MV/LV TRANSFORMERS
Rev. 0
26/10/2019
MV/LV TRANSFORMERS
This document is intellectual property of Enel SpA; reproduction or distribution of its contents in any way or by any means whatsoever is
subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
INDEX
1 SCOPE ------------------------------------------------------------------------------------------------------------------------ 7
5 RATINGS --------------------------------------------------------------------------------------------------------------------- 9
5.12 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS ------------------------------------10
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
5.17 TOLERANCES------------------------------------------------------------------------------------------------------------11
6.5 BUSHINGS----------------------------------------------------------------------------------------------------------------12
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
7 EXCEPTIONS ---------------------------------------------------------------------------------------------------------------13
8 DOCUMENTATION -------------------------------------------------------------------------------------------------------13
9 TESTS ------------------------------------------------------------------------------------------------------------------------15
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
9.2.1.7 LEAK TESTING WITH PRESSURE FOR LIQUID-IMMERSED TRANSFORMERS (TIGHTNESS TEST)
18
9.2.2.5 MEASUREMENT OF NO-LOAD LOSS AND CURRENT AT 90 % AND 110 % OF RATED VOLTAGE 20
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
GUARANTEE ---------------------------------------------------------------------------------------------------------------------21
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
1 SCOPE
The scope of this document is to provide technical requirements for the supply of the distribution
transformers to be used in the distribution networks.
This document is applicable for liquid immersed transformer, three-phase, bi-phase and single-
phase for indoor, outdoor, pole mounted and inbox installation.
This document is composed by a main common part, three Local Section and a common list of
main requirements in order to provide full information for transformers for each relevant country.
Additional prescriptions or integration to the main common part are reported in the Local Sections
with the same corresponding clause or sub-clause number.
2 LIST OF COMPONENTS
The list of components with the main requirements, which is an integral part of the present
document, is reported in: “MV/LV Transformers reference list” (Common List) attached.
3.1 LAWS
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
• IEC 60076-7 (2005) Power transformers – Part 7: Loading guide for oil-immersed power
transformers
• IEC 60076-10 (2001) Power transformers – Part 10: Determination of sound levels
• IEC 60214-1 Tap-Changers - Part 1: Performance requirements and test methods
• IEC 60214-2 Tap-Changers - Part 2: Application guide
• IEC 60815 Guide for the selection and dimensioning of high-voltage insulators for polluted
conditions
• IEC 60137 Insulated bushings for alternating voltages above 1 000 V
• IEC 60296 (2012) Fluids for electrotechnical applications - Unused mineral insulating oils
for transformers and switchgear
• IEC 60422 Mineral insulating oils in electrical equipment - Supervision and maintenance
guidance
• IEC 60317 Specifications for particular types of winding wires
• IEC 60085 Thermal evaluation and designation of electrical insulation
• IEC 60641-2 Pressboard and presspaper for electrical purposes - Part 2: Methods of test
• IEC 60417-2 Graphical symbols for use on equipment - Part 2: Symbol originals
• ISO 2808 Paints and varnishes – Determination of film thickness
• ISO 2409 Paints and varnishes - Cross-cut test
• ISO 2859-1 Sampling procedures for inspections by attributes
• ISO 2178 Non-magnetic coatings on magnetic substrates - Measurement of coating
thickness - Magnetic method
• ISO 4628-3 Paints and varnishes - Assessment of degree of rusting
• EN 50464-1 (2007-11) Three-phase oil-immersed distribution transformers - General
requirements
• EN 50216-4 Three-phase oil-immersed distribution transformers - Requirements and tests
concerning pressurized corrugated tanks
• EN 50180 Bushings above 1 kV up to 36 kV and from 250 A to 3,15 kA for liquid filled
transformers
• EN 50386 Bushings up to 1 kV and from 250 A to 5 kA for liquid filled transformers
• EN 50387 Busbar bushings 1 kV and from 1,25 kA to 5 kA for liquid filled transformers
• DIN 42551 Oil drain devices
and all the Standards mentioned in those listed above.
When the date of issue is not mentioned in the list above, the date to be taken as reference is that
of the standard in force when the present document has been issued.
