Heat Transfer Simulation of A Single Channel Air
Heat Transfer Simulation of A Single Channel Air
Abstract— A Polymer Electrolyte Membrane (PEM) fuel cell is layers, and a proton conductive membrane. When the
an electrical power generator utilizing a hydrogen-based fuel hydrogen gas enters the anode electrode, it comes into contact
reactant and oxygen in a reversed electrolysis reaction, with by- with the catalyst, which splits the gas into positive ions
products of water and heat. The application is sensitive to (hydrogen protons), and electrons. The electrons travel to the
temperature; more power is generated at elevated operating cathode via an external circuit, generating electrical current.
temperatures, but excessive cell temperature causes dehydration
The protons travel through the membrane to the cathode. At
to the membrane electrolyte and subsequent power decline as
well as cell deterioration. The power-to-weight ratio and reduced the same time, oxygen is being fed to the cathode, where a
parasitic load, which are the main advantages of an air-cooled catalyst layer creates oxygen ions. When the hydrogen protons
system, pushes the research tendency to replace water cooling arrive at the cathode side, they bond with these oxygen ions,
with air cooling. This work analyzes the heat transfer creating water and heat as the by-products of the
characteristics, using analytical and Computational Fluid electrochemical reaction. Fig. 1 illustrates the fuel cell
Dynamics (CFD) tools, of a 3 kW PEM fuel cell stack which is assembly and subsequent electrochemical reaction.
equipped with a single cooling channel on each bipolar plate. The
base stack design consisting of 73 bipolar plates refers to an
industrial water-cooled PEM fuel cell stack available at the
Faculty of Mechanical Engineering, University of Technology electric circuit
MARA. From the results of the coolant flow over the base stack
design, extended surfaces (fins) was added at an optimized
geometry to enhance the heat transfer. Both designs were fuel H2 O2
subjected to a heat flux magnitude of 1.6 times greater than
heat
theoretically required, and showed excellent simulated cooling
capability of 100% cooling effectiveness when subjected to flows used fuel
recirculation air and water
at Reynolds number of 800 and above. Addition of extended vapor
cooling surfaces further improves the thermal gradient reduction
within the plate by 30%. Though still requires practical evidence,
proton gas diffusion flow field plate
the simulation analysis has provided the groundwork of air gas diffusion
electrode
electrode (anode) exchange
cooling applicability in replacing water cooling for a 3 kW PEM flow field plate membrane (cathode)
fuel cell stack.
Figure 1. PEM fuel cell components and basic operation
Keywords- PEMFC; fuel cell; cooling; simulation; CFD In order to achieve the maximum electrical power output,
cell temperature needs to be maintained at an optimal level.
I. INTRODUCTION The optimal cell temperature is mainly related to the
Polymer Electrolyte Membrane (PEM) fuel cells are the membrane properties and electrode-catalyst interface
most widely applied fuel cell system within power parameters. Works by Ahn and Choe [4], Sohn et al. [5], as
requirements of up to 100 kW. It has seen tremendous well as Yu and Jung [6] among many others, related the effect
technological growth since 1992, and can be found in of cell temperature to the fuel cell performance. Fuel cells
stationary as well as mobile applications. The few trademark generates higher power densities at elevated temperatures due
projects involving PEM fuel cell are the residential power to better electrochemical reactivity at both electrodes;
supply in Japan [1], the Honda FCX car and the Formula Zero however, the power density would soon decline as membrane
race [2], as well as in Malaysia’s own project on the backup drying occurs which leads to higher resistance to proton flow.
power system for telecommunication towers [3]. Thermal engineering in fuel cell design and operation
Fuel cells works on the principle of electrochemical reaction focuses on maintaining the cell at the allowable temperature
between two reactants. A hydrogen-rich fuel and an oxidant limit, usually referring to the membrane operating
are needed, separated by electrodes, catalyst, gas diffusion temperature. Polymer electrolyte membranes have lower
92
layer mesher and tetrahedral meshes, but polyhedral mesh is
used for the finned stack to improve the mesh quality due to
the existence of curved edges.
Outlet
Figure 2. Bipolar plate geometry without gas flow field (units in mm)
the cooling channels, and secondly, a stack enhanced with Figure 4. Fuel cell stack and cooling air region with 73 bipolar plates
extended cooling surfaces (or fins). The fin geometry in terms
of optimal fin height was acquired by analyzing the velocity Table 1 lists the boundary conditions applied to the
vectors and boundary layer thickness over the top of the stack simulation.
from the simulation results of the first case (refer section 5A
TABLE I.
for details of analysis). A total of 36 fins of 5 mm thickness SIMULATED BOUNDARY CONDITIONS
(similar to plate thickness) were constructed; 3 bipolar plates
would have two fins and a 5 mm gap between them. Fig. 3 Cooling Air
shows the stack configuration with the fins.
