Ene Ssaa 23 Ssaa

This document outlines the technical requirements for MV/LV transformers used in distribution networks, applicable to various transformer types and installations. It includes specifications on components, service conditions, ratings, design requirements, and testing protocols, referencing multiple international standards. The document serves as a comprehensive guide for the supply and installation of transformers, ensuring compliance with relevant laws and performance criteria.

Uploaded by

BRANDON MARTINES
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views48 pages

Ene Ssaa 23 Ssaa

This document outlines the technical requirements for MV/LV transformers used in distribution networks, applicable to various transformer types and installations. It includes specifications on components, service conditions, ratings, design requirements, and testing protocols, referencing multiple international standards. The document serves as a comprehensive guide for the supply and installation of transformers, ensuring compliance with relevant laws and performance criteria.

Uploaded by

BRANDON MARTINES
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 48

GLOBAL STANDARD Page 1 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

MV/LV TRANSFORMERS

This document is intellectual property of Enel SpA; reproduction or distribution of its contents in any way or by any means whatsoever is
subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.

Revisión Fecha Listado de modificaciones


00 26/10/2019 Versión editada para proceso de licitación Decreto Exento N°198/2019

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 2 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

INDEX

1 SCOPE ------------------------------------------------------------------------------------------------------------------------ 7

2 LIST OF COMPONENTS --------------------------------------------------------------------------------------------------- 7

3 REFERENCE LAWS AND STANDARDS--------------------------------------------------------------------------------- 7

3.1 LAWS ----------------------------------------------------------------------------------------------------------------------- 7

3.2 INTERNATIONAL STANDARDS -------------------------------------------------------------------------------------- 7

4 SERVICE CONDITIONS ---------------------------------------------------------------------------------------------------- 9

5 RATINGS --------------------------------------------------------------------------------------------------------------------- 9

5.1 TYPE OF TRANSFORMERS -------------------------------------------------------------------------------------------- 9

5.2 NUMBER OF WINDINGS ----------------------------------------------------------------------------------------------- 9

5.3 NUMBER OF PHASES --------------------------------------------------------------------------------------------------- 9

5.4 COOLING SYSTEM ------------------------------------------------------------------------------------------------------- 9

5.5 RATED POWER ---------------------------------------------------------------------------------------------------------- 9

5.6 RATED VOLTAGES ------------------------------------------------------------------------------------------------------ 9

5.7 RATED FREQUENCY ---------------------------------------------------------------------------------------------------- 9

5.8 VOLTAGE REGULATION ----------------------------------------------------------------------------------------------- 9

5.9 WINDINGS CONNECTIONS -------------------------------------------------------------------------------------------- 9

5.10 INSTALLATION ---------------------------------------------------------------------------------------------------------10

5.11 INSULATION LEVELS --------------------------------------------------------------------------------------------------10

5.12 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS ------------------------------------10

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 3 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

5.13 TEMPERATURE RISE --------------------------------------------------------------------------------------------------10

5.14 CAPABILITY TO WITHSTAND SHORT-CIRCUIT ----------------------------------------------------------------10

5.15 OVERLOADING ---------------------------------------------------------------------------------------------------------10

5.16 OVERALL DIMENSIONS AND LAYOUT ----------------------------------------------------------------------------11

5.17 TOLERANCES------------------------------------------------------------------------------------------------------------11

6 DESIGN REQUIREMENTS -----------------------------------------------------------------------------------------------11

6.1 CORE ----------------------------------------------------------------------------------------------------------------------11

6.2 WINDINGS ---------------------------------------------------------------------------------------------------------------11

6.3 TANK ----------------------------------------------------------------------------------------------------------------------11

6.4 INSULATING LIQUID AND MATERIAL-----------------------------------------------------------------------------11

6.4.1 OIL FILLING AND SEALING PROCEDURES ---------------------------------------------------------------------12

6.5 BUSHINGS----------------------------------------------------------------------------------------------------------------12

6.5.1 MV BUSHINGS --------------------------------------------------------------------------------------------------------12

6.5.2 LV BUSHINGS ---------------------------------------------------------------------------------------------------------13

6.6 DE-ENERGIZED TAP-CHANGER FOR MV VOLTAGE REGULATION -----------------------------------------13

6.7 DE-ENERGIZED TAP-CHANGER FOR MV VOLTAGE COMMUTATION--------------------------------------13

6.8 SUPPORTING AND SLIDING DEVICES -----------------------------------------------------------------------------11

6.9 PAINTING ----------------------------------------------------------------------------------------------------------------11

6.10 ACCESSORIES -----------------------------------------------------------------------------------------------------------12

6.10.1 LIFTING AND BLOCKING DEVICES ------------------------------------------------------------------------------12

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 4 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

6.10.2 OIL DRAIN DEVICE AND SAMPLING PLUG OR VALVE ------------------------------------------------------12

6.10.3 THERMOMETER POCKET -----------------------------------------------------------------------------------------12

6.10.4 OVER PRESSURE VALVE -------------------------------------------------------------------------------------------13

6.10.5 OIL LEVEL INDICATOR ---------------------------------------------------------------------------------------------13

6.10.6 EARTHING TERMINALS --------------------------------------------------------------------------------------------13

6.11 IDENTIFICATION OF ACCESSORIES AND COMPONENTS -----------------------------------------------------13

7 EXCEPTIONS ---------------------------------------------------------------------------------------------------------------13

8 DOCUMENTATION -------------------------------------------------------------------------------------------------------13

8.1 NOT-RESERVED DOCUMENTATION -------------------------------------------------------------------------------14

8.2 RESERVED DOCUMENTATION --------------------------------------------------------------------------------------14

8.3 TECHNICAL DOCUMENTATION-------------------------------------------------------------------------------------14

9 TESTS ------------------------------------------------------------------------------------------------------------------------15

9.1 LIST AND CLASSIFICATION OF TESTS ----------------------------------------------------------------------------15

9.1.1 ROUTINE TESTS -----------------------------------------------------------------------------------------------------15

9.1.2 TYPE TESTS-----------------------------------------------------------------------------------------------------------15

9.1.3 TYPE TESTS ON ACCESSORIES -----------------------------------------------------------------------------------15

9.1.4 SPECIAL TESTS ------------------------------------------------------------------------------------------------------15

9.1.5 GENERAL STATEMENTS FOR THE TESTS ---------------------------------------------------------------------15

9.1.5.1 CRITERIA FOR ROUTINE TESTS ---------------------------------------------------------------------------------16

9.1.5.2 CRITERIA FOR TYPE AND SPECIAL TESTS --------------------------------------------------------------------17

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 5 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

9.2 TESTS DESCRIPTION --------------------------------------------------------------------------------------------------18

9.2.1 ROUTINE TESTS -----------------------------------------------------------------------------------------------------18

9.2.1.2 MEASUREMENT OF WINDING RESISTANCE ------------------------------------------------------------------18

9.2.1.3 MEASUREMENT OF VOLTAGE RATIO AND CHECK OF PHASE DISPLACEMENT ----------------------18

9.2.1.4 MEASUREMENT OF SHORT-CIRCUIT IMPEDANCE AND LOAD LOSS------------------------------------18

9.2.1.5 MEASUREMENT OF NO-LOAD LOSS AND CURRENT --------------------------------------------------------18

9.2.1.6 DIELECTRIC ROUTINE TESTS ------------------------------------------------------------------------------------18

9.2.1.7 LEAK TESTING WITH PRESSURE FOR LIQUID-IMMERSED TRANSFORMERS (TIGHTNESS TEST)
18

9.2.1.8 OIL TESTS -------------------------------------------------------------------------------------------------------------19

9.2.1.9 TEST ON DE-ENERGIZED TAP-CHANGERS --------------------------------------------------------------------19

9.2.1.10 CHECK OF THE EXTERNAL COATING ------------------------------------------------------------------------19

9.2.2 TYPE TESTS-----------------------------------------------------------------------------------------------------------19

9.2.2.2 TEMPERATURE-RISE TYPE TEST -------------------------------------------------------------------------------19

9.2.2.3 DIELECTRIC TYPE TESTS------------------------------------------------------------------------------------------19

