0% found this document useful (0 votes)
77 views28 pages

ABB-AC31 Open For The Future - e

The Advant Controller 31 from ABB is an intelligent automation system designed for flexibility and cost-efficiency in various applications, including warehousing and process automation. It features advanced programming tools compliant with IEC 61131-3, high-performance processors, and extensive communication capabilities, allowing for easy integration and configuration. The system also emphasizes safety, quality, and environmental considerations, making it suitable for a wide range of industrial applications.

Uploaded by

Khamis Alkhouli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views28 pages

ABB-AC31 Open For The Future - e

The Advant Controller 31 from ABB is an intelligent automation system designed for flexibility and cost-efficiency in various applications, including warehousing and process automation. It features advanced programming tools compliant with IEC 61131-3, high-performance processors, and extensive communication capabilities, allowing for easy integration and configuration. The system also emphasizes safety, quality, and environmental considerations, making it suitable for a wide range of industrial applications.

Uploaded by

Khamis Alkhouli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

Automation System Advant Controller 31

Open for the Future!


Open for the Future! Advant Controller 31

The key to intelligent automation solutions

Future-oriented technologies necessitate intelligent solutions based The emphasis is also on continuity in systems
on systems which can be used flexibly. Cutting your engineering engineering, as on the Advant ® Controller 31
costs will be more and more important in the future. It will be equally automation system from ABB. Thus, the
as important to assess a future-oriented system on the basis of the time-proven programmable controllers of the
aspects of handling, reliability and ease of servicing. AC31 family are becoming more and more
powerful and even more flexible in use. The
This is exactly why engineering tools are becoming more and more new high-performance units are an integral
important. Standardised software packages, e.g. to IEC 61131-3, part of the AC31 equipment family and
point the way to an open automation structure. existing know-how forms the basis for use
of the new technology.

For warehousing

For process automation

At pumping stations

2
The time-proven system structure has been The new 907 AC 1131 programming software makes available a
retained and additional functionalities have selection of five different, standardised configuration interfaces.
been added. These include, for instance, ad- Extensive Online Help and integrated visualisation allow time-opti-
ditional, cross-system communication levels. mised configuration and commissioning of the automation task.

New processors and a multi-tasking


operating system ensure that even more
stringent requirements applicable to future
automation tasks can be solved optimally.

At waste water treatment plants

In power generation

3
Open for the future!

Configuration – the key to cost-cutting

The requirements made of automation on modern, modular-design Programming to IEC 61131-3


machinery and systems are changing ever-faster. Future-oriented
automation concepts demand solutions which stimulate technical The open, manufacturer-independent pro-
progress. gramming standard to IEC 61131-3 for
automation has been implemented in the
Selection of a user-friendly, convenient programming software 907 AC 1131 programming software. You
package is of foremost importance in configuring, programming, can thus choose what configuration inter-
testing and commissioning an automation application. face you wish to use when writing your
application:
The programming tool 907 AC 1131 from ABB utilises all advantages
of the virtually intuitive and familiar Windows 95/98/NT GUI. This • Ladder Diagram
means that you can quite simply forget long familiarisation times when • Instruction List
learning how to use a new software package. • Function Block Diagram
• Sequential Function Chart
• Structured Text

All users, be they plant electricians or com-


puter scientists, thus have a configuration
interface in which they can feel at home.

Programming languages to IEC 61131-3

4
Extended functionalities Other functions, such as:
• Breakpoints,
Conversions allow a change of display modes. • Single-Step mode,
Integrated Online Help supports you should • Single-Cycle mode and
you not have your documentation at hand • Sampling-Trace
occasionally. But even when writing the pro- are integrated in 907 AC 1131.
gram, you can choose whether you wish to
use the standard functions of IEC 61131-3 Offline simulation of the IEC 61131-3 functions allows you to run a
(standard library) or the time-proven, familiar preliminary test even without a programmable controller connected.
functionalities of the ABB library. Finally, you The integrated visualisation system as well can provide you with
are free to choose whether you wish to write valuable assistance in implementing your project. This provides a
your own additional library with your specific practical cut in the planner’s or commissioner’s workload during the
functions. And, even then, you can choose start-up phase of commissioning.
your favourite programming interface.
Networked programmable controllers in the ARCNET network can
Detailed and extensive diagnostic and Help be chosen, programmed and tested directly from the software. A
functions reduce your testing and commis- ready-integrated configuration tool for Profibus-DP also rounds off
sioning effort. A Status function with Snap- the range of functionalities provided by the 907 AC 1131 configu-
shot option, and both overwriting and forc- ration software package.
ing variables are other functionalities which
you will be familiar with, which you expect
and which are offered by the 907 AC 1131
software package

