Saep 1135
Saep 1135
1 Scope…………………………………………… 2
2 Purpose………………………………………… 3
3 Conflicts and Deviations……………………… 3
4 Applicable Documents………………………… 4
5 Definitions………………………………………. 6
6 Instructions……………………….…………….. 9
7 Responsibilities………………………………. 20
1 Scope
1.1 This Saudi Aramco Engineering Procedure (SAEP) describes the steps
necessary to operate and administer a program for on-stream inspection (OSI)
on monitoring of static equipment (assets). The design and set up of an OSI
program is excluded from this procedure and is covered in SAES-A-135.
1.2 OSI Monitoring in this SAEP primarily means the systematic monitoring of
process equipment, piping and pipelines for general and localized metal loss,
cracking, material properties change and other forms of asset deterioration.
1.4 The overall OSI Program is intended to collect and integrate the different types of
OSI data required for implementing an asset integrity program and predicting
remaining asset life. This includes preparing equipment for Test & Inspection
(T&I) shutdowns and reporting per SAEP-1161.
This procedure applies to process equipment and piping for process fluids,
hydrocarbon and similar flammable or toxic fluid services identified in SAEP-20
and also includes fixed equipment contained in Community and Operations
Support Facilities as stated in SAEP-309.
The monitoring of equipment for wall thickness loss and for flaw development
(such as cracking and material properties change) is referred to as “OSI
Monitoring.” It is normally conducted using an appropriate NDT method whilst
the equipment is operating (i.e., on-stream), under pressure, or inaccessible for
internal inspection. The recommended internal inspection of fixed equipment,
particularly for internal conditions and associated maintenance and test work
during shutdowns, is referred to as “Equipment Inspection.” This type of
inspection, referred to in SAEP-20, is not covered in this document. It should be
noted that thickness monitoring, or other NDT performed during “Equipment
Inspection” becomes a part of the total OSI Program.
Page 2 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Prior to T&I shutdown, OSI reports can be used to timely forecast the
replacement of components that are at or near retirement age.
2 Purpose
3.1 Any conflicts between this procedure and other applicable Saudi Aramco
Engineering Standards (SAES’s), Materials System Specifications (SAMSS’s),
Standard Drawings (SASD’s), or industry standards, codes, and forms shall be
resolved in writing by the Company or Buyer Representative through the
Page 3 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
3.2 Direct all requests to deviate from this standard in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Chairman, Inspection Engineering Standards
Committee of Saudi Aramco, Dhahran.
4 Applicable Documents
On-stream inspection shall comply with the latest edition of the references listed below,
unless otherwise noted.
Page 4 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Page 5 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
5 Definitions
Components: Parts that make up a piece of equipment or equipment item. For example
a pressure boundary may consist of components (pipe, elbows, nipples, heads, shells,
nozzles, stiffening rings, skirts, supports, etc.) that are bolted or welded into assemblies to
make up equipment items.
Corrosion Allowance (Actual): Actual Corrosion allowance is equal to the actual wall
thickness minus the retirement or minimum wall thickness. This measurement may be
different than the ‘specified corrosion allowance’ found on the SIS prepared in accordance
with SAES-A-005 or other equipment drawings, prepared during the original design.
Corrosion Loop: A term to define equipment and piping grouped together that are
similar in their process environment, made of like material and are susceptible to the
same damage mechanisms.
Page 6 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Corrosion Rate: The rate of metal loss due to erosion, erosion/corrosion or the
chemical reaction(s) with the environment, either internal and/or external.
Corrosion Service Class: Is the class determined from estimated or measured corrosion
rate as outlined in SAEP-20 Table 1.
Corrosion Under Insulation (CUI): Corrosion under insulation, including SCC under
insulation. Refer to SAES-L-133.
Examination point: (e.g., recording point, measurement point, test point) An area
within a CML defined by a circle having a diameter not greater than 2 in. (50 mm) for a
pipe diameter not exceeding 10 in. (250 mm), or not greater than 3 in. (75 mm) for
larger lines and vessels. CMLs may contain multiple test points.
General corrosion: Corrosion that is distributed more or less uniformly over the
surface of the piping, as opposed to being localized in nature.