9.2.2.4 DETERMINATION OF SOUND POWER LEVEL ----------------------------------------------------------------20

9.2.2.5 MEASUREMENT OF NO-LOAD LOSS AND CURRENT AT 90 % AND 110 % OF RATED VOLTAGE 20

9.2.3 TYPE TESTS ON ACCESSORIES -----------------------------------------------------------------------------------20

9.2.3.2 CHECK OF THE DE ENERGIZED TAP CHANGER --------------------------------------------------------------20

9.2.3.3 MECHANICAL TESTS ON WHEELS -------------------------------------------------------------------------------20

9.2.3.4 TESTS ON RATING PLATES ---------------------------------------------------------------------------------------20

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 6 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

9.2.4 SPECIAL TESTS ------------------------------------------------------------------------------------------------------20

9.2.4.2 SHORT-CIRCUIT WITHSTAND TEST ----------------------------------------------------------------------------20

9.2.4.3 MECHANICAL STRENGTH OF BRACKETS FOR FIXING TRANSFORMERS, IF REQUIRED -----------20

GUARANTEE ---------------------------------------------------------------------------------------------------------------------21

10 TRANSPORT AND PACKING -----------------------------------------------------------------------------------------21

11 OTHER LOCAL ISSUES ------------------------------------------------------------------------------------------------21

FIGURE A MV BUSHING “PLUG-IN INSIDE CONE” ----------------------------------------------------------------------22

FIGURE B LV BUSHING “BUS-BAR” ---------------------------------------------------------------------------------------23

FIGURE C LV BUSHING “BUS-BAR” INSULATING PROTECTION ----------------------------------------------------24

FIGURE D ASSEMBLY LV BUSHING “BUS-BAR” AND INSULATING PROTECTION ------------------------------25

COMMON LIST ------------------------------------------------------------------------------------------------------------------57

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 7 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

1 SCOPE
The scope of this document is to provide technical requirements for the supply of the distribution
transformers to be used in the distribution networks.

This document is applicable for liquid immersed transformer, three-phase, bi-phase and single-
phase for indoor, outdoor, pole mounted and inbox installation.
This document is composed by a main common part, three Local Section and a common list of
main requirements in order to provide full information for transformers for each relevant country.
Additional prescriptions or integration to the main common part are reported in the Local Sections
with the same corresponding clause or sub-clause number.

2 LIST OF COMPONENTS
The list of components with the main requirements, which is an integral part of the present
document, is reported in: “MV/LV Transformers reference list” (Common List) attached.

3 REFERENCE LAWS AND STANDARDS


Here below is reported the list of reference laws and standard mentioned in this document.

3.1 LAWS

3.2 INTERNATIONAL STANDARDS


• IEC 60076-1 (2011) Power transformers – Part 1: General
• IEC 60076-2 (2011) Power transformers – Part 2: Temperature rise for liquid-immersed
transformers
• IEC 60076-3 (2013) Power transformers – Part 2: Insulation levels, dielectric tests and
external clearances in air
• IEC 60076-5 (2006) Power transformers – Part 5: Ability to withstand short circuit

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 8 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

• IEC 60076-7 (2005) Power transformers – Part 7: Loading guide for oil-immersed power
transformers
• IEC 60076-10 (2001) Power transformers – Part 10: Determination of sound levels
• IEC 60214-1 Tap-Changers - Part 1: Performance requirements and test methods
• IEC 60214-2 Tap-Changers - Part 2: Application guide
• IEC 60815 Guide for the selection and dimensioning of high-voltage insulators for polluted
conditions
• IEC 60137 Insulated bushings for alternating voltages above 1 000 V
• IEC 60296 (2012) Fluids for electrotechnical applications - Unused mineral insulating oils
for transformers and switchgear
• IEC 60422 Mineral insulating oils in electrical equipment - Supervision and maintenance
guidance
• IEC 60317 Specifications for particular types of winding wires
• IEC 60085 Thermal evaluation and designation of electrical insulation
• IEC 60641-2 Pressboard and presspaper for electrical purposes - Part 2: Methods of test
• IEC 60417-2 Graphical symbols for use on equipment - Part 2: Symbol originals
• ISO 2808 Paints and varnishes – Determination of film thickness
• ISO 2409 Paints and varnishes - Cross-cut test
• ISO 2859-1 Sampling procedures for inspections by attributes
• ISO 2178 Non-magnetic coatings on magnetic substrates - Measurement of coating
thickness - Magnetic method
• ISO 4628-3 Paints and varnishes - Assessment of degree of rusting
• EN 50464-1 (2007-11) Three-phase oil-immersed distribution transformers - General
requirements
• EN 50216-4 Three-phase oil-immersed distribution transformers - Requirements and tests
concerning pressurized corrugated tanks
• EN 50180 Bushings above 1 kV up to 36 kV and from 250 A to 3,15 kA for liquid filled
transformers
• EN 50386 Bushings up to 1 kV and from 250 A to 5 kA for liquid filled transformers
• EN 50387 Busbar bushings 1 kV and from 1,25 kA to 5 kA for liquid filled transformers
• DIN 42551 Oil drain devices
and all the Standards mentioned in those listed above.
When the date of issue is not mentioned in the list above, the date to be taken as reference is that
of the standard in force when the present document has been issued.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 9 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

4 SERVICE CONDITIONS
Unless otherwise specified the normal service conditions defined in IEC 60076-1 apply with the
following exceptions:

Characteristic

Altitude (m)
Pollution level
Medium
(IEC 60815)
Seismic
Yes (1)
activity

5 RATINGS
For the definitions IEC 60076-1 applies.

5.1 TYPE OF TRANSFORMERS


This document is applicable for liquid immersed transformer, three-phase, bi-phase and single-
phase.
For further details see Common List.

5.2 NUMBER OF WINDINGS


Two.

5.3 NUMBER OF PHASES


See Common List.

5.4 COOLING SYSTEM


ONAN.

5.5 RATED POWER


See Common List.

5.6 RATED VOLTAGES


See Common List.

5.7 RATED FREQUENCY


See Common List.

5.8 VOLTAGE REGULATION


See Common List.

5.9 WINDINGS CONNECTIONS


See Common List.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 10 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

5.10 INSTALLATION
The type of installation can be indoor, outdoor, pole mounted and inbox.
Transformers are generally used for step-down voltage purpose but they can also be used as step-
up. In the network, they could occasionally be subjected to frequent energisations, overvoltages
and short-circuits.

5.11 INSULATION LEVELS


See Common List where specific rated insulation levels are defined for MV and LV side.
• Um is the highest voltage for the equipment;
• LI is the lightning impulse withstand voltage;
• AC is the short duration induced and separated source AC withstand voltage.

5.12 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS


See Common List and Local Sections.

For Italy, Romania and Spain the losses shall be in compliance with EU Regulation.
Possible capitalization criteria for further loss reductions are given in the tender, if not specified in
Local Section.

For measured losses exceed the prescribed values and/or declared by the Manufacturer, within the
tolerance admitted in 5.17, penalties will be applied.
If the losses exceed the maximum tolerance limits admitted by IEC 60076-1, the transformer is
rejected.
The calculation of the penalties to apply to the single transformer, is the following:

Lv = 2 × Cv × ∆Pv
Lj = 2 × Cj × ∆Pj

where:
Lv penalties for no-load losses excess (expressed in local currency)
Lj penalties for load losses excess (expressed in local currency)
Cv no-load losses penalties rate (expressed in local currency per kW) (1)
Cj load losses penalties rate (expressed in local currency per kW) (1)
∆Pv difference between measured no-load losses and no-load losses declared by the
Manufacturer (kW)
∆Pj difference between measured load losses and load losses declared by the Manufacturer
(kW)
(1) Values given at tender stage

5.13 TEMPERATURE RISE


See IEC 60076-1.

5.14 CAPABILITY TO WITHSTAND SHORT-CIRCUIT


Transformers shall be able to withstand the short-circuit test in compliance with IEC 60076-5.

5.15 OVERLOADING
Transformers shall withstand overloading in the conditions specified in IEC 60076-7.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 11 of 69

MV/LV TRANSFORMERS
Rev. 0
26/10/2019

5.16 OVERALL DIMENSIONS AND LAYOUT


See Common List and Local Sections.