Sampling-Trace

Menu-driven program development

Integrated process visualisation

5
Open for the future!

The CPUs – the key to flexibility

The applications in automation are as different as the tasks are Distributed automation tasks in particular
diverse. Flexible systems with a high performance potential meet can be implemented particularly easily
these requirements. The ABB system Advant Controller 31 with its thanks to the integrated system bus inter-
open system structure and its high performance helps you to apply faces. This means that the I/O devices are
your know-how optimally for solving your automation problem. handled on the system bus as if they were
an integral element of a central control sys-
Integration tem, regardless of whether the I/O device is
installed 10 mm or 500 m (2 km with repeater)
The new, powerful programmable controllers can be used to op- away from the Master system.
timum effect both in the field of mechanical engineering and in the
field of plant construction. Regardless of whether there are only a “Simple but offering diverse capabilities” –
few I/O signals or whether the signal scope covers a few hundred these are the requirements applicable to an
or a thousand inputs/out-puts, Advant Controller 31 can be inte- automation system.
grated easily in your auto-mation solution. It is irrelevant to the CPUs ABB’s Advant Controller 31 is designed to
whether they are used as stand-alone units, as Master or as Slave. provide you as the user with optimum assist-
ance in solving your automation tasks owing
to its high flexibility and easy-to-master sys-
tem structure. Moreover, you have the option
of selecting from diverse expansion variants.

Flexibility
One device for all applications

Stand-alone
Communication/field bus

Master I/O I/O Slave

CS31 system bus


Master I/O I/O

Master I/O

6
Regardless of whether tightly packed or Well-conceived functionality
finely graded, expansible I/O bus modules
meet your requirement profile, Advant Future-oriented automation systems should make available maxi-
Controller 31 makes both techniques avail- mum self-diagnosis capability to the user. The systems engineering
able to you. The configurable digital and of Advant Controller 31 offers automatic diagnosis of the CPU,
analogue input/output devices offer you system bus and connected I/O devices. Optional diagnostic func-
particularly high flexibility for this. tions, such as discontinuity, short-circuit and overload, can be
polled as required.
It is just as easy to make modifications to
the system. Bus modules can be ex- All modules of the AC31 system feature excellent ease of installation.
changed without having to disconnect the The compact plastic housings can be snapped easily onto a 35 mm
power supply or interrupt bus operation. DIN rail or attached to a mounting plate using screws.
Even if the system is expanded, all that
needs to be done is to simply extend the
bus for connection of further bus modules.
Bus modules added are detected automat-
ically by the system, and the components
are uniquely identified to the system bus
and addressed by the system bus via the
module address. The setting is made, inde-
pendently of the module type used, either
using an address switch on the I/O devices
or via system constants on the programmable
controllers. This allows the I/O devices to be
addressed directly from the user program.
There is no additional effort for bus config-
uration.

The compatible devices of Series 40...50

I/O Slave

7
Open for the future!

Communication – the key to understanding

The CS31 system bus forms the basis for communication of ABB’s RCOM is a communication medium de-
AC31 intelligent automation system. It establishes the link between signed for data teletransmission. It can be
the CPUs and the I/O devices. The CS31 system bus is an RS 485 used for transmission on dedicated lines or
two-wire bus designed for interference immunity and fast data trans- dial-up lines. Commercially available modems
mission. Up to 31 bus devices can be integrated on the system bus. establish the link to the transmission media.

MODBUS offers interfacing capabilities to programmable control- Profibus-DP allows Master and Slave com-
lers of various manufacturers, to operator-control terminals and to munication in the field area. The open sys-
PC operator workstations owing to its high popularity. tem structure of Advant Controller 31 ensures
interfacing with automation systems of other
manufactures and with intelligent front-end
processing devices such as drives, actuators,
operator terminals and sensor systems.

Diverse/Entry-level Communicative Fast


07 KT 95/07 KT 96 07 KT 97 07 KT 98
Coupler Master Station Coupler Master Station Coupler Master Station

8 * in preparation
ARCNET – known an easy-to-handle, low- AF100 is the communication interfacing facility to ABB control and
cost communication bus system – forms the instrumentation systems. This communication variant allows you to
basis for high-speed networking of AC31 implement a system structure from the master control system through
programmable controllers and for SCADA to intelligent automation systems in the field area.
systems, connection of systems made by
other manufactures and interworking with
the PC in the Advant Controller 31 system.

