Atys A M 63 A Iec Installation and Operating Manual 2024-09-552931 en 1
Atys A M 63 A Iec Installation and Operating Manual 2024-09-552931 en 1
IEC
CONTENTS
• As a minimum the ATyS aM comply with the following international standards:
- IEC 60947-6-1
- GB 14048-11
-E N 60947-6-1
The information provided in this instruction manual is subject to change without notice, remains for general information
only and is non-contractual.
Configuration
40A - 160A
ATyS p ATyS p M
Power / Genset Evolved Genset
Management Management
40A - 125A
ATyS g ATyS g M
Simple Genset Simple Genset
Management Management
ATyS t ATyS t M
Transformer Transformer (building)
Management Management
ATyS d S ATyS d ATyS a M
Small Genset RTSE (DPS) Simple sources (building)
with DPS Management
ATyS S (RTSE) ATyS r ATyS
(1)
ATyS d M
Small Gense RTSE RTSE RTSE (DPS)
Side by Side Configuration
(1)
The UL version of ATyS r is available from 100 - 400A
160 A
40 A
COMMUNICATION*
loads
S
Critical
loads
ATyS p M
Non-critical Non-critical
U
U
P
loads loads
S
Critical Critical
loads loads
ATyS a M
25 A - 63 A
Automatic Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after
removal of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
Qty 1 x ATyS a M
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to 1 Installation
persons and / or damage to equipment.
This Quick Start is intended for personnel Caution: Ensure that the product is installed on a flat rigid surface. Dimensions (mm)
trained in the installation and commissioning
of this product. For further details refer to the
product instruction manual available on the
SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved
personnel.
• Maintenance and servicing operations should
be performed by trained and authorized
personnel.
• Do not handle any control or power cables
connected to the product when voltage may
be, or may become present on the product,
directly through the mains or indirectly through
external circuits.
• Always use an appropriate voltage detection
device to confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
Accessories
• Bridging bars.
• Terminal shrouds.
• Auxilliary contact blocks.
• Optional modules.
Warning! Wrong
Neutral wiring will 2.5 to 35 mm²
damage the product # 14 to # 2
and cancelled warranty. 15mm L1 L2 L3 N L1 L2 L3 N
Ensure that the product is in Manual Auxiliary contacts: Fitting of auxiliary contacts: 1309 1001
Mode (front cover open).
To fit an auxiliary contact, the switch must first be put in position 0. An auxiliary contact module
comprises one NO/NC changeover contact for each position (I-0-II). To install use the long
screws supplied with the module.
11: Posidriv PZ2
POP Output
12:
8.8 lb-in/1 Nm
1: Position 0 Order (Main-Main)/
Test on Load (Main-Gen)
2: Priority S1 / Priority S2
3: Retransfer Mode Selector
4: Inhibit Mode
5: Common
Use 20mm
screws for 1
11 Use 35mm
module
12 screws for 2
Slotted head 2,5 mm 0,2 Nm modules
1
2 0,5 to 1,5 mm²
3
4 0,5 to 1,5 mm²
5 6 mm
CORPORATE HQ CONTACT: SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE.
Print: 90 g/m2 - A4 > A4 - R/V - B&W - The bar code must be visible once the document is folded. Non contractual document. © 2024, Socomec SAS. All rights reserved.
4 1 2
This quick-acting transfer switch incorporates:
1. 2
mechanically interlocked switches.
2. A
quick-acting electric control unit enabling
automatic or manual system operation.
3. E
lectrical specifications compliant
with product standards, and a version
identification.
4. C
hangeover switch and sources informations.
5. C
onnection of control/command circuits.
5 3
CAUTION! If the product is mounted upside down (allowed), use the second supplied sticker to allow a good
reading of product information.
Fire input optional Plug-in module for fire signal (24Vdc) interpretation. Ref. : 9335 0002
module When fire linkage is active, the transfer is inhibited and
switch go to center OFF position for safety.