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
4 SERVICE CONDITIONS
Unless otherwise specified the normal service conditions defined in IEC 60076-1 apply with the
following exceptions:
Characteristic
Altitude (m)
Pollution level
Medium
(IEC 60815)
Seismic
Yes (1)
activity
5 RATINGS
For the definitions IEC 60076-1 applies.
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
5.10 INSTALLATION
The type of installation can be indoor, outdoor, pole mounted and inbox.
Transformers are generally used for step-down voltage purpose but they can also be used as step-
up. In the network, they could occasionally be subjected to frequent energisations, overvoltages
and short-circuits.
For Italy, Romania and Spain the losses shall be in compliance with EU Regulation.
Possible capitalization criteria for further loss reductions are given in the tender, if not specified in
Local Section.
For measured losses exceed the prescribed values and/or declared by the Manufacturer, within the
tolerance admitted in 5.17, penalties will be applied.
If the losses exceed the maximum tolerance limits admitted by IEC 60076-1, the transformer is
rejected.
The calculation of the penalties to apply to the single transformer, is the following:
Lv = 2 × Cv × ∆Pv
Lj = 2 × Cj × ∆Pj
where:
Lv penalties for no-load losses excess (expressed in local currency)
Lj penalties for load losses excess (expressed in local currency)
Cv no-load losses penalties rate (expressed in local currency per kW) (1)
Cj load losses penalties rate (expressed in local currency per kW) (1)
∆Pv difference between measured no-load losses and no-load losses declared by the
Manufacturer (kW)
∆Pj difference between measured load losses and load losses declared by the Manufacturer
(kW)
(1) Values given at tender stage
5.15 OVERLOADING
Transformers shall withstand overloading in the conditions specified in IEC 60076-7.
MV/LV TRANSFORMERS
Rev. 0
26/10/2019
5.17 TOLERANCES
See IEC 60076-1 and in compliance with EU Regulation for European countries.
6 DESIGN REQUIREMENTS
Unless otherwise specified, the transformers shall comply with IEC 60076-1; the single parts of the
transformers shall comply with the relevant standards.
6.1 CORE
The core shall be made wrapped type or cold rolled magnetic strips. The material shall be grain
oriented or amorphous.
6.2 WINDINGS
The windings shall be made of electrolytic copper of 99.9% purity or aluminum conductors of at
least 99.5% aluminum content; the cross section of windings shall be constant.
The star point of the LV windings shall be made on the connections of the layer or turn nearer to
the oil duct between LV and MV windings.
The enameled insulated conductors shall comply with IEC 60317.
The ties of joints and connections from the windings to the bushings or to the de-energized tap-
changer shall be manufactured in order to prevent the damaging of the conductor insulation during
transformers lifetime.
For Italy and Romania for rated power up to 160 KVA it is mandatory to manufacturer the windings
in aluminium.
6.3 TANK
The tank shall be made of steel sheets and shall not permit stagnation of water on the cover.
The tank can be provided sealed (without conservator), with full oil filling or with gas-cushion.
The coupling tank-cover shall be made by using a seal gasket, stainless steel fixing screws and
washers, and brass or hot zinc-plated nuts.
In the sealed solution, the coupling by uninterrupted welding is also acceptable.
The tank shall be provided with standing and sliding devices, and also with lifting and blocking
devices as specified in the following.
The whole tank, the cover and the accessories shall be uninterruptable connected (galvanic
contact).
The cooling system is considered an integral part of the tank.
In case of hermetically tank transformers with gas-cushion and MV inside cone plug-in
connections, specific design solutions shall be taken to assure the performance and reliability of
the transformers.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
Transformers ≤ 160 kVA 250-400 kVA 630 kVA > 630 kVA
Max oil quantities 200 liters 400 liters 500litres 600 liters
The value given in the table are applicable with the following indications:
• For rated power > 1000kVA oil quantity higher than 600 liters can be agreed.
The solid insulation material used shall be in compliance to class “A” (105°C) of IEC 60085 or
higher. The evaluation of the material should be carried out in accordance with the IEC 60641-2.