With integrated DeviceNet coupler for fast


data exchange in the field area. For the coup-
ling of distributed field devices like I/Os,
drives and valves

Open Operator AC31 AC31 input/


07 SL 97 terminals Series 40...50 output devices

*1 CS31-
Systembus

MODBUS

RCOM

Profibus DP

ARCNET

DeviceNet

AF100

* 1 via bus coupler 9


Open for the future!

Visualisation and operation – the key to transparency

Optimum process control does not end at the interfaces of a pro- an extensive array of such products. The
grammable controller. After all, cost-cutting on the end products range extends from low-cost, two-line display
will, in future, necessitate transparent processes to an ever-increasing units through to convenient, graphics-capable
extent. Convenient operation – even on a small machine – used operator terminals.
correctly, affords advantages in machine utilisation. Thus, for in-
stance, it is possible to diagnose and visualise preventive mainte- In simple cases, the integrated serial ports
nance. Fast fault detection and logging also reduce any machine can be used for connection to your pro-
downtimes. grammable controllers. In networked auto-
mation applications, you are free to utilise
Operating panels the full flexibility of the communication
options.
Depending on the requirements applicable to the process to be
operated, products designed in line with the automation task will be The operating panels provide the following
required. This necessitates solution components graded in the communication levels as options:
various performance classes. The product range provides you with • MODBUS
• ARCNET
• Profibus DP.

The operating panels


in the AC31 system

10
Process visualisation Additional network capabilities, remote connection functions and
standard interfaces turn modern visualisation packages into open
In future, it will be necessary to automate and integration-capable systems for all future-oriented automation
complex processes intelligently and trans- solutions.
parently and visualise them in line with re-
quirements to an increasing extent. The ABB A SCADA system and master control computer software package
Advant Controller 31 system, in conjunction provides you with a tool which does not force you to stop the
with a flexible and open SCADA system, can running process in the event of changes in visualisation and
also meet these future requirements. operation. You always remain online when doing this. And, as
Integrating an automation system with related already outlined with the operatoing panels, it becomes an open
visualisation in an overall process necessitates element of your automation solution thanks to the diverse
a high degree of openness of the communi- integration capabilities.
cation channels. A convenient GUI, integra- In the simplest case, integration is performed using the integrated
ted archiving and logging functions and trend serial ports, but can also be performed via:
displays in real-time are the basic precondi- • MODBUS
tions for this type of process control. • ARCNET

Process visualisation

11
Open for the future!

The advantages – the key to your success

ABB’s system Advant Controller 31 stands for modern, future-oriented • Peripheral devices with high packing
automation engineering. The transparency in systems engineering is density or as a finely graded, expansible
reflected in the ease of handling of the devices and in uncomplicated variant provide maximum possible flexibil-
configuration. This is achieved by the fact that ABB makes sure that ity. This is assisted, not least, by the digital
it does not ignore aspects which have proven successful even when and analogue input/output devices with
further-developing the system philosophy. Your AC31 advantages at freely selectable and configurable signal
a glance: specifications.

• Powerful processors and highly flexible I/O technology allow the • Advant Controller 31 provides powerful
new programmable controllers to be used in virtually any and system-open communication levels
application. for integration in overall processes.

• The configuration tool, developed in accordance with IEC 61131-3, • Diverse transmission media – conventional
with its extensive functionalities reduces configuration effort over copper, convenient and particularly reli-
and over again. able fibre-optics or modem – ensure that
you can make the right choice for any
• The CS31 system bus, a system which has proven successful for requirement.
many years now, guarantees optimum and reliable integration of
local intelligence and peripheral devices. • Advant Controller 31 even allows
redundant bus topologies.
• Bus repeaters make it possible to span even large distances. An
additional, redundant or ring structure enhances reliability of the • A broad range of devices for display, oper-
transmission medium. ation and process visualisation, such as
the Wizcon visualisation package, opens
up new roads into the future.

Advant Controller 31 approvals

Lloyd’s
Register Of
Shipping

CSA, Canada UL, USA GL, Germany DNV, Norway BV, France RINa, Italy LRS, Great Britain