GenSet output Plug-in module for Generating Set start and stop Ref. : 9335 0003
optional module management.
Auxiliary contacts Each product can take up to 2 auxiliary contact Ref. : 1309 1001
blocks. Each accessory integrates 1 NO /N C auxiliary
contact (for each position I, O and II) 1309 1001 for
separated common points.
Characteristics: 250 VAC / 5 A maximum.
Bridging bars To provide a common point on the outgoing side of Ref. : 9324 0001
the switch (load side).
Terminal shrouds Protection against direct contacts with terminals Ref. : 9324 0002
or connecting parts. Other features: Perforations 2 parts/ref.
allowing remote thermographic inspection without
removal. Possibility of sealing.
Auto-transformer For use with ATyS M in 400 VAC three-phase Ref. : 1599 4121
applications without a distributed neutral. As the ATyS
M has integrated measurement and power supply
circuits, a neutral connection is required for 400 VAC
three-phase applications. When no neutral connection
is available this autotransformer (400/230 VAC, 400
VA) provides the 230 VAC required for the ATyS M to
function.
Current rated as conditional short-circuit with any brand of circuit breaker that ensures tripping in less than 30ms (2)
Current rated as short-time withstand Icw 30ms (kA rms) 5 5 5 5
Short-circuit operation
Rated peak withstand current Ip (kA peak) 7.1 7.1 7.1 7.1
Connection
Minimum Cu cable cross-section (mm2) 2.5 2.5 2.5 2.5
Maximum Cu cable cross-section (mm2) 35 35 35 35
Tightening torque (Nm) 2.5 2.5 2.5 2.5
Power supply
Min./max. auxiliary power supply (VAC) 176-264 176-264 176-264 176-264
Mechanical specifications
Durability (number of operating cycles) 10 000 10 000 10 000 10 000
Weight - non-packaged (kg) 1.8 1.8 1.8 1.8
Weight - including packaging (kg) 2.3 2.3 2.3 2.3
(1) Category with index A = frequent operation / Category with index B = infrequent operation.
(2) Value for coordination with any circuit breaker that ensures tripping in less than 30ms.
For coordination with specific circuit-breaker references, higher short-circuit current values are available. Please contact us.
(3) At rated voltage - excluding time delays, where applicable.
Humidity
• 80 % humidity without condensation at 55 °C
• 95 % humidity without condensation at 40 °C
Temperature
• -20 +40 °C without de-rating
• 40 °C < t ≤ 70 °C with de-rating (see Technical Characteristics)
Altitude
• Up to 2000m without derating
Correction factors:
2 000 m < A ≤ 3 000 m 3 000 m < A ≤ 4 000 m
Ue 0.95 0.80
Ie 0.85 0.85
Storage
• 1 year maximum
• Maximum storage temperature: +55 °C
• 80 % humidity without condensation at 55 °C
IP rating
ø 1 mm
• IP2x minimim for modular integration or with required door cut-out (222x47mm).
Recommended
8.2. Dimensions
Dimensions (mm)
DIN RAIL
IEC 60715
Posidriv PZ1
2,2 lb-in/1 Nm
RS485 communication module Fire input module connection: GenSet output module connection:
connection: - Cross section: 0,5mm² - 1,5mm² - Cross section: 0,5mm² - 1,5mm²
- Cables: LiYCY shielded twisted pair - Tightening torque: 0,5Nm - 0,6Nm - Tightening torque: 0,5Nm - 0,6Nm
- Cross section: 0,5mm² - 1,5mm² - H x W x L (mm) = 22 x 38 x 45 - H x W x L (mm) = 22 x 38 x 45
- Tightening torque: 0,22Nm - 0,25Nm
- H x W x L (mm) = 22 x 38 x 45 Input voltage: 8,6Vdc - 28Vdc Output signal: 230Vac / 3A
Normally closed (NC) contact
Remove the protection from the ATyS a M connector, before optional module intallation. The same protection must be
placed on the optionnal module female connector, if not used.