Injection points: Locations where relatively small quantities of materials are injected
into process streams to control chemistry or other process variables. Injection points do
not include the locations where two process streams join (mixing tees).
Inspection: The external, internal, or on-stream evaluation (or any combination of the
three) of equipment and/or piping condition conducted by the authorized inspector or
his/her designee. Refer to API 572, API 574 and API 578.
Page 7 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
larger of the pressure design thickness per the ASME design codes listed in Section 4.2,
or the structural minimum thickness at a CML. It does not include thickness for
corrosion allowance, or mill tolerances. Alternately, minimum required thickness can
be reassessed using Fitness-For-Service analysis in accordance with API 579-1.
Mixing Tees: A piping component that combines two process streams of differing
composition and/or temperature.
Piping System: An assembly of interconnected piping circuits that are subject to the
same set or sets of design conditions and is used to convey, distribute, mix, separate,
discharge, meter, control, or snub fluid flows. Piping systems also include pipe-
supporting elements but do not include support structures, such as structural frames and
foundations. Damage mechanisms such as crevice corrosion under supports, fretting,
vibration, thermal expansion involving bowing, inadequate support resulting in low
spots may be applicable to a piping system.
Remaining Corrosion Allowance (RCA): is equal to the actual wall thickness minus
the minimum design thickness.
Scanning: An Ultrasonic Testing technique used to detect and locate the thinnest
thickness measurement, or cracking at a CML. Refer guidance contained in API 574.
Small-Bore Piping (SBP): Pipe or pipe components that are less than or equal to NPS 2.
Page 8 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
factors such as moisture, oxygen content of the soil and the operating temperature.
The zone generally is considered to be from 12 in. (30 cm) below to 6 in. (15 cm) above
the soil surface. Pipe running parallel with the soil surface that contacts the soil is
included.
Subject Matter Expert (SME): A person with direct knowledge of what is done in the
job, what knowledge, skills, abilities and other characteristics (KSAOs) are required, and
the general background of persons who are able to do the job successfully. These may
include those currently doing the job, recent incumbents, those who supervise others
doing the job, and other acknowledged job experts. Consult Inspection Engineering
Standards Committee Chairman for applicable SMEs in relation to this standard.
6 Instructions
6.1 Comprehensive OSI Program: The Inspection Unit Supervisor will design a
facility specific comprehensive OSI program to be inclusive of the following
elements:
The Inspection Unit Supervisor will also incorporate information from other
programs such as maintenance, engineering assessments, corrosion engineering,
cathodic protection, coatings and other information considered necessary to
produce a comprehensive OSI program.
6.2 Process equipment, piping and pipelines: This section outlines instructions to
operate and administer an OSI program. This program is set-up using the
requirements of SAES-A-135 and SAES-L-133.
6.2.1 Review the existing OSI program and determine whether it was
established using one of following scenarios:
Page 9 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.2.2.4 Review overdue and due CML data and perform appropriate
NDT per the requirements of SAES-A-135. Investigate and
resolve any anomalous data or inconsistency. Issue defect
notification per 00-SAIP-76, if necessary.
6.2.2.5 Update OSI drawings and NDT measurement data in the SAP
Application for Inspection of Facilities (SAIF) program.
6.2.2.6 Analyze OSI data results and trends per paragraph 6.4 of this
procedure. Investigate and resolve any anomalous data or
inconsistency. Issue defect notification per 00-SAIP-76, if
necessary.
6.2.2.7 Issue any reports to management and others per paragraph 6.8
of this standard and your organization requirements.
Page 10 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.2.3.5 Update OSI drawings and NDT measurement data in the SAP
Application for Inspection of Facilities (SAIF) program.
Update date of next inspection based on RBI inspection plan.
6.2.3.6 Issue any reports to management and others per paragraph 6.8
of this standard and your organization requirements.
Page 11 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
This method is only approved for use where the predicted damage
mechanism is general thinning as defined by API RP 571.
Page 12 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Type A grid: the area within the grid is scanned and the lowest
thickness is recorded for that cell. Type A is normally suitable
for components where the monitoring of migration or
development of localized corrosion is required.