12
On the safe side Quality and the environment

The safety-related Advant Controller 31-S Quality is the supreme principle of the Advant Controller 31. A
automation system, certified by the German certified quality management system to DIN ISO 9001 creates
Technical Inspection Authority (TÜV), is avail- an important basis for this:
able for safety-related applications. It is based
on the time-proven system structure of the “Our thinking and actions are aimed at meeting the needs and
“classic” AC31 variant. Internally redundant wishes of our customers. Our customers decide on the quality of
I/O devices, developed specifically for safety- our products and services. It is they who assess the quality”.
related applications, communicate via the (Excerpt from: ABB Quality Manual)
AC31 Safety Field Bus with the safety-re-
lated CPU. Extending AC31-S with standard Ambitious goals for ongoing improvement of all business processes
AC31 I/O devices on the same field bus are defined within the framework of the Total Quality System Review
allows low-cost conversion of operating and which is conducted at ABB STOTZ-KONTAKT GmbH at regular
safety functions in one CPU. AC31-S is ap- intervals.
proved for safety-applications up to require-
ment class 4 and machine category 3. The environmental impact of a product is determined very essentially
by the design targets. Consequently, special attention is paid to
Numerous approvals for AC31 allow export gentle use of resources, avoidance of problematic materials, recycl-
of components and systems through to able design and longevity of products as early as the stage at which
machines and installations. Even applications the Performance Specifications are elaborated.
in the marine and shipbuilding sector are
approved fields of application for the reliable
technology of Advant Controller 31.

13
14
Advant Controller 31

Summary

Technical features

Programmable controllers 16

General system data 18

Ordering information
Programmable controllers 19
Input/output devices 20
Communication 21
Operating panels 22
Accessories 25
Programming and documentation 25

Technical data
Dimensions 26

15
CPUs

AC31

Details 07 CT/CR 41 07 KT/KR 51 07 KT 95

CS31 system bus No Yes Yes


Program memory
Size 32 kByte 32 kByte 480 kByte
Memory Flash EPROM and RAM Flash EPROM and RAM Flash EPROM and RAM
Plug-in memory Smart Media Card
(Flash, 2 MByte).
For data storage and
and for the reload of
controller-program
Power Supply 24V DC/230V AC 24V DC/230V AC 24V DC
Dimensions (W x H x D) in mm 120x93x84 120x93x84 240x140x85
Serial Ports 1 1 2
Number of inputs and outputs
Integrated DI/DO 8 DI and 6 DO 8 DI and 6 DO 12 DI and 8 DO
DI/DO maximum 110 overall >1000 overall 1012 overall
Integrated AI/AO - - 4 AI and 2 AO
AI/AO maximum 48 AI/12 AO 544 AI/136 AO 228 AI/226 AO
Data puffering (selectable) Replaceable battery Replaceable battery Replaceable battery
Real-time clock Yes Yes Yes
Programming system 907 AC 1131 907 AC 1131 907 AC 1131
Programming interface COM 1 COM 1 COM 1 or COM 2

Program execution time and priority driven time and priority driven time and priority driven
tasks tasks tasks
Subroutines any any any
User program protection Password Password Password
Addressable range
Flags (Bit) 2016 2016 8192
Words (16 Bit) 2016 2016 8192
Double Words (32 Bit) 64 64 1024
Globale und local variables - - 256 kB
Timers Unlimited Unlimited Unlimited
Counters Unlimited Unlimited Unlimited
High-Speed Counters (digital in- 1 (7kHz) or 2 (7kHz) with 1 (7kHz) or 2 (7kHz) with 1 to 2 (different operating modes,
and outputs used as counter inputs) sensor-input sensor-input max. 50 kHz)
Special functions Protocols: Protocols: Protocols such as
MODBUS, MODBUS, MODBUS,
Controllers Controllers RCOM, AF100
ASCII-communication ASCII-communication PI und PID Controllers
32 Bit arithmetic

Connections Detachable terminal blocks Detachable terminal blocks Detachable terminal blocks
with screw-type terminals with screw-type terminals with screw-type terminals
or snap-on clamps or snap-on clamps
Mounting With and without top-hat rail With and without top-hat rail With and without top-hat rail

16
07 KT 96 07 KT 97 07 SL 97 07 KT 98

Yes Yes Yes Yes

480 kByte 480 kByte 480 kByte 1000 kByte


Flash EPROM and RAM Flash EPROM and RAM Flash EPROM und RAM Flash EPROM und RAM
Smart Media Card Smart Media Card Smar t Media Card (Flash) Smart Media Card (Flash)
(Flash, 2 MByte) (Flash, 2 MByte) For data storage and For data storage and
For data storage and For data storage and and for the reload of and for the reload of
and for the reload of and for the reload of controller-program controller-program
controller-program controller-program
24V DC 24V DC 24V DC 24V DC
240x140x85 240x140x85 Fullsize PCI-Karte 240x140x85
2 2 1 2

