SHEET NO.
3
PROJECT :RESIDENTIAL VILLA (G+1)
LOAD DISTRIBUTION SCHEDULE LOCATION OF DB: LOBBY,FIRST FLOOR
PANEL ID: DB-FF
FED FROM :MDB CONSULTANT : ARKAN ENGINEERING CONSULTANCY
CKT ECC
MCB CONNECTED LOAD /POINTS LOAD PER CIRCUIT /WATT
WIR
RATI
RATING OF RATING OF SL.N CKT. WIR E LTG LTG
INCOMER ELCB O. NO.
NG ROOM/AREA CH SH 13A 13A W/M T.PUM B.PUM AUTO SOLAR COCK WATT PET UNIT R - PH Y - PH B - PH REMARKS
E SIZE 10W 30W EX FAN 15A S/O W/H SPLIT CU MISC
IN 200W S/O S/O D/O P P GATE HEATER ER KW KW KW
SIZ IN S OR M D
Amp
E mm3
1 R1 10 2.5 2.5 LIVING, GYM, OFFICE 5 2 30,200 0.55
2 Y1 10 2.5 2.5 M.BED ROOM 16 6 2 1 10,30,200,80 0.82
3 B1 10 2.5 2.5 BED ROOM 01 11 3 1 1 10,30,200,80 0.48
4 R2 SPACE 0.00
40A 100mA
5 Y2 10 2.5 2.5 BED ROOM 03 14 3 1 1 10,30,200,80 0.51
ELCB SEC-1
6 B2 10 2.5 2.5 STAIR AREA 26 3 10,30 0.35
7 R3 0.00
8 Y3 10 2.5 2.5 BED ROOM 02 14 3 1 1 10,30,200,80 0.51
9 B3 10 2.5 2.5 ROOF 8 0.24
10 R4 32 4 4 LIVING 4 400 1.60 RING
11 Y4 32 4 4 M.BED ROOM 3 3 200,400 1.80 RING
40A 30mA 12 B4 32 4 4 BED ROOM 01 2 3 200,400 1.60 RING
ELCB SEC-2 13 R5 32 4 4 GYM, OFFICE 1 2 200,400 1.00 RING
14 Y5 32 4 4 BED ROOM 03 2 3 200,400 1.60 RING
125ATP ISO
15 B5 SPACE 0.00
16 R6 20 4 4 LIVING 2 400 0.80
17 Y6 32 4 4 BED ROOM 02 2 3 200,400 1.60 RING
40A 30mA 18 B6 32 4 4 ROOF 6 200 1.20 RING
ELCB SEC-3 19 R7 20 4 4 ROOF 1 1000 1.00 BOOSTER PUMP
20 Y7 20 4 4 ROOF 1 1000 1.00 RECIRCULATION PUMP
21 B7 25 6 6 ROOF 1 2,500 2.50 SOLAR HEATER
22 R8 2.00
40A 100mA
23 Y8 20 6 6 M.BED ROOM CU-F4 1 6,000 2.00 UVR+TIMER+CONT.
ELCB SEC-4
24 B8 2.00
25 R9 2.00
40A 100mA
26 Y9 20 6 6 LIVING CU-F5 1 6,000 2.00 UVR+TIMER+CONT.
ELCB SEC-5
27 B9 2.00
28 R10 2.00
40A 100mA
29 Y10 2 6 6 LIVING CU-F6 1 6000 2.00 UVR+TIMER+CONT.
ELCB SEC-6
30 B10 2.00
31 R11 32 6 6 BED ROOM 01 CU-F1 1 3600 3.60
40A 100mA
32 Y11 32 6 6 BED ROOM 02 CU-F2 1 3600 3.60 UVR+TIMER+CONT.
ELCB SEC-7
33 B11 32 6 6 BED ROOM 03 CU-F3 1 3600 3.60
CABLE SIZE 4CX35mm2 Cu/PVC-XLPE/SWA/PVC+1X1C 25mm2,G/Y PVC ,ECC TOTAL 14.55 17.44 15.97
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O = Single Socket Outlet, D/O = Double Socket Outlet, W/M=washing machne, CU = condensing unit, FCU = Fan Coil Unit, ISOL =
Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules.
TCL 47.96 KW