5.17 TOLERANCES
See IEC 60076-1 and in compliance with EU Regulation for European countries.

6 DESIGN REQUIREMENTS
Unless otherwise specified, the transformers shall comply with IEC 60076-1; the single parts of the
transformers shall comply with the relevant standards.

6.1 CORE
The core shall be made wrapped type or cold rolled magnetic strips. The material shall be grain
oriented or amorphous.

6.2 WINDINGS
The windings shall be made of electrolytic copper of 99.9% purity or aluminum conductors of at
least 99.5% aluminum content; the cross section of windings shall be constant.
The star point of the LV windings shall be made on the connections of the layer or turn nearer to
the oil duct between LV and MV windings.
The enameled insulated conductors shall comply with IEC 60317.
The ties of joints and connections from the windings to the bushings or to the de-energized tap-
changer shall be manufactured in order to prevent the damaging of the conductor insulation during
transformers lifetime.
For Italy and Romania for rated power up to 160 KVA it is mandatory to manufacturer the windings
in aluminium.

6.3 TANK
The tank shall be made of steel sheets and shall not permit stagnation of water on the cover.
The tank can be provided sealed (without conservator), with full oil filling or with gas-cushion.
The coupling tank-cover shall be made by using a seal gasket, stainless steel fixing screws and
washers, and brass or hot zinc-plated nuts.
In the sealed solution, the coupling by uninterrupted welding is also acceptable.
The tank shall be provided with standing and sliding devices, and also with lifting and blocking
devices as specified in the following.
The whole tank, the cover and the accessories shall be uninterruptable connected (galvanic
contact).
The cooling system is considered an integral part of the tank.
In case of hermetically tank transformers with gas-cushion and MV inside cone plug-in
connections, specific design solutions shall be taken to assure the performance and reliability of
the transformers.

6.4 INSULATING LIQUID AND MATERIAL


The insulating liquids shall be mineral oil of the not-inhibited type, identified with the U letter,
without any anti-oxidant additive, accordingly to IEC 60296 (2012).
The oil shall not contain PCB.
It is forbidden the use of any mineral oil which presents characteristics such that to make it be
classified as dangerous substance.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 9 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

Alternatively insulating liquids can be specified in Local Sections.


Any part of the transformer which is in contact with the oil shall be compatible with it.
Oil supplier and type shall be clearly indicated in the rating plate or, alternatively, in the manual.
The maximal oil quantities for European Countries are indicated in the following table:

Transformers ≤ 160 kVA 250-400 kVA 630 kVA > 630 kVA

Max oil quantities 200 liters 400 liters 500litres 600 liters

The value given in the table are applicable with the following indications:
• For rated power > 1000kVA oil quantity higher than 600 liters can be agreed.
The solid insulation material used shall be in compliance to class “A” (105°C) of IEC 60085 or
higher. The evaluation of the material should be carried out in accordance with the IEC 60641-2.
Further specific requirements are requested in Local Sections.

6.4.1 Oil filling and sealing procedures


The filling and sealing of the transformer shall be done as stated by the Manufacturer in the
Production and Control Plan and shall be submitted to quality control.

6.5 BUSHINGS
Bushing shall be in compliance with their relevant standards.
The MV bushings shall be fixed to the tank cover by using stainless steel studs, washers and nuts
(or brass or hot galvanized steel nuts) and light metal alloy or stainless steel spacers and flanges.
Each MV and LV bushing shall be prearranged for sealing, by one drilled stud or two nuts.
Indications about bushing identifications and markings are reported in Local Sections.
The following solutions are defined for Medium Voltage and Low Voltage bushings.

6.5.1 MV Bushings

Solution MV Bushing

1 EN 50180 -- type 24-250/P3

2 EN 50180 -- type 24-250/P2

3 EN 50180 -- type 36-250/P1

4 EN 50180 inside cone plug-in [Fig. A]


EN 50180 outside cone plug-in:
5 - 24 kV interface type A
- 36 kV interface type B
6 IEC 60137 (porcelain or polymeric)

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 10 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.5.2 LV Bushings

Solution LV Bushing

1 EN 50386 - type 1)

2 EN 50386 - type 3)

3 EN 50386 - type 4)

4 EN 50386 - type 5)

5 EN 50386 - type 6)

6 Bus-bar (EN 50387) [Fig. B] without insulating protection

7 Bus-bar (EN 50387) [Fig.B] + insulating protection [Fig.C] – Assembly [Fig.D]

8 IEC 60137

6.6 DE-ENERGIZED TAP-CHANGER FOR MV VOLTAGE REGULATION


De-Energized Tap-Changer (DETC) shall be in compliance with IEC 60214.
The knob drives of the tap-changer shall have the markings turning to decreasing position by
moving in a clock-wise direction (for example: +2, +1, 0, -1, -2, …). The DETC shall be designed in
order to avoid the possibility to be set on an intermediate position between two prescribed
positions. It has to be mechanically locked only in correspondence of operating positions. The
prescribed positions are indicate in the Common List.
The position markings shall be inerasably engraved on an aluminum plate with 10 ÷ 20 mm text
size. They shall also be positioned in a way that the reading of the connected tapping shall be
possible from the low-voltage side of the transformer in operation.
A clearly visible warning label shall indicate in local language “WARNING DO NOT OPERATE
WHILE THE TRANSFORMER IS ENERGIZED”.
The knob of the DETC shall be designed for blocking in any chosen position by a padlock.
The control shaft of the tap-changer shall be made of stainless steel or suitable insulating material;
in the first case it shall be connected to earth under the cover.

6.7 DE-ENERGIZED TAP-CHANGER FOR MV VOLTAGE COMMUTATION


Transformers with two primary voltages shall be provided with an off-circuit changer for the
commutation of the MV operating voltage.
The DETC has to be operated when the transformer is disconnected from the network.
The changer has to mechanically be locked only in correspondence of the operating position.
The positions of the changer shall bear markings showing the value of the operating voltage; these
markings shall be engraved on a plate by characters 10÷20 mm in size.
A clearly visible warning label shall indicate in local language “WARNING DO NOT OPERATE
WHILE THE TRANSFORMER IS ENERGIZED”.
The knob of the DETC shall be designed for locking in both positions by a padlock.
The control shaft of the DETC shall be made of stainless steel or suitable insulating material; in the
first case the shaft shall be connected to earth under the cover.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 11 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.8 SUPPORTING AND SLIDING DEVICES


Transformers shall be provided with supporting and sliding devices.

6.9 PAINTING
The external painting of transformers and the metallic accessories made of iron materials, shall be
obtained by using epoxy or polyurethane painting cycle as indicated in the following:

Pollution level Base layer Cover layer Total thickness


(IEC 60815) (µm) (µm) (µm)

Medium ≥ 60 ≥ 60 ≥ 120

High or Very high ≥ 80 ≥ 80 ≥ 160

Extra very high ≥ 80 + 80 (1) ≥ 60 (2) ≥ 220

(1)
Base layer - Primer-epoxy with zinc: 80 µm + Epoxy-polyamide micaceous iron oxide: 80 µm
(2)
Cover layer - Polyurethane aliphatic: 60 µm

NOTE: alternatively the painting may be made by one layer of the same total thickness, also
mono component. Galvanized layers are also accepted.

Internal surfaces of the transformers shall be protected by a hot oil resistant painting (epoxy-
polyamine or equivalent), ≥ 30 µm thick.

The surfaces to be painted shall be prepared by Manufacturer practice with suitable sandblasting
or chemical cleaning (degreasing) treatments, specific for the painting cycle adopted.
The paint must be free of lead oxides or chromates. The safety and technical data sheets of the
painting shall be provided by the Manufacturer.
The color to be used is prescribed in Local Section.

