating procedure.
ABB REM 615, REM 610 & REM 611 TESTING PROCEDURE
Relay purpose:
ABB REM 615, REM 610 & REM 611 is commonly used as a motor
protection relay. Which can be used for both HT and LT motors. For testing of this
relay we need aux supply, 3ph CT supply and feedback from 1 binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts SO2-
13 and 14 (NO contacts) can be used for feedback of tripping, now check the
protection that are enabled and note down the settings. Usually for motor protection
five protections will be enabled as follows.
Note: For further details, verify relay manuals, testing kit manuals and related
relay kit operating procedure.
ABB RET 615, RET 620 & RET 630- TRANSFORMER
Relay purpose:
ABB RET 615, RET 620 & RET 630 are commonly used as a
Transformer protection relay. Which can be used for both HT and LT transformer
feeders. For testing of this relay we need aux supply, 3ph CT supply, 3ph VT supply
and feedback from 1 binary output.
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts can be
used for feedback of tripping, now check the protection that are enabled and note
down the settings. Usually for motor protection five protections will be enabled as
follows.
RET 630 –X327 (7,8) (9,10) (11,12) (13,14) (15,16) (17,18) [NO contacts]
Note: All these feeder protection relay protections can be used as both
directional and non-directional with instantaneous as well as time delayed
protection the above mentioned protections are the general protection, for
further protection details verify relay manuals, testing kit manuals and related
relay kit operating procedure.
Relay purpose:
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and output relay contacts 13 and 14 (NO contacts) can
be used for feedback of tripping, now check the protection that are enabled and note
down the settings. Usually for motor protection five protections will be enabled as
follows.
Relay purpose:
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings. Usually for motor protection five protections
will be enabled as follows.
[46] UNBALANCE-
For testing unbalance inject equal current below the thermal setting
value with angle reversed in all three phases in the CT input. Now the relay
has to trip in unbalance.
For example: normal angles are 0,-120,120 reverse it to 0, 120,-120.
Relay will trip in unbalance.
Note: For further details verify relay manuals, testing kit manuals and related
relay kit operating procedure.
Relay purpose:
MICOM P921, P922 and P923 are commonly used as frequency and
voltage protection, used for BUS PT. For testing of this relay we need aux supply,
3ph VT supply and feedback from 1 binary output.
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply, also switch on VT supply as per connection diagram
and programmable tripping output relay contacts 2 and 6 (NO contacts) can be used
for feedback of tripping, now check the protection that are enabled and note down
the settings.
Increase the voltage to 120 V (More than settings) in any one of the phase for
the relay to trip in over voltage.
Note: If IDMT curve is chosen then relay will trip based on the [27] TMS
value.
[81] FREQUENCY-
Under frequency (81<):
For testing of under frequency decrease the frequency
value below the settings value for the relay to trip in under frequency at given
time delay settings.
For example:
Under frequency 81< (F1) setting – 49 (which is 49 Hz)
Time delay 81< (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Over frequency (81>):
For testing of over frequency increase the frequency value
above the settings value for the relay to trip in over frequency at given time
delay settings.
For example:
Over frequency 81> (F1) setting – 51 (which is 51 Hz)
Time delay 81> (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Note: Above mentioned protections are generally used in MICOM P922 relay,
for details on other protections please check with manufacturing manuals.
Relay purpose:
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts E1 and
E2 (NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
Increase the voltage to 120 V (More than settings) in any one of the phase for
the relay to trip in over voltage. If IDMT curve is chosen then relay will trip
based on the [27] TMS value.
Note: Overvoltage (2-stage), configurable as either phase to phase or phase
to neutral measuring. Stage 1 may be selected as either IDMT or DT and
stage 2 is DT only.
[81] FREQUENCY-
Under frequency (81<):
For testing of under frequency decrease the frequency
value below the settings value for the relay to trip in under frequency at given
time delay settings.
For example:
Under frequency 81< (F1) setting – 49 (which is 49 Hz)
Time delay 81< (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Over frequency (81>):
For testing of over frequency increase the frequency value
above the settings value for the relay to trip in over frequency at given time
delay settings.
For example:
Over frequency 81> (F1) setting – 51 (which is 51 Hz)
Time delay 81> (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Note: A 4-stage under frequency and 2-stage over frequency can be used.
Here an advanced frequency protection gives you more advanced options for
a frequency protection.
Note: Above mentioned protections are generally used in MICOM P143 relay,
for details on other protections please check with manufacturing manuals.
MICOM P120, P121, P122 AND P123 TESTING PROCEDURE
Relay purpose:
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
Relay purpose:
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
Relay purpose:
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
[46] UNBALANCE-
For testing unbalance inject equal current below the thermal setting
value with angle reversed in all three phases in the CT input. Now the relay
has to trip in unbalance.