Page 13 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
For General and Localized Thinning Damage Mechanisms, once two or more
successive thickness readings are available, OSI measured CML and
equipment/circuit information can be calculated manually or automatically by
the SAP Application for Inspection of Facilities (SAIF) program for each CML
component are:
6.4.1 CMLs
● Long Term Corrosion Rate
● Short Term Corrosion Rate
● CML Retirement Date
● CML Recommended Inspection Date
● Remaining Life Calculation
Page 14 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.5.1 After Components have been baseline-measured, noted for flaws, and the
Corrosion Class has been estimated, the first monitoring dates can be
determined. This allows the initial monitoring dates to fit the expected
corrosion conditions as shown by the Corrosion Class.
6.5.4 If the initial measured corrosion rate exceeds the estimated corrosion
rate, additional follow up inspection should be performed to validate the
findings.
6.5.5 The maximum inspection intervals based on OSI data are as listed in
Table 1 below:
Page 15 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Table 1
6.6.1 The OSI program is not a static system and will change over time as the
corrosion profile of the equipment changes. These changes shall be
reflected in the number, location and NDT method of the CMLs per
component. The Corrosion Engineer and Inspection Supervisor (or
delegate) shall review the OSI program on an annual basis to refine the
number and location of CMLs in a comprehensive review. Appendix A
flow chart identifies one possible scenario for performing and optimizing
an OSI program.
Page 16 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.6.2.1 Compare the P&IDs to the OSI drawings to verify all required
piping circuits and equipment are included in SAIF. Any missing
must be added with UTT or scanning performed at scheduled
intervals per paragraph 6.5.5 Table 1 of this procedure.
6.6.2.3 Review all CML readings for accuracy. Any readings that are
questionable must be verified.
6.6.2.4 Review the NDT technique used for each CML to ensure it is
appropriate to inspect for the damage mechanism type.
6.6.2.5 Review the number and location of each CML to ensure proper
monitoring.
6.6.2.9 Review the results and robustness of the small diameter nipples
monitoring program.
6.7.1 No more than 50% of CML for thinning shall be removed from an
Page 17 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.7.5 MEDIUM RISK components with a probability of 1 and are class 3 per
SAEP-20 criteria are re-evaluated..
6.7.7 Inspection technique must be able to detect the damage mechanism type
(localized corrosion - scanning, etc.).
6.7.11 Only shell CML are eligible for vessels and fin fans, no reduction for
nozzles.
6.8 Reporting
6.8.1 All OSI data reporting shall be addressed to the Supt. Operations with
copies to the Plant Manager, Engineering Supt. and Maintenance Supt.
Proponent local reporting needs may only modify the distribution list of
copies.
6.8.3 An Annual OSI status report shall be prepared to show progress made
during baseline and regular OSI monitoring. An updated master list of
all components due for retirement within the approved T&I interval
years should be included in the report. This report can be part of other
regular Inspection Unit Reporting.
Page 18 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
6.8.4 Once OSI data has been gathered and analyzed, reports can be prepared
by computer into one or more of the following types of reports.
This report illustrates all thickness readings and the dates taken
for each CML by area and component. It also includes the
corrosion class, the long and short term corrosion rates, the
remaining life, next inspection date and shall include
equipment condition.
Page 19 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
This report displays all CML that are overdue for inspection
showing corrosion class, long and short term corrosion rates,
the remaining life and the planned inspection date.
6.8.6 During OSI, it will be necessary to make changes and revisions to the
program, CML’s, drawings, etc., and all changes should be in
accordance with the requirements of SAES-A-135.
7 Responsibilities
7.1.1 Assures an active OSI Program and responsible for the planning and
administering of the OSI Program within his area of responsibility.
7.1.2 Assures the availability of an active OSI program and all unit personnel
have access to the program for the required action.
7.1.4 Ensures a comprehensive review of the OSI program has been performed
a minimum of every ten years to ensure its robustness.
Page 20 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
7.1.5 Ensures optimization of the CMLs in the OSI program after every RBI
assessment, or comprehensive review.