The reports and tests aimed to verify the good quality and the process of the painting cycle shall be
provided by the Manufacturer.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 12 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.10 ACCESSORIES
Each transformer shall be provided with the accessories as indicate:

Accessory Totally filled transformers Gas cushion filled transformers


Lifting and blocking
X X (1)
devices
Oil drain and sampling
X X (1)
plug or valve
Thermometer pocket X X (1)

Over-pressure valve X (1)

Oil level indicator X (1)


Supports for surge
X (1) X (1)
arresters
Earthing terminals X X

Rating plate X X
Filling hole and
X X
plug (filling cap)
(1) Only if specifically required

6.10.1 Lifting and blocking devices


Transformers shall be provided with 2 (two) eyebolts for the lifting of the complete transformer of a
minimum diameter of 60mm. These two eyebolts shall be positioned in compliance with Local
Section.

Furthermore 4 (four) blocking eyebolts shall be provided in the upper part of the tank for the
blocking of transformers during transport. These four blocking eyebolts shall have a minimum
diameter of 24 mm and shall be positioned in a way that, when in use, they will not damage
accessories and cooling system.

6.10.2 Oil drain device and sampling plug or valve


Transformers shall be provided with an oil drain device and sampling plug or valve complying with:

This device shall be placed at the bottom of the tank on the left short side looking at the
transformer from the MV bushings side.

6.10.3 Thermometer pocket


Transformers shall have a thermometer pocket to allow the measuring of the top-oil temperature.
This pocket shall be placed as shown in the EN 50216-4 (type A1). The pocket shall be provided
with a corrosion-proof cap. The thread shall be protected with silicone-grease.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 13 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.10.4 Over pressure valve


The pressure relief valve shall be installed on the transformer cover and the design shall be such
that it does not permit the accumulation of dirt that could interfere in its calibration and/or operation.

6.10.5 Oil level indicator


The oil level indicator, which should be magnetic with a circular sight glass, should be located on
the upper part of the tank wall.

6.10.6 Earthing terminals


Transformers shall be provided with two stainless steel earthing terminals complying with EN
50216-4 (type 1). Only one of these terminals needs to be complete with stainless steel washer
and screw.
These terminals shall be placed at the tank bottom.
They shall be countersigned by labels, glued on the tank wall, showing the earth symbol complying
with IEC 60417-2, Symbol N. 5019.

6.11 IDENTIFICATION OF ACCESSORIES AND COMPONENTS


All components and accessories, tap changers, MV and LV bushings, sliding rollers, tank, cooling
system, etc. shall have the name or the mark of their Manufacturer.

7 EXCEPTIONS
Possible exceptions to the present prescriptions, concerning the adoption of technical and/or
manufacturing aspects different from the ones prescribed in the present GS, can be evaluated by
the Distribution company. In such a case, the Distribution company will take into account the
opportunity to require additional tests with regard to the technical/manufacturing proposed
solutions.
Such exceptions can be approved only by the Distribution company.

8 DOCUMENTATION
The Supplier, for each transformer prototype to be subjected to homologation or certification
procedure, shall make available a complete documentation containing calculations, drawings,
schemas, pictures of the MV and LV side, internal and external, descriptions, list of characteristics,
performances, assembling, maintenance and operational norms and whatever necessary for the
complete acknowledgment of the transformer.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 14 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

8.1 NOT-RESERVED DOCUMENTATION


This is the documentation issued by the Manufacturer that allows to verify, directly or indirectly, the
compliance of the transformer with the prescription of the GS. The Manufacturer authorizes the
diffusion and the reproduction of this documentation within the Distribution Companies.
It shall contain at least:
• list of all the documents (including the list of the reserved documentation);
• list of the sub-suppliers of the main components and parts;
• transportation, installation, operation and maintenance manual;
• rating plates;
• overall drawings and relevant details;
• external pictures.

In addition to the documentation above, the Manufacturer shall submit all the test reports of the
transformer, components and materials used and a document with the calculation of the capability
to withstand the short circuit (in case of the test is not performed).

The documentation shall be in English or local language, except for the rating plates and the
manuals that shall be in local language.

8.2 RESERVED DOCUMENTATION


It is the documentation considered reserved, of which the Manufacturer does not authorize the
diffusion, used to completely identify the design and the manufacturing of the transformer; it shall
include all the elements required in this GS and the documentation of the origins of the materials
not reported in “not-reserved documentation”. Such documentation will be overviewed by the
companies representatives or by the certification body during the homologation or certification and
will be archived by the Manufacturer.

8.3 TECHNICAL DOCUMENTATION


When requested, the technical documentation to be produced by the Supplier with the economical
offer shall contain the following items:
1. Description of the transformer and drawing of the overall dimensions;
2. Description of the design and main components:
• magnetic core (type of magnetic strips, , type of magnetic core, clamping mode);
• windings (type of winding, type of wire, isolations, channels of cooling);
• bushing, tap-changer, accessories, etc.;
• type of the tank;
• painting cycle.
3. detailed plan of the quality control made during the manufacturing, assembling and
commissioning

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 15 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

9 TESTS
Unless otherwise specified IEC 60076-1 applies.

9.1 LIST AND CLASSIFICATION OF TESTS

9.1.1 Routine tests


1) Check of the correspondence with the approved prototype
2) Measurement of winding resistance.
3) Measurement of voltage ratio and check of phase displacement.
4) Measurement of short-circuit impedance and load loss.
5) Measurement of no-load loss and current.
6) Dielectric routine tests (IEC 60076-3).
a. separate-source power-frequency voltage withstand test for MV and LV windings
b. induced AC withstand voltage test
c. lightning impulse test
7) Leak testing with pressure for liquid-immersed transformers (tightness test)
8) Oil tests (IEC 60422)
9) Test on de-energized tap-changers
10) Check of the external coating

9.1.2 Type tests


1) Verification of the compliance to the specification requirements
2) Temperature-rise type test (IEC 60076-2).
3) Dielectric type tests (IEC 60076-3):
a. lightning impulse test
4) Determination of sound level (IEC 60076-10).
5) Measurement of no-load loss and current at 90 % and 110 % of rated voltage.

9.1.3 Type tests on accessories


1) Tests concerning pressurized corrugated tanks
2) Check of the de-energized Tap Changer
3) Mechanical tests on wheels
4) Tests on rating plates

9.1.4 Special tests


1) Determination of capacitances windings-to-earth, and between windings
2) Short-circuit withstand test (IEC 60076-5)
3) Mechanical strength of brackets for fixing transformers, if required

9.1.5 General statements for the tests


Further tests in addition to ones listed above can be requested to the transformers manufacturer in
case of particular technologies adopted.
If not elsewhere specified, for Certification, Homologation or Approval, all the Routine tests, Type
tests and Special tests shall be performed.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 16 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

9.1.5.1 Criteria for routine tests


With reference to par. 9.1.1, the routine tests shall be performed on each transformer as
acceptance tests before delivering, with the following exceptions:
• Test 1) shall be performed on one transformer for each typology (type code);
• Tests 6).c, 8)(1) and 10) shall be carried out on a sample of transformers chosen at random
amongst those submitted to the testing from the Manufacturer, within the maximum
numbers of units stated on the sampling plan according to:
ISO 2859-1, for the double sampling plan, normal inspection AQL = 6,5%, level II.

To define the number of samples submitted to be tested for each batch of similar
transformers, reference shall be made to general inspection level II. The following table
gives an example of the sampling plan for transformer lots less than 500 units.

Lot or batch Cumulated Acceptance Rejection


size Sample Sample size sample size number number
2-8 Single 2 2 0 1
9-15 Single 3 3 0 1
First 5 5 0 2
16-25
Second 5 10 1 2
First 5 5 0 2
26-50
Second 5 10 1 2
First 8 8 0 3
51-90
Second 8 16 3 4
First 13 13 1 4
91-150
Second 13 26 4 5
First 20 20 2 5
151-280
Second 20 40 6 7
First 32 32 3 7
281-500
Second 32 64 8 9

As shown in the table, for lots greater than 15 units is prescribed a double sampling.
If the number of defectives found in the first sample is equal or less than the first
acceptance number, the lot or batch shall be considered acceptable.
If the number of defectives found in the first sample is equal or greater than the first
rejection number, the lot or batch shall be rejected.
If the number of defectives found in the first sample is between the first acceptance and
rejection numbers, the number indicated in the table of the sample size for second sample
shall be inspected.
The number of defectives found in the first and second sample shall be accumulated. If
cumulative number of defectives is equal or less than the second acceptance number the
lot, shall be considered acceptable.
If the cumulative number of defectives is equal or greater than the second rejection number,
the lot or batch shall be rejected.
The transformers resulting afflicted by defects during the test are rejected. When the non-
conformance is repaired, with Distribution Company representatives agreement, the units
can be resubmitted to the test.
(1)
NOTE: for test 8) “Oil tests”, further reduction of the transformers to be tested, up to two
oil samples for each lot, can be agreed between Distribution Company representatives

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 17 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

and Manufacturer during acceptance tests if the quality and treatments of oil are proved
by the manufacturers also by quality documentations for each lot of impregnation.