Posidriv PZ2
8.8 lb-in/1 Nm
Use 20mm
screws for 1
module Use 35mm
screws for 2
modules
It is essential to tighten all used terminals, with cables and/or bridging bars, before use.
2.5 to 35 mm²
Posidriv PZ2 # 14 to # 2
22.13 lb-in/2.5 Nm
15mm
Posidriv PZ2
22.13 lb-in/2.5 Nm
2.5 to 35 mm²
# 14 to # 2
15mm
It is essential to tighten all used terminals, with cables and/or bridging bars, before use.
25 A 32 A 40 A 63 A
Auto-transformer connections
Reference 1599 4121
Load
L1 L2 L3
1 3 5 N 1 3 5 N
I II
2 4 6 N 2 4 6 N
N N
Atys aM
Source II Source I
11:
POP Output
12:
All pressure on the connector pins is to be avoided
1: Position 0 Order (Main-Main)/ during wiring of the auxiliary cables
Test on Load (Main-Gen)
2: Priority S1 / Priority S2
3: Retransfer Mode Selector
4: Inhibit Mode The product is delivered in the 0 position and in
5: Common auto mode. Maximum control cables length = 10 m.
In case of longer distance, use control relays.
Recommended
Status of
Type Terminal no. Description Output characteristics connection cross-
the contact section
250V AC 5A AC1
14
11/12/14 11 12 Changeover switch in position I 24VDC 2A
AC13 - 250VAC - 2A
0.5 to 2.5 mm²
Auxiliary 250V AC 5A AC1 (rigid)
contact 21/22/24 24
Changeover switch in position II 24VDC 2A
block 21 22
AC13 - 250VAC - 2A 0.5 to 1.5 mm²
1309 1001 (stranded)
01
04 250V AC 5A AC1
01/02/04 02 Changeover switch in position 0 24VDC 2A
AC13 - 250VAC - 2A
PositionPosition
I I
Position
Position 0 0
Position II
Position II
C.A.
C.A. Position
Position I I 11-14 Closed
11-12 Open
C.A. Position
C.A. Position 0 0 01-04 Closed
01-02 Open
C.A. Position
C.A. Position II II 21-24 Closed
21-22 Open
3 5 4 8
2 1 7
7 1 2
6 8 4 5 3
2 Warning Fault indication RED BLINKING (1sec) in case of major fault : GenSet fail to start,
operating factor reached (too much operations), transfer failed,
unknown position.
3 1. Locking
• Mechanism to padlock using a 1 x 8 mm max. padlock.
5
2. AUT/MAN cover
4 5 1 • Open the cover to switch to manual mode.
• Close the cover to return to automatic (remote control) mode.
4 • Open and close the cover to clear faults.
3 3. Auto/Manual mode sensor
4. Switch position indicators
• Display of position I, 0, II.
5. Manual switching
• Insert the Allen key (5.0 mm) provided and turn to switch
2 manually.
• Manual operation is not possible when padlocked.
MANUAL MODE
Manual changeover
Locking
switching
12.4. Padlocking
Locking is only possible in manual mode (cover open).
Pull on the locking handle to enable the interlock. Lock by inserting a padlock into the orifice provided for this purpose.
1 x 4-8 mm
4 mm min
3/16” min
8 mm max
5/16” max
Timer
Timer
Timer name Timer description factory
mnemonic
setting
When source 1 returns inside the limits, 1RT is started. At the end of 1RT, source 1 is then considered to be
1RT Source I return timer 2sec
available. Should source 1 unavailable before the end of 1RT, the changeover will not be carried out.
When source 1 is considered unavailable, 1FT is started. If source 1 is considered restored (available again)
1FT Source I failure timer 2sec
before the end of 1FT, the changeover sequence will not be engaged.