For example: normal angles are 0,-120,120 reverse it to 0, 120,-120. Relay
will trip in unbalance.
Relay purpose:
AREVA P127 is commonly used as directional over current and earth fault protection
relay, which can be used for both HT and LT incomer feeders. For testing of this
relay we need aux supply, 3ph CT supply, 3ph VT supply and feedback from 1
binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
Relay purpose:
AREVA P211 is commonly used as a motor protection relay that can
be used for LT motors. For testing of this relay we need aux supply, 3ph CT supply
and feedback from 1 output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and output relay contacts 13 and 14 (NO contacts) can
be used for feedback of tripping, now check the protection that are enabled and note
down the settings. Usually for motor protection five protections will be enabled as
follows.
[46] UNBALANCE-
For testing unbalance inject equal current below the thermal setting
value with angle reversed in all three phases in the CT input. Now the relay
has to trip in unbalance.
For example: CT ratio - 200/1
UNBALANCE (I >>) setting – 0.15 In (which is 30
amps in primary)
Normal angles are 0,-120,120 reverse it to 0, 120,-
120. Relay will trip in unbalance.
Relay purpose:
AREVA P220 is commonly used as a motor protection relay. Which
can be used for both HT and LT motors. For testing of this relay we need aux supply,
3ph CT supply, 1 opto input and feedback from 1 binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts 2 and 6
(NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings. Usually for motor protection five protections
will be enabled as follows.
[46] UNBALANCE-
For testing unbalance inject equal current below the thermal setting
value with angle reversed in all three phases in the CT input. Now the relay
has to trip in unbalance.
For example: normal angles are 0,-120,120 reverse it to 0, 120,-120.
Relay will trip in unbalance.
Note: For further details verify relay manuals, testing kit manuals and related
relay kit operating procedure.
Relay purpose:
AREVA P141, P142, P143 and P145 is commonly used as feeder
management relay with more number of protection stages, binary inputs and binary
outputs which can be used for both HT and LT bus coupler feeders. For testing of
this relay we need aux supply, 3ph CT supply, 3ph VT supply and feedback from 1
binary output.
Kit used:
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply and programmable tripping output relay contacts E1 and
E2 (NO contacts) can be used for feedback of tripping, now check the protection that
are enabled and note down the settings.
[46] UNBALANCE-
For testing unbalance inject equal current below the thermal setting
value with angle reversed in all three phases in the CT input. Now the relay
has to trip in unbalance.
For example: normal angles are 0,-120,120 reverse it to 0, 120,-120. Relay
will trip in unbalance.
Note: Four stages are provided and can be selected to be either non-
directional, directional forward or directional reverse and provides remote
backup protection for both phase to earth and phase to phase faults.
Increase the voltage to 120 V (More than settings) in any one of the phase for
the relay to trip in over voltage. If IDMT curve is chosen then relay will trip
based on the [27] TMS value.
Note: Overvoltage (2-stage), configurable as either phase to phase or phase
to neutral measuring. Stage 1 may be selected as either IDMT or DT and
stage 2 is DT only.
[81] FREQUENCY-
Under frequency (81<):
For testing of under frequency decrease the frequency
value below the settings value for the relay to trip in under frequency at given
time delay settings.
For example:
Under frequency 81< (F1) setting – 49 (which is 49 Hz)
Time delay 81< (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Over frequency (81>):
For testing of over frequency increase the frequency value
above the settings value for the relay to trip in over frequency at given time
delay settings.
For example:
Over frequency 81> (F1) setting – 51 (which is 51 Hz)
Time delay 81> (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Note: A 4-stage under frequency and 2-stage over frequency can be used.
Here an advanced frequency protection gives you more advanced options for
a frequency protection.
Note: Above mentioned protections are generally used in AREVA P143 relay,
for details on other protections please check with manufacturing manuals.
Relay purpose:
AREVA P921, P922 and P923 are commonly used as frequency and
voltage protection, used for BUS PT. For testing of this relay we need aux supply,
3ph VT supply and feedback from 1 binary output.
Kit used:
Any three phase relay testing kit can be used.
Testing:
First give the connections as per the diagram and power on the relay by
switching on the aux supply, also switch on VT supply as per connection diagram
and programmable tripping output relay contacts 2 and 6 (NO contacts) can be used
for feedback of tripping, now check the protection that are enabled and note down
the settings.
[81] FREQUENCY-
Under frequency (81<):
For testing of under frequency decrease the frequency
value below the settings value for the relay to trip in under frequency at given
time delay settings.