The routine tests shall be performed by the Manufacturer at the Customer inspector presence if not
otherwise agreed (the Manufacturer shall always inform the Customer in due time about the
scheduled period to give the possibility to attend or not the tests).
In case of tests performing without inspector supervision, the Manufacturer may be requested to
repeat the tests on the same sample size that shall be selected by the Customer inspector.

At the end of the testing, within the limits of the measures accuracy, no difference between the
measured values and the values registered by the Manufacturer shall be found. If the testing of
one unit is negative, the whole lot shall be rejected.

The Manufacturer shall prepare a test report containing the results of the tests.

9.1.5.2 Criteria for type and special tests


With reference to par. 9.1.2, 9.1.3 and 9.1.4, type tests and special tests shall be performed on one
unit for each set of identical transformers which have the same type code, if unless otherwise
specified in a specific document at the tender stage.

Before Type and Special tests performing, the unit shall have already passed all Routine Tests
except test 1) and 6).c.

Type test on accessories shall be performed with the following exceptions:


• test 9.1.3; 1): Tests concerning pressurized corrugated tanks shall be performed on the two
most stressed tanks of the series of the same sub-supplier.
NOTE: to identify the most stressed tanks, the ratio “oil volume in the corrugate wings/total
oil volume”, shall be calculated. The two tanks with the highest and the lowest ratios shall
be tested. The results are considered also valid for the other tanks if the calculated over
pressure at rated power do not exceeds the over pressure resulting from the two most
stressed tanks tested.
• test 9.1.3; 3): Mechanical tests on wheels shall be performed for every wheels sub-supplier;
• test 9.1.3; 4): Tests on rating plates shall be performed for every plates sub-supplier;

Special tests shall be performed with the following exceptions:


• test 9.1.4; 2): Short-circuit withstand test (IEC 60076-5) shall be performed on one
transformer for each rated power size. The test carried on such transformer will be valid for
all transformer of different rated voltages having the same rated power. The rated voltages
of the transformer under test will be selected by the Distribution Company representative n
charge of the technical approval, if not otherwise agreed.
• test 9.1.4; 3): Mechanical strength of brackets for fixing transformers, when required Local
Section shall be performed on one unit by rated power.

When permitted, in case of several transformers with same rated power and insulation level, but
different rated voltage levels, possible further reduction of tests are reported in Local Sections.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 18 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

9.2 TESTS DESCRIPTION


The accuracy of measurement during tests shall be in compliance with relevant standards. For loss
measurements the accuracy minimum requirement shall be:
• wattmeters with low power factor: class 0,5;
• instruments/instrument transformers: class 0.2.

9.2.1 ROUTINE TESTS

9.2.1.1 Check of the correspondence with the approved prototype


The ratings and the design requirements of the transformer under test (including active part of the
transformers, bushings, tap changer, accessories, etc.) shall be compared with the approved
prototype drawings.
The visual inspection shall also be performed in order to verify the absence of defects.

9.2.1.2 Measurement of winding resistance


According to IEC 60076-1 § 11.2.

9.2.1.3 Measurement of voltage ratio and check of phase displacement


According to IEC 60076-1 § 11.3.

9.2.1.4 Measurement of short-circuit impedance and load loss


According to IEC 60076-1 § 11.4.

9.2.1.5 Measurement of no-load loss and current


According to IEC 60076-1 § 11.5

9.2.1.6 Dielectric routine tests


According to IEC 60076-3. In case of two primary rated voltages with different insulation levels, the
dielectric tests shall be performed for each voltage level.
9.2.1.6.1 Separate-source power-frequency voltage withstand test for MV and LV windings
9.2.1.6.2 Induced AC withstand voltage test
9.2.1.6.3 Lightning impulse test (sample test)

9.2.1.7 Leak testing with pressure for liquid-immersed transformers (tightness test)
According to IEC 60076-1 § 11.8.
For totally filled transformers the maximum over pressure P+ (reference EN 50464-4) shall be
maintained for 8 hours. At the end of the test the transformer shall not show leakages. After the
test the pressure value shall be restored at the rated value.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 19 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

9.2.1.8 Oil tests


With reference to IEC 60422 the following parameters shall be verified:
• Water content
• Acidity
• Breakdown Voltage
• Interfacial tension
• Dielectric Dissipator Factor (DDF)

The verifications above listed shall be performed on one sample of mineral oil, for each
impregnating lot.

In case the instrumentations is available and certified in the manufacturer laboratory, the
verifications can be performed by the manufacturers itself with the attendance of Enel or
independent certification body representative, when permitted by the procedures (acceptance tests
on lots).

For the PCB absence it is mandatory to perform the verification in a laboratory accredited ILAC or
IAF in compliance with the test method of IEC 61619 with the indication of the tranformer sampled.
The detectability value of the analytic method shall be al least 2 mg/kg (2 ppm) to assure the
respect of the parameters reported in table 3 of IEC 60422.

9.2.1.9 Test on de-energized tap-changers


The correct operation of the DETC (for regulation and for commutation) shall be checked by
manually movement on the complete range of positions.

9.2.1.10 Check of the external coating


Following test shall be performed:
• Thickness: ISO 2808 or ISO 2178 “Measurement of coating thickness”
• Cross-cut test: ISO 2409

9.2.2 Type tests

9.2.2.1 Verification of the compliance to the specification requirements


The verification of compliance shall be executed through the comparison between the
characteristics and the documentation of the transformer under test stated by the Manufacturer,
and the requirements stated in the present GS (including the relevant Local Sections) concerning
the ratings and the design (accessories, painting cycles, etc.).

9.2.2.2 Temperature-rise type test


According to IEC 60076-2.

9.2.2.3 Dielectric type tests


According to IEC 60076-3.
9.2.2.3.1 Lightning impulse test

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 20 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

9.2.2.4 Determination of sound power level


According to IEC 60076-10.

9.2.2.5 Measurement of no-load loss and current at 90 % and 110 % of rated voltage
According to IEC 60076-1.

9.2.3 Type tests on accessories

9.2.3.1 Tests concerning pressurized corrugated tanks


According to EN 50464-4.

9.2.3.2 Check of the De Energized Tap Changer


According to IEC 60214-1.
Moreover the following tests shall be certificated by the DETC supplier:
• Salt fog test: in compliance with UNI ISO 9227 NSS or ASTM B 117 (1000 hours)
• UV ray test: [UV-Condenser (in QUV-Panel)]: in compliance with EN ISO 11507 Method A
or ASTM G53 (1000 hours)
• Abrasion resistance test: in compliance with ASTM D968

9.2.3.3 Mechanical tests on wheels


The mechanical characteristics specified in the Local Sections shall be verified.

9.2.3.4 Tests on rating plates


The following tests shall be certificated by the rating plate supplier:
• Salt fog test: in compliance with ISO 9227 NSS or ASTM B 117 (1000 hours)
• UV ray test: [UV-Condenser (in QUV-Panel)]: in compliance with EN ISO 11507 Method A
or ASTM G53 (1000 hours)
• Abrasion resistance test: in compliance with ASTM D968

9.2.4 Special tests

9.2.4.1 Determination of capacitances windings-to-earth, and between windings


According to IEC 60076-1.

9.2.4.2 Short-circuit withstand test


According to IEC 60076-5.