Further specific requirements are requested in Local Sections.
6.5 BUSHINGS
Bushing shall be in compliance with their relevant standards.
The MV bushings shall be fixed to the tank cover by using stainless steel studs, washers and nuts
(or brass or hot galvanized steel nuts) and light metal alloy or stainless steel spacers and flanges.
Each MV and LV bushing shall be prearranged for sealing, by one drilled stud or two nuts.
Indications about bushing identifications and markings are reported in Local Sections.
The following solutions are defined for Medium Voltage and Low Voltage bushings.
6.5.1 MV Bushings
Solution MV Bushing
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
6.5.2 LV Bushings
Solution LV Bushing
1 EN 50386 - type 1)
2 EN 50386 - type 3)
3 EN 50386 - type 4)
4 EN 50386 - type 5)
5 EN 50386 - type 6)
8 IEC 60137
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
6.9 PAINTING
The external painting of transformers and the metallic accessories made of iron materials, shall be
obtained by using epoxy or polyurethane painting cycle as indicated in the following:
Medium ≥ 60 ≥ 60 ≥ 120
(1)
Base layer - Primer-epoxy with zinc: 80 µm + Epoxy-polyamide micaceous iron oxide: 80 µm
(2)
Cover layer - Polyurethane aliphatic: 60 µm
NOTE: alternatively the painting may be made by one layer of the same total thickness, also
mono component. Galvanized layers are also accepted.
Internal surfaces of the transformers shall be protected by a hot oil resistant painting (epoxy-
polyamine or equivalent), ≥ 30 µm thick.
The surfaces to be painted shall be prepared by Manufacturer practice with suitable sandblasting
or chemical cleaning (degreasing) treatments, specific for the painting cycle adopted.
The paint must be free of lead oxides or chromates. The safety and technical data sheets of the
painting shall be provided by the Manufacturer.
The color to be used is prescribed in Local Section.
The reports and tests aimed to verify the good quality and the process of the painting cycle shall be
provided by the Manufacturer.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
6.10 ACCESSORIES
Each transformer shall be provided with the accessories as indicate:
Rating plate X X
Filling hole and
X X
plug (filling cap)
(1) Only if specifically required
Furthermore 4 (four) blocking eyebolts shall be provided in the upper part of the tank for the
blocking of transformers during transport. These four blocking eyebolts shall have a minimum
diameter of 24 mm and shall be positioned in a way that, when in use, they will not damage
accessories and cooling system.
This device shall be placed at the bottom of the tank on the left short side looking at the
transformer from the MV bushings side.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
7 EXCEPTIONS
Possible exceptions to the present prescriptions, concerning the adoption of technical and/or
manufacturing aspects different from the ones prescribed in the present GS, can be evaluated by
the Distribution company. In such a case, the Distribution company will take into account the
opportunity to require additional tests with regard to the technical/manufacturing proposed
solutions.
Such exceptions can be approved only by the Distribution company.
8 DOCUMENTATION
The Supplier, for each transformer prototype to be subjected to homologation or certification
procedure, shall make available a complete documentation containing calculations, drawings,
schemas, pictures of the MV and LV side, internal and external, descriptions, list of characteristics,
performances, assembling, maintenance and operational norms and whatever necessary for the
complete acknowledgment of the transformer.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
In addition to the documentation above, the Manufacturer shall submit all the test reports of the
transformer, components and materials used and a document with the calculation of the capability
to withstand the short circuit (in case of the test is not performed).
The documentation shall be in English or local language, except for the rating plates and the
manuals that shall be in local language.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
9 TESTS
Unless otherwise specified IEC 60076-1 applies.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
To define the number of samples submitted to be tested for each batch of similar
transformers, reference shall be made to general inspection level II. The following table
gives an example of the sampling plan for transformer lots less than 500 units.
As shown in the table, for lots greater than 15 units is prescribed a double sampling.
If the number of defectives found in the first sample is equal or less than the first
acceptance number, the lot or batch shall be considered acceptable.
If the number of defectives found in the first sample is equal or greater than the first
rejection number, the lot or batch shall be rejected.