Properties /
Notes Values
parameters
1. Flow phase Laminar -
2. Flow source Uniform inlet -
condition
3. Inlet specifications Velocity 0.01 m/s
(practical 1 m/s
assumption) 2 m/s
3 m/s
3.5 m/s
4. Outlet specifications Pressure outlet 1 atm
5. Inlet temperature Ambient 30oC
6. Outlet temperature Ambient 30oC
7. Inlet pressure Ambient 1 atm
8. Outlet pressure Ambient 1 atm
9. Thermal Constant 0.02588 W/m.K
conductivity
10. Specific heat, Cp Constant 1005 J/kg.K
93
V. RESULTS AND DISCUSSIONS Air
Outlet
20
Plane Velocity (m/s)
15
10
0
10 20 30 40 45
Fig. 6 and Fig. 7 presents the temperature scalar scene The average stack temperature in Fig. 8 was obtained from
obtained for the standard stack and the finned stack at air the volume averaged analysis of the simulation. Higher
delivery velocity of 3.5 m/s, where the cooling effect is most nominal air velocities introduced into the stack allows the
significant. Cold regions below the required 50oC stack steady-state stack temperature to be maintained at 53oC to
temperature are concentrated at the mid-plane section and 55oC. Cooling air at 1 m/s delivery fails to have the required
extend to approximately a quarter of the stack width. cooling effect on the stack. Delivery at 2 m/s displays a
Expectedly, the hottest regions are the edge surfaces most steady-state stack temperature of 62oC, while the average stack
distant from the coolant inlet, which are surfaces not within temperature is approximately 55oC at higher air delivery
the reactive area of electrical power generation. velocities. However, it should be noted that the generated heat
At mid-plane and along the air flow path, the stack flux boundary condition was set 1.6 times higher than the
temperature difference between the inlet and exit of the anticipated practical heat flux. It is also analyzed that
cooling air is 15oC. However, higher temperature difference is increasing the air velocity from 3 m/s to 3.5 m/s does not have
registered along the vertical axis of the stack. At the inlet, the any significant effect on the stack temperature, thus the
difference from mid-plane to the top and bottom surface is optimum cooling velocity from this analysis was determined
approximately 30oC. Similarly at the exit, the difference is as 3 m/s.
23oC. This shows that variable cooling rates exists along the Theoretically, a PEM fuel cell in isothermal condition
cooling air flow path. allows a uniform electrochemical reaction over the MEA. In
practice, this condition is difficult to achieve for both air and
water cooled stacks [11]. Fig. 9 plots the simulated
temperature distribution of the stack at 15 mm planes from the
inlet and normal to the airflow. Non-uniform temperature
distribution exists for all the cooling velocities. The largest
94
thermal gradient was shown by the standard stack design at 1 only 7% difference at 3.5 m/s. The large difference at low
m/s air velocity. A significant reduction in gradient was velocity can be contributed to inaccurate estimation of the air
observed as the velocity (and Reynolds number) is doubled. At stream velocity flowing over the top surface of the stack.
3 m/s and 3.5 m/s, the thermal gradient is less than 0.1 oC/mm Enhanced flow velocity near the surface could occur at 1 m/s
increments, as analyzed in Fig. 10. It is also noted that the as the flow changes direction from a vertical flow to a
addition of fins at a similar generated heat flux lowers the horizontal flow as it passes the stack edges. The low margin of
thermal gradient by approximately 30% compared to the difference at 3 m/s and 3.5 m/s suggests that the simulation
standard stack design at a similar nominal air velocity. This results are satisfactory in accuracy.
fact proves that extended cooling surfaces are capable of
improving the stack thermal gradient due to a larger available
120
area for heat distribution.
V o l u m e A v e ra g e d S ta c k
Cooling effectiveness is a measured ratio between the 100
T em p e ra tu re ( o C )
simulated boundary heat transfers to the generated heat load of 80
the stack. It is desirable to obtain the maximum cooling 60
effectiveness. Previous works by the authors [12] has 40
analytically concluded that active cooling should provide at 20
least 90% of cooling effect for stacks generating higher than
0
one kW of thermal power. Fig. 11 plots the cooling 1 2 3 3.5 fin 3.5
effectiveness for each simulated cases and proves the
Nomina l Air Delivery Veloc ity (m/s)
capability of the single cooling channel design to effectively
dissipate the cooling load. Simulation on air inlet velocity of Figure 8. Average stack temperature
0.01 m/s acts as a reference case when the stack is assumed to
be naturally cooled by the ambient surrounding, registering 120
only 10% of the desired cooling effect. At inlet air delivery
110
velocities of 2 m/s to 3.5 m/s (Reynolds number from 800 to
S ta c k T e m p e ra tu re ( o C )
Theoretically, the stack temperature should have been Figure 9. Stack temperature distribution normal to the cooling airflow
similar for all cases with similar cooling effectiveness.
Comparing the average stack temperature and the temperature 0.4
distribution to the cooling effectiveness shows that average
L i n e a r T e m p e r a tu r e I n c r e m e n t
0.35
o v e r D i s ta n c e ( o C /m m )
than those at 3 m/s and 3.5 m/s due to the lower active cooling 0.15
0.1
rates within the cooling channels. However, external forced
0.05
convection effects on the outer surfaces, mainly on the surface 0
directly exposed to the incoming air flow increases the total 1 2 3 3.5 fin 3.5
boundary cooling effect between the stack and coolant.
Nominal Air Delivery Velocity (m/s)
Therefore, the average stack temperature was different from
Figure 10. Linear temperature increment of the stack and cooling air
one another even at similar cooling effectiveness as substantial
difference exists in internal cooling rates that directly
influence the steady-state stack temperature. 120
100
C o o l i n g E ffe c ti v e n e s s , (% )
60
Internal and external forced convection calculations were
performed using equations (1) to (4) for the standard stack 40
95
Figure 11. Cooling effectiveness of the simulated designs
REFERENCES
5000
[1] New Energy Foundation, “Residential PEFC Demonstration Project”, at
4000
www.nef.or.jp, accessed on 30th March 2009.
Cooling rate (W)
96