9.2.4.3 Mechanical strength of brackets for fixing transformers, if required


See Local Sections.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 21 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

GUARANTEE
The transformer guaranty is for a minimum period of 5 years, if not otherwise agreed.
Moreover the below conditions are valid for the guarantees of painting.
• during the twenty-four (24) months of the period of guarantee for faults as those described
at previous point, the Manufacturer will have to, at his own expenses, carry out all the
necessary finishing touches to eliminate possible alterations of the painted surface (blisters,
split tings of the film of paint etc.). These alterations must not, however, cover more than
5% of the entire painted surface.
• The Manufacturer must also issue a five year guarantee (starting from the date of the end
the acceptance tests with positive result). At the end of this period of guarantee, there it
must not be rust on more than 1% of the entire painted surface; this compares to a rusting
level not above the Ri3 (see ISO 4628-3).

10 TRANSPORT AND PACKING


It shall be care of the Manufacturer to provide the loading of vehicles. This applies even in case
where transports are made using vehicles belonging to Distribution Company. More information
may be given in other specific documents.
The transformers shall be delivered without any packing.

11 OTHER LOCAL ISSUES


When necessary they are specified in Local Sections.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 22 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

12 FIGURES

Spr ing washer A1 0 , 5


Nut M 1 0

Met allic sc r een


Sealing ar ea

S RATINGS

Rat ed volt age ( k V) 24


Tr asf or m er
c over Phas e t o gr ound r at ed volt age ( k V) 24/3

Rat ed f r equenc y ( Hz) 50


Rat ed A. C . wit hst and volt age ( k V) 50
Rat ed lig t ning im pulse wit hst and volt age ( k V peak) 125
Rat ed c ur rent ( A) 250
Th ic kness 2 ÷ 4 m m
Fla t ant io il gasket

Rat ed t er m al shor t t im e cur r ent ( k A) 10


Sealing sur f ac e of plug Rat ed dur at ion of t he t er m al c ur rent ( s) 1
Rat ed dynam ic c ur rent ( k A peak) 25

OPERATING C ONDITIONS
C on t ac t ar ea
Type of inst allat ion indo or
Am bient air t em per at ur e:
- m axim um ( °C ) 40
- m axim um of t he daily m ean values ( °C ) 30

- m in im um ( °C) - 25
S

m axim um alt it ude a. s. l. not spec if ied

Dielec t r ic m iner al oil


Tem per at ur e of oil:
Plug c ont a c t pin

- m axim um ( °C ) 100
Fem ale c ont a c t par t

- m axim um of daily m eam ( °C ) 90

1 - Mat er ials:
- synt het ic r esin insulat ing par t s
- c onduc t ive c opper or c opper anoy part s

2 - The f em ale c o nt a c t par t ( P) shall have pr oper dim ens y ons t o be c oupled wit h
t h e plug- in c ont ac t ( S) : it m ust has lam ellar c ont ac t s.

3 - The ac c essor ies ( V) ( sc rews, washer s and nut s) , and t he pulg- in c ont act ( S)
ar e not par t of t he bus hing.

4 - Eac h insulat or sha ll be equipped wit h a s ealing c over f or t he pr ot ec t ion


PART. 1
of t he c onic al plug- in c oupling par t .

5 - On ea c h sam ple s hall be st am ped t h e nam e or t he br and of t he m anuf ac t urer .


In addit ion, shall be st am ped t he m anu f ac t ur ing year , t he serial num ber and
t he c ode assig ned by t he m anuf ac t ur er.
PART. 1

GROOVE
3 x 3 mm

St ud bolt
Hole Ø 1 3
3

. . Gas k et
. .. . . . ..
Tr a ns f or m er
3 c ov er

Figure A MV Bushing “Plug-in inside cone”

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 23 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

SECTION A-A SECTION B-B

n° 5 holes Ø 13

part. 1

PART. HOLE ON TRANSFORMER COVER

Figure B LV Bushing “Bus-bar”

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

Figure C LV Bushing “Bus-bar” insulating protection

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

LV c a b le

C lam p

C o m p r essio n c a b le t er m ina l

In sula t in g pr o t ec t io n
Fixin g f lan g e

B u sba r b u shin g

Exa m p le o f rea liza t io n o f insu la t ed c o nn ec t io n


b et ween b usb a r b u sh in g a n d LV c a b les.

Figure D Assembly LV Bushing “Bus-bar” and insulating protection

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

In addition on what specified in the common part, the following requirements are prescribed:

3.1 INTERNATIONAL STANDARDS


ASTM - B117, D2247, D2794, D3359: Requerimientos de Pintura del transformador.
ASTM D-3487: Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus
ASTM D 297: Standard Test Methods for Rubber Products-Chemical Analysis
ASTM D 2240: Standard Test Method for Rubber Property—Durometer Hardness
ASTM D 1619: Standard Test Methods for Carbon Black—Sulfur Content
ASTM D 412: Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers-
Tension
ASTM D 471: Standard Test Method for Rubber Property-Effect of Liquids
IEC 60068: Environmental test

3.2 INSTALLATION
Mounting System
Single-Pole Double-pole Surface Level
≤ 150 >75 not used
Table A1 – Mounting system
NOTE 1: All transformers require anchoring base to be used either single-pole, double pole or
surface level and TR ≤150kVA require support.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

3.3 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS


The values for the short circuit impedance, referred to 75 ° C, shall be as shown in Table A2 with
tolerance of ± 10% that sets the standard IEC 60076-1.

Table A2 – Short circuit impedance

Rated Power Transformer Short circuit impedance, referring to 75 °C


[kVA] [%]
single-phase and double-phase
≤ 25 2÷4
Three-phase
≤ 630 4
> 630 5

3.4 OVERALL DIMENSIONS AND LAYOUT


See Common List TR MV/LV and Figure A1, A2 and A3 which define the maximum dimensions
for the length, the width (depth) and the height of transformers and the layout of the main
elements (bushings, supports, anchoring bases or wheels).

Figure A1 - Dimensions and layout of the main elements (Elevation)

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

Figure A2 - Dimensions and layout of main elements (Top)

Figure A3 - Dimension and layout of the main elements (Side)

3.5 WINDINGS
For Edelnor, rated power transformers of ≤ 100 kVA the use of aluminum is mandatory for MV
and LV winding.

3.6 TANK
In the case of transformers with a non-welded lid, the active part, which is mounted to the tank
walls, should have devices (hooks, holes, or others) that facilitate its removal and placement.
These devices should be symmetrical and guarantee lifting without horizontal movement; and
they should be different from the tank fastening supports.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

3.7 INSULATING LIQUID AND MATERIAL


Class "T" oil according to table 2 of IEC 60296. The use of paraffinic or naphthenic oil is
permitted, according to the manufacturer’s offer.
Alternatively, and only in the cases where required, silicone, mineral or vegetable oils with a high
flammability point, according to the manufacturer’s offer, may be requested.

GASKETS
Seal materials of transformers should be nitrite rubber or higher, in accordance with ASTM
D297, ASTM D2240 and ASTMD471

3.8 BUSHINGS
The MV bushing is considered the solution 6 considering porcelain or silicon rubber polymer as
IEC 60137, and may be bolted either on or under the cover, according to the manufacturer’s
offer.
The LV bushing is considered the solution 8 considering porcelain or epoxy as IEC 60137, or
porcelain insulators and terminals according to DIN42530 standard NEMA or where indicated,
see Table A3.
Capacity
[kVA]
Locking
≤75kVA
connector
Blade
>75kVA and
connector
≤150kVA
(NEMA 2)
Blade
>150kVA connector
(NEMA 4)

Table A3 - Type of low voltage terminal connectors

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

For companies exposed to an environment with pollution levels of High and Very High, epoxy
bushings should be accompanied by certificates demonstrating the good performance of this
material in this type of environment. The testing certificates to be submitted will correspond to
those defined as special tests according to IEC60068:
• Saline mist cycle – 96 hours
• Heat and humidity cycle – severity of 40ºC, 6 cycles.
• UV Rays
• Climatic sequence – method 1

Phase markings and identification


The sequence for each phase of the distribution transformer should be marked. The
identification should be engraved in high relief or bas-relief, each phase painted with a different
color.
During the draft approval stage, details for the required markings and identification will be
indicated.