For example:
Under frequency 81< (F1) setting – 49 (which is 49 Hz)
Time delay 81< (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Over frequency (81>):
For testing of over frequency increase the frequency value
above the settings value for the relay to trip in over frequency at given time
delay settings.
For example:
Over frequency 81> (F1) setting – 51 (which is 51 Hz)
Time delay 81> (tF1) setting – 60 ms (relay will trip after 60 milli sec)
Note: Above mentioned protections are generally used in AREVA P922 relay,
for details on other protections please check with manufacturing manuals.
Connect the relay through front port with laptop using USB Type B cable.
Open Reydisp software and click on FILE and Click on Connect. (It will
communicate)
Now you can see the connected relay under the system created.
Click Get settings Icon on menu bar & save the settings in other folder by
clicking save Icon on menu bar.
Similarly, we can get events, Wave form records, Fault data.
By clicking save Icon, it will save on mentioned folder individually.
Now open a new system to connect the new relay similarly and get the
settings.
Save the existing settings.
Now Open the required settings, which needs to upload in new relay.
Click on send all settings Icon in menu bar.
Click on send to send the downloaded settings to the new relay.
Connect the relay through front port with laptop using MOXA cable.
Open EASERGY STUDIO software and click on FILE NEW SYSTEM.
Enter the name of the project and click ok.
Now under the connect select QUICK CONNECT RELAY SERIES
FRONT PORT.
For example – [MICOM P220 Relay series is X20]
Click next and finish, now you can see the connected relay under the system
created.
Now open a new system to connect the new relay similarly and extract the
settings.
Rename the settings file `000’ into `001’.
Now right click on setting select `ADD EXISTING FILE’ and select the settings
file [000] need to be uploaded from the default destination.
Click right on the device and select `SEND’, mark the settings file needed to
be uploaded.
Click on send to send the downloaded settings to the new relay.
ALSTOM RELAY DETAILS
Connect the relay through front port with laptop using MOXA cable.
Open MICOM S1 AGILE software and click on FILE NEW SYSTEM.
Enter the name of the project and click ok.
Now select QUICK CONNECT RELAY SERIES FRONT PORT.
For example – [MICOM P220 Relay series is Px20]
Click next and finish, now you can see the connected relay under the system
created.
Now open a new system to connect the new relay similarly and extract the
settings.
Rename the settings file `000’ into `001’.
Now right click on setting select `ADD EXISTING FILE’ and select the settings
file[000] need to be uploaded from the default destination.
Click right on the device and select `SEND’, mark the settings file needed to
be uploaded.
Click on send to send the downloaded settings to the new relay.
Communicate and download settings from the relay as per the procedure.
Save the downloaded setting to any destination.
Now close and reopen the AcSELerator QuickSet software again.
Communicate with the new relay and open the previously saved settings file.
Select Send Active Settings option, mark the sections needed and click ok.
ALTERNATE METHOD for communication CLICK file and select the GET
INFO FROM RELAY now communication dialogue box appears enter the
required values as we mention in above.
For downloading the settings and records from relay following procedure
CLICK the SETPOINT from file menu bar, Select SYSTEM SETUP
and GENERAL SETTINGS save the setting in required location.
For records downloading select ACTUAL from file menu bar, select
RECORDS, now can select EVENTS OR FAULT RECORD which one
we required. Once EVENTS gets selected and save, that events file
should save in required location.
WAVEFORM RECORD, select ACTUAL from file menu bar, select
RECORDS, now can select WAVEFORM, dialogue box will appear in
that select range and click OK.
MIT RELAY DETAILS -MODEL NO:GENESIS (MIT)
APPROPRIATE KIT – MEGGER (Single phase relay testing kit), OMICRON (Three
phase relay testing kit), KINGSINE (Three phase relay testing kit), EPSEE (Three
phase relay testing kit).
REQUIRED TOOLS – CROCODILE PINS, CONNECTING CLIPS, BANANA
PINS(OR) BRASSES PIN AND CONNECTING CABLE.
VARIANTS:
Connect the kit as per proper terminals, Ensure proper earthing, Switch on the kit.
Give supply voltage to the respective coil terminal & measure the respective pickup
voltage of coil by raising the voltage & Tripping of the relay.
For example:
Steps:
CURV
S.NO 2*Is 5*Is 10*Is 20*Is
E
1 SI3 10.03 4.28 2.97 2.27
2 SI1 4.39 1.87 1.3 1
3 EI 26.67 3.33 0.81 0.2
4 VI 13.5 3.38 1.5 0.71
5 LTI 120 30 13.33 6.32
SI=simple inverse, VI=very inverse, EI=extreme inverse, LTI=long time inverse
Testing details:
For example:
1. O/C relay setting for very inverse (VI) is (PSM =10 & TMS=1.5 Ref curve table)
whatever PSM we choose and select the respective TMS based on the type of
curve.