If the number of defectives found in the first sample is between the first acceptance and
rejection numbers, the number indicated in the table of the sample size for second sample
shall be inspected.
The number of defectives found in the first and second sample shall be accumulated. If
cumulative number of defectives is equal or less than the second acceptance number the
lot, shall be considered acceptable.
If the cumulative number of defectives is equal or greater than the second rejection number,
the lot or batch shall be rejected.
The transformers resulting afflicted by defects during the test are rejected. When the non-
conformance is repaired, with Distribution Company representatives agreement, the units
can be resubmitted to the test.
(1)
NOTE: for test 8) “Oil tests”, further reduction of the transformers to be tested, up to two
oil samples for each lot, can be agreed between Distribution Company representatives
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
and Manufacturer during acceptance tests if the quality and treatments of oil are proved
by the manufacturers also by quality documentations for each lot of impregnation.
The routine tests shall be performed by the Manufacturer at the Customer inspector presence if not
otherwise agreed (the Manufacturer shall always inform the Customer in due time about the
scheduled period to give the possibility to attend or not the tests).
In case of tests performing without inspector supervision, the Manufacturer may be requested to
repeat the tests on the same sample size that shall be selected by the Customer inspector.
At the end of the testing, within the limits of the measures accuracy, no difference between the
measured values and the values registered by the Manufacturer shall be found. If the testing of
one unit is negative, the whole lot shall be rejected.
The Manufacturer shall prepare a test report containing the results of the tests.
Before Type and Special tests performing, the unit shall have already passed all Routine Tests
except test 1) and 6).c.
When permitted, in case of several transformers with same rated power and insulation level, but
different rated voltage levels, possible further reduction of tests are reported in Local Sections.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
9.2.1.7 Leak testing with pressure for liquid-immersed transformers (tightness test)
According to IEC 60076-1 § 11.8.
For totally filled transformers the maximum over pressure P+ (reference EN 50464-4) shall be
maintained for 8 hours. At the end of the test the transformer shall not show leakages. After the
test the pressure value shall be restored at the rated value.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
The verifications above listed shall be performed on one sample of mineral oil, for each
impregnating lot.
In case the instrumentations is available and certified in the manufacturer laboratory, the
verifications can be performed by the manufacturers itself with the attendance of Enel or
independent certification body representative, when permitted by the procedures (acceptance tests
on lots).
For the PCB absence it is mandatory to perform the verification in a laboratory accredited ILAC or
IAF in compliance with the test method of IEC 61619 with the indication of the tranformer sampled.
The detectability value of the analytic method shall be al least 2 mg/kg (2 ppm) to assure the
respect of the parameters reported in table 3 of IEC 60422.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
9.2.2.5 Measurement of no-load loss and current at 90 % and 110 % of rated voltage
According to IEC 60076-1.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GUARANTEE
The transformer guaranty is for a minimum period of 5 years, if not otherwise agreed.
Moreover the below conditions are valid for the guarantees of painting.
• during the twenty-four (24) months of the period of guarantee for faults as those described
at previous point, the Manufacturer will have to, at his own expenses, carry out all the
necessary finishing touches to eliminate possible alterations of the painted surface (blisters,
split tings of the film of paint etc.). These alterations must not, however, cover more than
5% of the entire painted surface.
• The Manufacturer must also issue a five year guarantee (starting from the date of the end
the acceptance tests with positive result). At the end of this period of guarantee, there it
must not be rust on more than 1% of the entire painted surface; this compares to a rusting
level not above the Ri3 (see ISO 4628-3).
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
12 FIGURES
S RATINGS
OPERATING C ONDITIONS
C on t ac t ar ea
Type of inst allat ion indo or
Am bient air t em per at ur e:
- m axim um ( °C ) 40
- m axim um of t he daily m ean values ( °C ) 30
- m in im um ( °C) - 25
S
- m axim um ( °C ) 100
Fem ale c ont a c t par t
1 - Mat er ials:
- synt het ic r esin insulat ing par t s
- c onduc t ive c opper or c opper anoy part s
2 - The f em ale c o nt a c t par t ( P) shall have pr oper dim ens y ons t o be c oupled wit h
t h e plug- in c ont ac t ( S) : it m ust has lam ellar c ont ac t s.