3.9 DE-ENERGIZED TAP-CHANGER


The knob of the tap changer may be located on the cover or wall of the supply transformer
according to the manufacturer. The DETC must be installed in the opposite side of LV bushing
For Ampla the DETC will be located on the tank side and at the low voltage side installed to
ensure tightness. The lid switch must be fixed to the tank in order to be unmissable.

3.9.1 SUPPORTING
The position of the mounting support (on the MV or LV) for single-pole mounted transformer will
be defined by each distribution company and is also detailed in Table A4.

Position of the bracket Rated Power

Fixing bracket in the LV side ≤ 150 kVA

Table A4 – Position of the bracket

3.9.2 SLIDING DEVICES


At the base of the tanks should be placed rails or profiles which serve as fixing means and / or
allowing a minimal height over the floor during storage, according to the weight of the equipment.
See TR Common List MV / LV for wheels.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

3.9 PAINTING
The color is RAL7038.

3.10 Lifting and blocking devices


Transformer shall be provided with Two hooks located in the top part of the tank. The hooks will
allow fastening the suspension of the transformer, in such way as not to damage the bushing
insulators of the terminals and accessories and ensure the suspension of the transformer in a
horizontal position.

HOOK LIFTING OF THE ACTIVE PART


Two eyebolts or hooks designated for machine detanking shall be located: on the cover, when
the LV bushing are fixed on it, or on the structure of the active part, when the LV bushings are
fixed on the side of tank.
The eyebolts will allow fastening in such a way so as not to damage the bushing insulators of the
terminals and ensure detanking with the cover in a horizontal position.
These eyebolts will be provided with blind holes for the purpose of dissuading their use for
machine transport.
This accessory will not be requested for transformers of less than 150kVA.

3.10.1 Oil drain device and sampling plug or valve


For evacuating the insulating oil is available at the bottom of tank, flush with the bottom, a valve
gate-type one-inch diameter minimum.
Oil drain is required for the following rated power:

≥ 75 KVA

3.10.2 Thermometer pocket


Only for rated powers ≥ 150 kVA

3.10.3 Over pressure valve


For totally filled transformers this accessory will not be required.
For gas cushion transformers the over pressure valve is required for the following rated power:

3.10.4 Oil level indicator


For totally filled transformers this accessory will not be required.
For gas cushion transformers the over pressure valve is required for the following rated power:

≥ 150 KVA

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

3.10.5 Support for surge arrester


The transformer must be provided of a support (one each phase) for the installation of medium
voltage arresters. The structures may be welded or bolted to the tank or fixed by the bolt, nut
and washer of the tank-cover coupling hardware, according to manufacturer's design and
approval of the distributor. The material used for brackets, bolts, nuts and washers shall be
carbon steel hot dip galvanized.

The surge arresters are not considered in the supply.

3.10.6 Rating plates and plate-holders


Additional to data requested in IEC standard must be added:
• Level noise
• Losses
• Winding material
• Serial number
• Purchase order number
• Date of manufacture (Day, Month, Year)

3.10.9 Filling hole and plug (filling cap)


For Ampla: to allow for the completion of the leak test the transformer should have a small tube
in the top ½” internal thread and plug for nitrogen filling.
4 Criteria for type and special tests
Type tests
The selection of samples for type tests shall be two units by type of transformer. The rated
power will be on agreement with the Distribution Company.

Special Test
Short-circuit test. The sample shall be one unit by type of transformer. The rated power will be
on agreement with the Distribution Company.

NOTE. Type of transformer. Group of transformers which have the same voltage level in the
primary side and the same kind of core, wrapped type or cold rolled . Transformers with dual
voltage level on the primary side should be considered a different type.

4.1 Special tests


Test for support fixed to tank (NBR 5440).

5 TRANSPORT AND PACKING

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 24 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

The equipment should be individually packed onto treated wood or plastic pallets in a way
suitable for transport, in such a way as to avoid any damage to equipment. The packing should
be suitable for introducing equipment into standard transport industry containers. All additional
elements of the equipment should be packed into a single crate.

Transformers should be transported with their complete oil load and accessories in place. The
transformer should be completely secured in its packaging.

Wood should be treated according to international plague control requirements, avoiding


compounds dangerous to human health or the environment, such as “pentachlorophenol” and
“creosote”. The treatment should consider at least: high toxicity to xylophagous organisms, high
penetrability and staying power, chemical stability, and substances which are non-corrosive to
metals and which do not affect the physical characteristics of wood.

A visual inspection of the equipment will be carried out upon receiving it, checking for possible
damage occurred during transport and the warehousing process. In addition, the p
resence of the complementary elements should be verified (clamps, grounding bolt, fuses, etc.)
Packaging should be able to withstand the weight produced upon stacking up to 3 single-phase
and 2 three-phase transformers of normal capacity no higher than 150 kVA.

A list of the packaging brands should be submitted for the Client’s comments and final approval.
The country of manufacture should be included in the packaging information.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 38 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

Fixing support in single-pole (single-phase and two-phase transformer)


The single-phase transformers must carry two clamping backpacks, whose construction detail
shown in Figure A3.
The bottom of the tank must be isolated at least 50mm from the floor level.

Figure A7 - Fixing support of single-phase and two-phase transformer

Fixing support in single-pole (three-phase transformer up to 75 kVA)

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 39 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

Figure A8 - Fixing support in single-pole of three-phase transformer up to 75 kVA


Support bracket, this is an item that must be installed in exceptional cases where the post holes
do not match with supports of the transformer.

Anchoring base Docking (three-phase transformers up to 75kVA)


• Transformers must incorporate an anchoring base, with two U-profiles, separating the pond
bottom floor, at least at 50 mm. The design must conform to Figure A9.
• The profiles must come with holes spaced at 590mm between centers measuring at least
630mm long.

Figure A9 - Profile for anchoring base


Support for three-phase transformer greater than 75 kVA.
Anchoring base
• Transformers must incorporate an anchoring base, with two U-profiles, separating the
pond bottom floor, at least at 50 mm. The design must conform to Figure A10.
• The profiles must come with holes spaced at 590mm between centers measuring at least
630mm long.
Anchoring base three-phase transformer greater than 75 kVA.

Figure A10

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 40 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

In addition on what specified in the common part, the following requirements are prescribed:

3.1 LAWS
R.D. 337/2014 “Reglamento sobre condiciones técnicas y garantías de seguridad en
instalaciones eléctricas de alta tensión y sus Instrucciones Técnicas Complementarias ITC-RAT
01 a 23.”
R.D. 614/2001 “Disposiciones mínimas para la protección de la salud y seguridad de los
trabajadores frente al riesgo eléctrico”.
and subsequent modification/integration.

3.3 LOCAL STANDARDS


UNE 21428-1 (2011)
UNE 21428-1-1 (2011)
UNE 21428-1-2 (2011)
UNE 207019 IN (2009)
UNE 48103
and all the Standard mentioned in those listed above, in what does not contradict Commission
Regulation (EU) N. 548/2014

3.4 LIST OF REPLACED STANDARDS


Norma ENDESA FND001

3.5 OTHER RELEVANT DOCUMENTS


ENDESA Technical Specification 6700496

5.1 TYPE OF TRANSFORMERS


The transformers shall be of one of the following classes:
- Class B2 transformers: the no-load rated voltage of these transformers is 420 V phase-to-
phase.
- Class B1B2 transformers: the no-load rated voltages of these transformers are 242 V
phase-to-neutral (reduced power) and 420 V phase-to-phase (full rated power)

5.5 RATED POWER


In class B1B2 transformers, the rated power (Pr) will be that fixed for its total use at 420 V and
will have the following distribution formula:
P1/K+P2=Pr
with:
Pr = rated power of the transformer
P1 = required power for 242 V
P2 = required power for 420 V
K = 0.75 guaranteed by the manufacturer (for Pr ≤ 630 kVA)
K = 1 guaranteed by the manufacturer (for Pr = 1000 kVA)

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 50 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

5.12 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS


See MV/LV transformers reference list (common list) attached and, in what does not contradict
Commission Regulation (EU) N. 548/2014, requirements specified in:
• UNE 21428-1, chapters 3.7 and 3.8
• UNE 21428-1-1, UNE 21428-1-2 , chapters 3.5 and 3.6

6.5 BUSHINGS
Looking at the transformer from the low voltage side, the low voltage bushing are designated
from right to left, by the following symbols:

N - 2U - 2V - 2W

The symbol N corresponds to the neutral bushing.

