Manual de Instrucciones Power Pack RPP20, Lithonia

The rPP20 Relay Power/Relay Pack is designed for on/off switching and dimming of light fixtures in commercial and industrial indoor environments, supporting input ratings of 120-480VAC and a maximum load of 20A. It includes installation instructions, safety precautions, and troubleshooting tips, emphasizing the importance of following electrical codes and using qualified personnel for installation. The device features a user button for testing and programming, and it is compliant with various safety and environmental standards.

Uploaded by

12345
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views3 pages

Manual de Instrucciones Power Pack RPP20, Lithonia

The rPP20 Relay Power/Relay Pack is designed for on/off switching and dimming of light fixtures in commercial and industrial indoor environments, supporting input ratings of 120-480VAC and a maximum load of 20A. It includes installation instructions, safety precautions, and troubleshooting tips, emphasizing the importance of following electrical codes and using qualified personnel for installation. The device features a user button for testing and programming, and it is compliant with various safety and environmental standards.

Uploaded by

12345
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

rPP20 Relay

POWER/RELAY PACK
Pack
FAMILY INSTRUCTIONS

SPECIFICATIONS (rPP20)
Electrical Specifications Input Ratings 120-277VAC , 120-480VAC (UVOLT)
Maximum Load 20A general purpose, tungsten and standard
ballast; 16A electronic ballast
Dimming Load Sinks 150mA; 0-10VDC dimmable ballasts
or LED drivers; “D” 0-10V leads Class 1, “DS”
0-10V leads Class 2
Minimum Load None
Class Rating 0-10V Dimming can be wired Class 1 or 2
Mechanical Mounting 1/2” Knockout (7/8” hole)
Connection Type Line and Low Voltage Leads
Environmental Warrantied Operating Temperature -10°C to 60°C up to 5 amps; -10°C to 50°C up
to 20 amps
Standards/ Ratings RoHS, UL 916, UL 924 (optional), FCC / IC / IFETEL

Contains FCC ID: 2ADCB-RMODIT or 2ADCB-RMODIT3 This device complies with Part 15 of the FCC Rules. Operation is subject to the

Contains IC: 6715C-RMODIT or 6715C-RMODIT3


following two conditions: (1) This device may not cause harmful interference, and (2) IMPORTANT SAFEGUARDS
this device must accept any interference received, including interference that may
IFT #: RCPACRM18-1879 or RCPNLNL20-2057 cause undesired operation. WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
Acuity Brands Lighting Inc. RMODIT or RMODIT3 PRECAUTIONS SHOULD ALWAYS BE FOLLOWED
La operación de este equipo está sujeta a las siguientes dos condiciones: (1) es posible
que este equipo o dispositivo no cause interferencia perjudicial y (2) este equipo o
INCLUDING THE FOLLOWING:
In order to avoid the possibility of exceeding the FCC radio frequency dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su
exposure limits, human proximity to the radiator shall not be less than operación no deseada. • DO NOT USE OUTDOORS.
20cm during normal operation. • DO NOT MOUNT NEAR GAS OR ELECTRIC HEATERS.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed • EQUIPMENT SHOULD BE MOUNTED IN
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and,
if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference
LOCATIONS AND AT HEIGHTS WHERE IT WILL NOT
will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the READILY BE SUBJECTED TO TAMPERING BY
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: UNAUTHORIZED PERSONNEL.
1. Reorient or relocate the receiving antenna. • THE USE OF ACCESSORY EQUIPMENT NOT
2. Increase the separation between the equipment and receiver. RECOMMENDED BY THE MANUFACTURER MAY
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
CAUSE AN UNSAFE CONDITION.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS!


SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
WARRANTY
5-year limited warranty.
C US LISTED
Full warranty terms located at: www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
TITLE 20/24 Note: Specifications subject to change without notice.
Actual performance may differ as a result of end-user environment and application.
• To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions
included with and on the fixture box and all fixture labels.
• Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
• Installation and service should be performed by a qualified licensed electrician.
• Maintenance should be performed by qualified person(s) familiar with the products’ construction & operation & any hazards involved. Regular maintenance programs recommended.
• To be installed to a circuit with overvoltage control to Overvoltage category Cat.III or less, minimum suppression rating 6.0 kV for a 600 V ac rms system voltage
• DO NOT INSTALL DAMAGED PRODUCT! This product has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged
or broken during or after assembly should be replaced.
WARNING - RISK OF ELECTRIC SHOCK WARNING - RISK OF BURN or FIRE
CAUTION: RISK OF PRODUCT DAMAGE √ Disconnect or turn off power before installation or servicing. √ Do not exceed maximum wattage, ratings, or published
√ Electrostatic Discharge (ESD): ESD can damage product(s). Personal grounding equipment should be worn √ Verify that supply voltage is correct by comparing it with the operation conditions of product.
during all installation or servicing of the unit. product information. √ Do not overload.
√ Do not touch individual electrical components, as this can cause ESD and affect product performance. √ Make all electrical and grounded connections in accordance with √ Follow all manufacturer’s warnings, recommendations
√ Do not stretch or use cable sets that are too short or are of insufficient length. the National Electrical Code (NEC) and any applicable local code and restrictions to ensure proper operation of product.
√ Do not tamper with contacts. requirements.
√ Do not modify the product. √ All wiring connections should be capped with UL approved CAUTION - RISK OF INJURY
√ Do not change or alter internal wiring or installation circuitry. √ Wear gloves and safety glasses at all times when
recognized wire connectors.
√ Do not use product for anything other than its intended use. installing, servicing or performing maintenance.
√ All unused connector openings must be capped.

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 09/12/2021 1 of 3
IS-RLSXR-002
rPP20 Relay
POWER/RELAY PACK
Pack
FAMILY INSTRUCTIONS

OVERVIEW
nLight AIR rPP/rPP20 is a device that provides on/off switching and dimming for light fixtures. It is suitable for control of commercial and industrial light fixtures in
indoor environments. When installed as part of an nLight AIR lighting control system, the rPP/rPP20 will respond to wireless commands from other devices, to be
programmed during startup.

INSTALLATION INSTRUCTIONS
REQUIRED TOOLS & SUPPLIES
• Electical Pliers
• Screwdriver
• Wire nuts
• Electrical box
• 2mm Precision Slotted Screwdriver, used for 24V terminals only

INSTALLATION STEPS
1. Turn power off at circuit breaker.
2. Install electrical box in accordance with state, local and national electrical
codes and requirements.
3. Remove knock-out from side of electrical box.
4. Remove retaining nut and washer from power pack mounting nipple.
NOTE: Standard device includes a wireless antenna internal to the device. This
restricts it from being installed inside a metal enclosure. For metal enclosure
applications, use the CP (Chicago Plenum) model with an external antenna.
5. Feed Class 1* wires and mounting nipple through knockout hole.
6. Install washer and thread retaining nut onto nipple, and hand-tighten to wall
of electrical box, then apply additional quarter-turn tightening with pliers. Chicago Plenum Device
7. Using wire nuts, connect line and low voltage wires as shown in the applicable
wiring diagram in accordance to state, local and national codes and require-
ments.
8. “24V” models only: Connect +/- DC power leads from nLight AIR sensor(s) to
24VDC terminal block on side of rPP enclosure, if needed. See diagrams below
for additional details.
9. For Chicago Plenum models only: Connect the antenna with the gasket to the
inside of the sealed box, with the retaining nut on the outside of the box, as
illustrated.
10. Install electical box cover plate before restoring power. *DS option provides Class 2 low voltage dimming wires
on side of enclosure opposite from chase nipple.
INITIAL OPERATION *For Chicago Plenum option, see step 9 .

Following power up, the relay shall close to energize the load. The dimming output shall be at 100% light output. The device shall remain in this state until programmed
with Clairity Pro mobile application. See Clairity Pro User Guide for additional programming information.

For Emergency Variant ER


The RPP/RPP20 ER version is a UL924 listed device that is powered on the Emergency circuit and provides full light output (at user-defined high-trim level) in absense of
AC voltage on Normal Power sense leads. Normal operation of the control device is restored when AC line voltage is restored to the normal power sensing leads.

TROUBLESHOOTING TIPS
Device cannot be viewed in Clairity Pro
1. Press user button for specified time to reset the device to place the device in Maintenance Mode
2. Once the user-button LED confirms that the RP20 is in Maintenance Mode, open the Clairity Pro application and search for the device in Clairity Pro.
a. If you still cannot see the device in Clairity Pro, contact Technical Support for additional assistance; device may need to be replaced.
3. Once the device is identifiable Clairity Pro, attempt to group or configure the device. If you are still having issues, refer to the Clairity Pro User Manual or contact Technical
Support for assistance using Clairity Pro to complete programming of your device.

For further troubleshooting guidance, please contact the Controls Technical Support Team

1(800)-535-2465
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 09/12/2021 2 of 3
IS-RLSXR-002
rPP20 Relay
POWER/RELAY PACK
Pack
FAMILY INSTRUCTIONS
USER BUTTON
On the side of the controller is a lighted user button. This button can be used for testing and re-programming purposes.