Source II return timer
When source 2 returns inside the limits, 2RT is started. At the end of 2RT, source 2 is then considered to be
2RT/2AT / Source II Availability 2sec
available. Should source 2 unavailable before the end of 2RT, the changeover will not be carried out.
timer
When source 2 is considered unavailable, 2FT is started. If source 2 is considered restored (available again)
2FT Source II failure timer 2sec
before the end of 2FT, the changeover sequence will not be engaged.
Minimum load downtime possibility with stop in position 0; to enable residual voltage generated by the load
0DT 0 dead timer 0sec
to dissapear.
This timer is used to replace the return timer of the prioritary source in case of a retransfer back to main
DRT Dynamic return timer 3sec
source, if we lost the backup source while the return timer is counting.
Genset cooldown In Main-GenSet application, following a return to the priority source (when it is closed), the genset is kept running
2CT 180sec
timer for the 2CT timer duration. This timer is intented to cool down the genset (off load) before switching it off.
"In Main-GenSet application, this timer is used to know if genset has started and turned available (end of
2AT) fast enough.
Genset start timeout
2ST Timer start as soon as the genset start order has been given. If 2AT has not been satisfied before the end of 30sec
timer
this timer, an error will be raised (Genset failed to start). In AUTO mode this timer does not affect the genset
start request. During a test sequence, the test will be cancelled and the genset turned OFF."
AUTOMATIC MODE
On load test (M-G application only): this test is only possible in automatic mode, it enables to start the GenSet and
simulate a complete transfer sequence, including time delays.
Main-Main application:
- if opposite source is acceptable for commutation (voltage, frequence and phase rotation), normal behavior is done (go to
0 then inhibition)
- if opposite source is not present (or not within acceptable tolerances), inhibition mode is set, and if opposite source gets
acceptable, move to position 0 to disconnect the load while being still inhibited.
Main-GenSet application:
- ATyS is on the main source, and GenSet is no started: ATyS will not start the GenSet for safety reasons, and inhibition
mode is set. If in that case, main source is lost, ATyS will be powered OFF and monostable genset relay will start by
itself. Product is still inhibited but since there is now energy in opposite source, switch will move to position 0. Inhibition
remains, and GenSet is kept ON to power the product whatever if main source comes back.
- ATyS is on the GenSet, main source is not present. Inhibition immediately, and if main returns, ATyS goes to position 0
while inhibition is still active, GenSet is kept ON. When Fire signal is removed, ATyS transfers to Main source if available,
and cooldown timer is launched. If main is not available, ATyS goes back on GenSet.
- ATyS is on the GenSet, main is available, case of a test on load: ATyS goes to 0 and GenSet stays ON.
If test is launched from the input connector, and input is still active, after releasing the Fire signal the test continues and
ATyS goes back to the GenSet.
If test is launched from communication layer, being in position 0 will stop the test.
- ATyS is on the main source, and GenSet is cooling down: ATyS goes to position 0, raises inhibition mode and GenSet is
kept ON. When Fire signal is removed, ATyS goes back to main source and a new cooldown timing is launched.
The use of any Megohmmeter is prohibited on this product as the connection terminals are intrinsically
connected to the sensing circuit.
The switch does not Check that the product is not in manual mode: The AUT LED is ON.
return to its priority - Automatic mode = Cover closed,
position after the - Manual mode = Cover open.
priority source has been Check that automatic operation has not been inhibited by an external order
restored. (input terminals 4-5).
Check that the priority source is seen as available ; appropriate source The AUT and the priority SOURCE
availability LED is ON. LEDs are ON.
If it is not ON refer to above actions for “SOURCE x availability LED is OFF”.
The changeover will only take place at the end of RT. When RT reaches zero the switch
will operate to position 0 before
finally transferring to its priority
position.
www.socomec.com Non contractual document. © 2024, Socomec SAS. All rights reserved.