Looking at the transformer from the high voltage side, the high voltage bushings are designated
from left to right by the following symbols:

1U - 1V - 1W

For the class B1B2 transformers, the low voltage bushing symbols are as following:

Looking at the transformer from the low voltage side, the low voltage bushings are designated
from right to left by the following symbols:

N - 2U - 2V - 2W - 3U - 3V - 3W

The symbol N corresponds to the neutral bushing


The symbols 2U, 2V and 2W correspond to the bushing at 420 V.
The symbols 3U, 3V and 3W correspond to the bushing at 242 V.

The symbols, which will be perfectly visible, must be located and marked on the tank cover
indelibly, in relief and with a minimum size of 30 mm.

The transformers (B1B2) with Type 4, Type 5 and Type 6 LV bushings will be supplied with the
corresponding flat coupling part.

6.8.1 SUPPORTING
The transformers of 50, 100 and 160 kVA will have a suspension device solidly joined (welded or
screwed) to the tank for its mounting on a pole in accordance with Figure B1:

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 51 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

NOTE – All the dimensions are in mm.


Figure B1 - Suspension device

6.8.2 SLIDING DEVICES


All transformers, except 50 and 100 kVA rated power, are equipped with wheels without flanges,
adjustable, in two perpendicular directions, for longitudinal and transversal displacements.

The dimensions of the wheels and the distances between shafts are those indicated in EN
50216-4 Standard, chapter 8.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 52 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.9 PAINTING
The color of the external painting shall be type S 8010-R90B as described in UNE 48103
Standard. The equivalent color of RAL 840-HR is RAL 5008.

6.10.3 Thermometer pocket


The thermometer will be installed at source by the manufacturer in the supply of the followings
transformers:

250 – 400 – 630 – 1000 kVA

The type and model of thermometer to be installed in these transformers is indicated in the
ENDESA Technical Specification 6700496.

6.10.6 Support for surge arrester


The transformers of 50, 100 and 160 kVA will have support for surge arresters in accordance
with the following Figure B2Errore. L'origine riferimento non è stata trovata.:

Figure B2 - Supports for surge arresters

6.10.7 Earthing terminals


These terminals shall be placed at the tank bottom on the two long sides

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 53 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.10.8 Rating plates and plate-holders


All transformers must have a rating plate, ready to be easily set at both longer sides of the
transformer and for that purpose, adequate support shall be placed.

The contents, layout, dimensions and materials shall be as indicated in the following figures:

Figure B3 - Rating plate


NOTE:
See point 3. “Product information requirements” at Commission Regulation (EU) No 548/2014
for additional fields.
• All the letters in bas and/or high relief
• Material: Stainless Steel
• Thickness: 0,8-1,2 mm
• Tolerances: ±0,5 mm

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 54 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

The field “TIPO” shall be engraved as follows:


a) a number indicating the rated power followed by the letter I indicating the hermetically
sealed liquid-immersed type.
b) a number indicating the highest voltage for the material (12, 24 or 36 kV)
The two previous numbers are separated by a slash

c) a number or numbers separated by a dash, indicating the rated primary voltages in kV. It
follows a) and b) and separated from them by a slash
d) the class (B2 or B1B2)
e) the reference to this Standard
f) Code assigned by the Manufacturer to each series of identical units, in brackets.

Example: 630I/24/9.5-16.4B1B2-GST001 r.02 (“Code assigned”)

The K factors of the dual secondary voltage transformers can be identified by plates of 105 x 40
mm, white, with the identification K = 0.75 or K = 1, in black characters with a minimum height of
30 mm, mounted on the rating plate supports.

Figure B4 – K factor plate


In order to differentiate the transformers built in accordance with this standard from the ones
before 2008, the following marking is established:

Yellow rectangular plates 105 x 40 mm, fastened to the lower part of the rating plate supports,
indicating "420 V" in black characters with a minimum height of 30 mm.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 55 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

6.10.9 Filling hole and plug


The filling cap shall be placed on the cover of the tank in the opposite side of the oil draining
device and shall be compliant with EN 50216-4, chapter 7. The shape and dimensions are
indicated in the Figure B5:

Figure B5 - Filling cap

9.1.1 Routine tests


The check of external coating shall be made in compliance with UNE 21428-1.

9.1.5.1 Criteria for routine tests


The Manufacturer shall prepare a test report, as indicated in document UNE 207019 IN,
containing the results of the tests.

9.1.5.2 Criteria for type and special tests

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 56 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

In case of several transformers with same insulation level, but different rated voltage levels, it is
possible to perform type and special test on only one transformer for each of the following
families, provided that the all transformers are made using the same technology.

• Family 1: Transformers with Um= 24 kV and rated power between 50 and 250 kVA, both
included.
• Family 2: Transformers with Um= 24 kV and rated power between 400 y 1000 kVA both
included.
• Family 3: Transformers with Um= 36 kV and rated power between 50 y 250 kVA both
included.
• Family 4: Transformers with Um= 36 kV and rated power between 400 y 1000 kVA both
included.

For other transformers, the manufacturer must demonstrate that the constructive method allows
to extend the validity of the above tests to the rest of the range or if additional testing is
required.

Copyright 2015. All rights reserved.


GLOBAL STANDARD Page 57 of 69

GST001
MV/LV TRANSFORMERS
Rev. 03
31/01/2018

COMMON LIST

MV/LV TRANSFORMERS REFERENCE LIST is attached in the following

Copyright 2015. All rights reserved.


LV MV LV Noise
MV N. of MV No Wheels Overall Brackets
Rated Insulation Minimum bushing Losses Load level - Painting Brackets
GS Rated MV Volt. Reg. (steps Rated LV insulation level phases Connection bushing type Load dimensions for
Country Code Power level f (Hz) Zsc (%) creepage type classes or Loss Sound (Yes/No) (ref. GS p. for pole
Type Code (kV) number x step %) (kV) Um/LI/AC 1P, 2P, Symbol (ref. GS p. Loss HxLxW arrester
(kVA) Um/LI/AC distance (ref. GS p. max values (W) Power 6.9) (Yes/ No)
(kV) 3P 6.5.1) (W) (mm) (Yes/ No)
(kV) (mm) 6.5.2) (dB)

GST001/801 6785304 15 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 2P Ii0 2a4 Sol. 6 480 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No

GST001/802 6785307 45 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No

GST001/803 6785299 75 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No

GST001/804 6785300 150 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No

GST001/805 6785302 300 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No

GST001/806 6785303 500 23-12 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 480 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No

GST001/807 6752137 15 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 2P Ii0 2a4 Sol. 6 350 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No

GST001/808 6776039 45 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No

GST001/809 6776050 75 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No

GST001/810 6752143 150 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No

GST001/811 6776052 300 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No

GST001/812 6752145 500 12 ±2x2,5% 0,4 17,5/95/38 1,1/-- /3 50 3P Dyn1 4 Sol. 6 350 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No

GST001/813 6776053 15 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 2P Dyn1 2a4 Sol. 6 490 Sol. 8 max. value ≤195 ≤70 48 N 1400x1300x1200 Medium Yes No

GST001/814 6752167 45 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤710 ≤180 48 N 1150x1300x1200 Medium Yes No

GST001/815 6752168 75 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤1090 ≤265 51 N 1150x1300x1200 Medium Yes No

GST001/816 6776057 150 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤1910 ≤450 55 N 1800x1600x1400 Medium No No

GST001/817 6752170 300 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤3360 ≤800 55 N 1800x1600x1400 Medium No No

GST001/818 6752171 500 23 ±2x2,5% 0,4 24/125/50 1,1/-- /3 50 3P Dyn1 4 Sol. 6 490 Sol. 8 max. value ≤6000 ≤1200 56 N 1800x1600x1400 Medium No No

Common List TR MV-LV - rev 03 - 2018-01-31 Pagina 8