3 - The ac c essor ies ( V) ( sc rews, washer s and nut s) , and t he pulg- in c ont act ( S)
ar e not par t of t he bus hing.
GROOVE
3 x 3 mm
St ud bolt
Hole Ø 1 3
3
. . Gas k et
. .. . . . ..
Tr a ns f or m er
3 c ov er
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
n° 5 holes Ø 13
part. 1
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
LV c a b le
C lam p
C o m p r essio n c a b le t er m ina l
In sula t in g pr o t ec t io n
Fixin g f lan g e
B u sba r b u shin g
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
In addition on what specified in the common part, the following requirements are prescribed:
3.2 INSTALLATION
Mounting System
Single-Pole Double-pole Surface Level
≤ 150 >75 not used
Table A1 – Mounting system
NOTE 1: All transformers require anchoring base to be used either single-pole, double pole or
surface level and TR ≤150kVA require support.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
3.5 WINDINGS
For Edelnor, rated power transformers of ≤ 100 kVA the use of aluminum is mandatory for MV
and LV winding.
3.6 TANK
In the case of transformers with a non-welded lid, the active part, which is mounted to the tank
walls, should have devices (hooks, holes, or others) that facilitate its removal and placement.
These devices should be symmetrical and guarantee lifting without horizontal movement; and
they should be different from the tank fastening supports.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GASKETS
Seal materials of transformers should be nitrite rubber or higher, in accordance with ASTM
D297, ASTM D2240 and ASTMD471
3.8 BUSHINGS
The MV bushing is considered the solution 6 considering porcelain or silicon rubber polymer as
IEC 60137, and may be bolted either on or under the cover, according to the manufacturer’s
offer.
The LV bushing is considered the solution 8 considering porcelain or epoxy as IEC 60137, or
porcelain insulators and terminals according to DIN42530 standard NEMA or where indicated,
see Table A3.
Capacity
[kVA]
Locking
≤75kVA
connector
Blade
>75kVA and
connector
≤150kVA
(NEMA 2)
Blade
>150kVA connector
(NEMA 4)
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
For companies exposed to an environment with pollution levels of High and Very High, epoxy
bushings should be accompanied by certificates demonstrating the good performance of this
material in this type of environment. The testing certificates to be submitted will correspond to
those defined as special tests according to IEC60068:
• Saline mist cycle – 96 hours
• Heat and humidity cycle – severity of 40ºC, 6 cycles.
• UV Rays
• Climatic sequence – method 1
3.9.1 SUPPORTING
The position of the mounting support (on the MV or LV) for single-pole mounted transformer will
be defined by each distribution company and is also detailed in Table A4.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
3.9 PAINTING
The color is RAL7038.
≥ 75 KVA
≥ 150 KVA
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
Special Test
Short-circuit test. The sample shall be one unit by type of transformer. The rated power will be
on agreement with the Distribution Company.
NOTE. Type of transformer. Group of transformers which have the same voltage level in the
primary side and the same kind of core, wrapped type or cold rolled . Transformers with dual
voltage level on the primary side should be considered a different type.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
The equipment should be individually packed onto treated wood or plastic pallets in a way
suitable for transport, in such a way as to avoid any damage to equipment. The packing should
be suitable for introducing equipment into standard transport industry containers. All additional
elements of the equipment should be packed into a single crate.
Transformers should be transported with their complete oil load and accessories in place. The
transformer should be completely secured in its packaging.
A visual inspection of the equipment will be carried out upon receiving it, checking for possible
damage occurred during transport and the warehousing process. In addition, the p
resence of the complementary elements should be verified (clamps, grounding bolt, fuses, etc.)
Packaging should be able to withstand the weight produced upon stacking up to 3 single-phase
and 2 three-phase transformers of normal capacity no higher than 150 kVA.
A list of the packaging brands should be submitted for the Client’s comments and final approval.