For testing of O/C protection note down the over current settings from the
relay.
For example: O/C Setting is 125% which means 1.25 amps of CT secondary i.e.
(100%=1 amps)
Once the settings are noted calculate the current to be injected and tripping
time of the relay.
THEORITICAL VALUE:
Current injection (10 x 1.25 = 12.5 A) Time taken (1.5 x 0.5 = 0.750 S)
Now inject 12.5A in each phase the relay will operate at 0.750 s
R=12.5 A
Y=12.5 A
B=12.5 A
Relay has operated at 0.736 s which is the practical value.
PRACTICAL VALUE:
2. E/F relay setting for long term inverse (LTI) is (PSM =10 & TMS=13.33 we can
take value from curve table,) whatever PSM we choose select the respective TMS
also based on the type of curve.
For testing of E/F protection note down the earth fault settings from the relay.
For example: E/F Setting is 40% which means 0.4 amps of CT secondary i.e.
(100%=1 amps)
Once the settings are noted calculate the current to be injected and tripping
time of the relay.
THEORITICAL VALUE:
Now inject 4A in any one phase the relay will operate at 6.665 s
R=4 A
Y=0 A
B=0 A
Relay has operated at 6.645 s which is the practical value.
PRACTICAL VALUE:
Connect the Transducer through front port with laptop using MOXA cable.
Open RISHDUCER (V1.0 for M42 / v1.1 for M40) software and click on FILE
READ FROM TRANSDUCER.
Now the program in the transducer will be displayed.
This shows the communication between laptop and transducer is established.
Now the default program in the transducer will be opened once transducer
gets communicated with the laptop.
Now click `INPUT’ to feed the primary and secondary current as well as
voltage from the CT and PT of the system.
Set the rated frequency and frequency as `VIA VOLTAGE’.
System configuration as `3 WIRE SYSTEM, BALANCED LOAD’ (check
manual for the system configuration connection diagrams) and click ok.
Choose between `PRIMARY AND SECONDAY VALUE DISPLAY’ from
`OPTION’ menu
Select `OUTPUT A’ program the settings as per need (SECONDARY VALUE
DIPLAY is selected in the example given below).
To program the transducer with already saved settings connect the transducer
using `READ FROM TRANSDUCER’ option as already mention in the above
procedure.
Once the program is downloaded now open the saved settings by clicking
FILE OPEN.
Now open the program from the destination saved previously.
Click on `PROGRAM TRANSDUCER’ from `FILE’ to program the transducer.
TRANSDUCER
Appropriate kit for testing – ANY THREE PHASE RELAY TEST KIT
Features –
Simultaneous measurement of several variables of a heavy current power
system / Full supervision of an asymmetrically loaded four-wire power system,
rated current 1 to 6 A, rated voltage 57 to 400 V (phase to neutral) or 100 to 693 V
(phase-to phase)
For all heavy-current power system variables
4 analogue outputs
Input voltage up to 693 V (phase-to-phase)
Universal analogue outputs (programmable)
High accuracy: U/I 0.2% and P 0.25% (under reference conditions)
4 integrated energy meters, storage each 203 s, storage for: 20 years
Windows software with password protection for programming, data analysis,
power system status simulation, acquisition of meter data and making settings
DC-,AC-power pack with wide power supply tolerance / universal
Provision for either snapping the transducer onto top-hat rails or securing
Input- X0=0 & X2=125 (secondary voltage is given as per the site
requirement)
To program the transducer with already saved settings connect the transducer
using `READ FROM TRANSDUCER’ option as already mention in the above
procedure.
Once the program is downloaded now open the saved settings by clicking
FILE OPEN.
Now open the program from the destination saved previously.
Click on `PROGRAM TRANSDUCER’ from `FILE’ to program the transducer.
TESTING PROCEDURE FOR TRANSDUCER
First connect the transducer with all the CT, VT and AUX supply based on the
connection details given below also check for the respective terminals for CT, VT
and AUX supply.
Various types of connections can be choosing in the program based on the system
and the appropriate connection should be used as the supply terminals. The various
types of connections are listed below.
NOTE: This live display of values through software can be used when
the transducer is connected in online also.
DIGSI MANAGER (DIGSI 4)
Serial interface:
DIGSI 4: 1. First open the software and connect the cable RS232 Cross
communication cable between laptop and relay front side (for example
SIPROTEC 4 relay).
SIPROTEC 7UM85
CLASS: 0.5
STEP 2: After voltage injection. default page will appear CLICK DOUBLE
ARROW LEFT AND RIGHT simultaneously, will get CODE then press down
arrow will get 0000.