User Button, also functions as LED


indicator. (On UVOLT models, the
button is separate from the LED)
Maintenance Mode
Use this mode if you are unable to Identify this device within the Clairity Pro application.
1. Press and hold button for 10 seconds, then release. LED will begin to flash rapidly
after 10 seconds and stop flashing when the button is released.
UL924 Test (ER model only) 2. Immediately press and hold button again for 10 seconds, then release. LED will
Use this test to confirm that the lighting load is properly connected and begin to flash rapidly after 10 seconds and stop flashing when the button is released.
provides the necessary output in event of loss of power. 3. The LED will flash twice to confirm entry into Maintenance Mode.
1. Press and Release the button.
2. Relay will close and dimming output will go to full brightness for 4 For 60 minutes, the device becomes identifiable in the Clairity Pro app and available
seconds. for direct connection from mobile app to device (without requiring Group Monitor to be
3. After 4 seconds expires, the device returns to its previous state and the present, in case of a fault or connectivity issue with the Group Monitor).
indicator LED shuts off.
Clairity Pro can then be used to perform functions such as:
LED Diagnostics * Reprogram device settings
The LED is illuminated whenever the button is depressed, and blinks to * Reset device network settings
confirm the start of maintenance mode. Depress the button from the side to * Firmware update
view LED and confirm that the device is operational. * General troubleshooting and diagnostic functions

WIRING (DO NOT WIRE HOT)


RPP DS 24V EFP LOAD Legend
RPP 24V EFP
LOAD GRY PNK* GRY PNK* Legend
BLK – Unswitched Hot 120-277V
WHT – Neutral
BLK - Unswitched Hot 120-277V
BLU – Switched Output
RPP DS 24V EFP VIO – 0-10V Dim
RPP 24V EFP RED – 120-277VAC Emergency Hot**
PNK* – 0-10V Common

} }
RED (Terminal) – +24VDC
WHT/RED – Emergency Neutral
BLK (Terminal) – DC Common

}
Normal

}
Normal BLK – Unswitched Norm. Hot**
GRN – Ground

+24 VDC * 0-10V DimmingWHT – Norm.


Common from luminaire Neutral**
+24 VDC may be pink or as otherwise indicated per

BLU – Switched Output


section 410.69 of the 2020 NEC

VIO – 0-10V Dim (+)


RPP D/DS 24V EM EFP Legend
PNK* – 0-10V Com (-)
RPP D/DS 24V ER EFP Legend EMERGENCY Emergency
EMERGENCY Emergency 0-10 VDC Ballast RED Hot
BLK - 120-277VAC Emergency (Terminal) - +24VDC
}
RED – 120-277VAC Emergency Hot
Normal 0-10 VDC Ballast WHT – Emergency Neutral
BLU – Switched OutputBLK (Terminal) - DC Com
}

WHT/RED – Emergency Neutral or LED Driver


or LED Driver
}

BLK – Unswitched Norm. Hot GRY PNK* GRY PNK*


PNK* – 0-10V Com (-) GRN – Ground
VIO – 0-10V Dim (+)
WHT – Norm. Neutral
GRY PNK* GRY PNK* BLU – Switched Output
VIO – 0-10V Dim (+)
RPP DS 24V EM EFP RED (Terminal) - +24VDC
BLK (Terminal) - DC Com
- Optional Test Switch
RPP DS 24V ER EFP PNK* – 0-10V Com (-) 120 V - GRN – Ground (by others)

}
120 V -
RED (Terminal) - +24VDC 277 V * 0-10V Dimming Common from luminaire
BLK (Terminal) - DC Com
* 0-10V Dimming Common from luminaire
may be pink or as otherwise indicated per
277 V section 410.69 of the 2020 NEC

}
GRN – Ground+24 VDC
- Optional Test Switch
may be pink or as otherwise indicated per
(by others) section 410.69 of the 2020 NEC
+24 VDC ** Emergency on ER and EM devices
* 0-10V Dimming Common from luminaire
may be pink or as otherwise indicated per
section 410.69 of the 2020 NEC

Do NOT wire while connected to live power, damage may occur.

USING 24 VDC TERMINALS (24V models only)


Connecting Wire to 24V Terminals Removing Wire from 24V Terminals

Strip length: 3/8” 1. Strip jacket to correct length, then insert firmly
into terminal hole. 1. Insert precision slotted screwdriver into
Solid or tinned leads
only terminal slot.
2. Gently pull to confirm that terminal has
16-20 AWG securely captured wirelead. 2. Gently press screwdriver into terminal,
then gently pull wire to remove.

Max screwdriver size: 2mm

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 09/12/2021 3 of 3
IS-RLSXR-002