The country of manufacture should be included in the packaging information.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
Figure A10
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
In addition on what specified in the common part, the following requirements are prescribed:
3.1 LAWS
R.D. 337/2014 “Reglamento sobre condiciones técnicas y garantías de seguridad en
instalaciones eléctricas de alta tensión y sus Instrucciones Técnicas Complementarias ITC-RAT
01 a 23.”
R.D. 614/2001 “Disposiciones mínimas para la protección de la salud y seguridad de los
trabajadores frente al riesgo eléctrico”.
and subsequent modification/integration.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
6.5 BUSHINGS
Looking at the transformer from the low voltage side, the low voltage bushing are designated
from right to left, by the following symbols:
N - 2U - 2V - 2W
Looking at the transformer from the high voltage side, the high voltage bushings are designated
from left to right by the following symbols:
1U - 1V - 1W
For the class B1B2 transformers, the low voltage bushing symbols are as following:
Looking at the transformer from the low voltage side, the low voltage bushings are designated
from right to left by the following symbols:
N - 2U - 2V - 2W - 3U - 3V - 3W
The symbols, which will be perfectly visible, must be located and marked on the tank cover
indelibly, in relief and with a minimum size of 30 mm.
The transformers (B1B2) with Type 4, Type 5 and Type 6 LV bushings will be supplied with the
corresponding flat coupling part.
6.8.1 SUPPORTING
The transformers of 50, 100 and 160 kVA will have a suspension device solidly joined (welded or
screwed) to the tank for its mounting on a pole in accordance with Figure B1:
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
The dimensions of the wheels and the distances between shafts are those indicated in EN
50216-4 Standard, chapter 8.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
6.9 PAINTING
The color of the external painting shall be type S 8010-R90B as described in UNE 48103
Standard. The equivalent color of RAL 840-HR is RAL 5008.
The type and model of thermometer to be installed in these transformers is indicated in the
ENDESA Technical Specification 6700496.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
The contents, layout, dimensions and materials shall be as indicated in the following figures:
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
c) a number or numbers separated by a dash, indicating the rated primary voltages in kV. It
follows a) and b) and separated from them by a slash
d) the class (B2 or B1B2)
e) the reference to this Standard
f) Code assigned by the Manufacturer to each series of identical units, in brackets.
The K factors of the dual secondary voltage transformers can be identified by plates of 105 x 40
mm, white, with the identification K = 0.75 or K = 1, in black characters with a minimum height of
30 mm, mounted on the rating plate supports.
Yellow rectangular plates 105 x 40 mm, fastened to the lower part of the rating plate supports,
indicating "420 V" in black characters with a minimum height of 30 mm.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
In case of several transformers with same insulation level, but different rated voltage levels, it is
possible to perform type and special test on only one transformer for each of the following
families, provided that the all transformers are made using the same technology.
• Family 1: Transformers with Um= 24 kV and rated power between 50 and 250 kVA, both
included.
• Family 2: Transformers with Um= 24 kV and rated power between 400 y 1000 kVA both
included.
• Family 3: Transformers with Um= 36 kV and rated power between 50 y 250 kVA both
included.
• Family 4: Transformers with Um= 36 kV and rated power between 400 y 1000 kVA both
included.
For other transformers, the manufacturer must demonstrate that the constructive method allows
to extend the validity of the above tests to the rest of the range or if additional testing is
required.
GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018
COMMON LIST
GST001/801 6785304 15 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 2P Ii0 2a4 Sol. 6 480 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No
GST001/802 6785307 45 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No
GST001/803 6785299 75 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No
GST001/804 6785300 150 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No
GST001/805 6785302 300 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No
GST001/806 6785303 500 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No
GST001/807 6752137 15 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 2P Ii0 2a4 Sol. 6 350 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No
GST001/808 6776039 45 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No
GST001/809 6776050 75 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No
GST001/810 6752143 150 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No
GST001/811 6776052 300 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No
GST001/812 6752145 500 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No
GST001/813 6776053 15 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 2P Dyn1 2a4 Sol. 6 490 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No
GST001/814 6752167 45 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No
GST001/815 6752168 75 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No
GST001/816 6776057 150 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No
GST001/817 6752170 300 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No
GST001/818 6752171 500 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No