7.1.8 In case, the Unit has no assigned Corrosion Engineer, the Unit
Supervisor shall seek the support of either a qualified engineering service
provider or CSD.
7.2.1 Develops the corrosion loops per SAES-L-133 using the process flow
diagrams and descriptions per SAEP-343 paragraph 6.2.1.
7.2.2 Estimates corrosion rates for each component that does not have a
measured corrosion rate.
7.2.3 Assigns CMLs to each component so that the quantity and location
matches the expected or known corrosion class.
7.2.4 At least review corrosion rates greater than 0.12 mpy (5 mpy) annually
or components with remaining life less than twice the OSI interval and
issue a report of the review to the Inspection Supervisor.
7.2.6 Reviews the result of CML surveys and set next inspection intervals
according to comprehensive review, or RBI.
7.3.3 Issues the required OSI progress reports and OSI CML overdue reports
to the Unit Supervisor.
7.3.4 Coordination of NDT actions between the area inspectors and the NDT
technicians.
Page 21 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
7.4.3 Reviews OSI data with the responsible Area Inspector and advise
accordingly.
7.4.4 Ensures OSI program data is reviewed, analyzed, and added to the
equipment per T&I reports.
7.5.2 Reviews OSI data periodically (at least monthly) and plan/coordinate all
resources necessary to complete OSI with no overdue CMLs.
7.5.4 Requests for preparation of OSI isometric drawings of new piping and
equipment.
7.5.6 Updates or coordinates SAIF program and/or the RBI database with the
latest CML measurements and results of all inspections.
7.5.7 Verifies all data entered into SAIF and/or the RBI database.
Page 22 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Reviews the OSI program during OIU review in accordance with SAEP-308.
Revision Summary
29 December 2104 Major revision.
Page 23 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
SAES-A-135
SAEP-1135
Perform OSI for CML
All OSI steps or NDT as required to
map corrosion and validate damage
mechanisms
Damage Other
Mechanism Damage
Mechanism
Metal
Loss
Class No
0 or 1
Yes
Comprehensive Review
SAEP-1135
MOC, Deviations, Schedule
Revisions, APM, Audit Results.
No Any changes
to CMLs?
Yes
SAES-A-135
Page 24 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
Updated S Supports
supervisor
Insp. Field
Inspection
Corrosion
Inspector
Engineer
Division
Supv.
Head
ID
Paragraph Description
Page 25 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
C.1 SAP Application for Inspection of Facilities (SAIF) program shall be used for
conducting OSI Program calculations and scheduling. Some of the basic
calculations performed by SAIF are identified in this section. For a detailed
description of these calculations refer to API 570 paragraph 7.1.1
C.4 T-min calculations are performed for Piping, Vessels, Power Boilers and Tanks.
These calculations are based on formulas from the industry standards governing
their design. Refer to section 4.2 for a list of applicable ASME codes.
C.5 Structural T-min is obtained from SAES-L-310 paragraph 10.4 Table 1 and
paragraph 10.5 Table 2.
Page 26 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
1
Upstream Weld Downstream
1 Sequence
Right Hand Rule
Imaginary grip of pipe-
Flow Thumb points in
2,4 direction of flow, fingers
4 2
point in sequence of
measurement location
numbering.
3
3
NORTH
Flow
Downstream
1
1,3
2, 4
Weld
2 4
Upstream
Page 27 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
FLOW 270 90
1D 1D 180
90
180
270
Page 28 of 29
Document Responsibility: Inspection Engineering Standards Committee SAEP-1135
Issue Date: 29 December 2014
Next Planned Update: 29 December 2019 On-Stream Inspection Administration
FLOW 270 90
1D 1D 180
TYPE A GRID
0 1 2 3 4 5 6 7 8 9 10 11 12
A 0
B
C
D 90
E Each square
F scanned & T
G 180 minimum
Recorded for
H
each square
I
J 270
K
L
M 0
TYPE B GRID
0 1 2 3 4 5 6 7 8 9 10 11 12
A 0
B
C Intersection of
each grid spot
D 90
measurement &
E recorded
F
G 180
H
I
J 270
K
L
M 0
Page 29 of 29