24 DI and 16 DO 24 DI, 16 DO and 8 DC - 24 DI, 16 DO und 8 DC


1032 overall 1024 overall 992 overall 1040 overall
- 8 AI and 4 AO - 8 AI und 4 AO
224 AI/224 AO 232 AI/228 AO 224 AI/224 AO 232 AI/224 AO
Replaceable battery Replaceable battery Replaceable battery Replaceable battery
Yes Yes Yes Yes
907 AC 1131 907 AC 1131 907 AC 1131 907 AC 1131
COM 1 or COM 2 COM 1 or COM 2 COM 1 COM 1/2
or optional ARCNET or ARCNET or ARCNET
time and priority driven time and priority driven time and priority driven time and priority driven
tasks tasks tasks tasks
any any any any
Password Password Password Password

8192 8192 8192 8192


8192 8192 8192 8192
1024 1024 1024 1024
256 kB 256 kB 256 kB 1 MB
Unlimited Unlimited Unlimited Unlimited
Unlimited Unlimited Unlimited Unlimited
1 to 2 (different operating modes, 1 to 2 (different operating modes, 1 to 2 (different operating modes,
max. 50 kHz) max. 50 kHz) max. 50 kHz)
Protocols: Protocols: Protocols: Protocols:
MODBUS, MODBUS ARCNET, integrated MODBUS , ARCNET, MODBUS, AF100*
RCOM, AF100 RCOM andAF100, Profibus DP Profibus DP or DeviceNet as PI- and PID-Controller
PI and PID Controller and ARCNET, opt. KP, PI- and PID-Controller, 32 Bit arithmetic,
32 Bit arithmetic PI and PID Controller 32 Bit arithmetic, ASCII- ASCII-communication
32 Bit arithmetic communication Floating point arithmetic
*in preparation
Detachable terminal blocks Detachable terminal blocks Detachable terminal blocks
with screw-type terminals with screw-type terminals with screw-type terminals

With and without top-hat rail With and without top-hat rail in the PCI-Slot (fullsize) With and without top-hat rail

17
AC31 – Technical Features

General system data


Operating conditions Operating temperature 0 ºC to + 55 ºC
Storage temperature – 25 ºC to + 75 ºC
Transport temperature – 25 ºC to + 75 ºC
Relative humidity, no condensation 50...95%
Atmospheric pressure, operation ≥ 800 hPa ≥ 2000m

Mechanical data Enclosure IP 20


Housing to UL 94
Vibration resistance to IEC 68-2-6: 1g (Series 40/50), 4g (Series 90)
Shock resistance to IEC 68-2-27
Power supply 24 V DC 19.2 … 30 V DC (– 15 % … + 20 %)
Air gaps and creepage distances IEC 664 und DIN VDE 0160
Insulation test IEC 1131-2

Electromagnetic compatibility Electrostatic discharge IEC 1000-4-2 (Level 3)


Radiated electromagnetic fields
Immunity tests IEC 1000-4-3 (Level 3)
Transient noise voltages (burst) IEC 1000-4-4
Capacitance immunity IEC 1000-4-5
Radio-frequency noise power IEC 1000-4-6

Bus system

CS31 field bus

RS232

Communication Serial
Interface specifications RS 485 (shielded twisted pair)
Transmission speed 187.5 kbaud
Protocol CS31 (Master Slave)
Transmission integrity check CRC8
Number of AC31 devices on the bus 31 max.
Maximum length 500 m or 2000 m (with repeaters)
Bus redundancy with bus repeater
Refresh time 2 ms min. oder 12 ms typical for 31 AC31 I/O devices on the bus

18
Programmable Controllers
Ordering Data
Programmable Contollers Series 40
Expansible with 6 I/O devices, up to 110 I/O
Digital inputs 24 V DC - Digital outputs relay 250 V AC, 2 A / transistor 24 V DC, 0,5 A
serial port RS232 for programing and communication ASCII, MODBUS

Integrated Integrated Program memory Supply- Type Order No. Weight


inputs outputs online changes voltage kg
with without
8 digital 6 relay 16 kb 32 kb 24 V DC 07 CR 41 1SBP 26 0020 R 1001 0,355
8 digital 6 relay 16 kb 32 kb 120/ 230 V AC 07 CR 41 1SBP 26 0021 R 1001 0,800
07 CR 41 8 digital 6 transistor 16 kb 32 kb 24 V DC 07 CT 41 1SBP 26 0022 R 1001 0,355

Programmable Contollers Series 50


Expansible with 6 I/O devices, distributed expansibility up to approx. 1000 I/O, integrated CS31 bus
Digital inputs 24 V DC - Digital outputs relay 250 V AC, 2 A / transistor 24 V DC, 0,5 A
serial port RS232 or RS485 for programming and communication ASCII, MODBUS
real-time clock

Integrated Integrated Program memory Supply- Type Order No. Weight


inputs outputs online changes voltage kg
with without

8 digital 6 relay 16 kb 32 kb 24 V DC 07 KR 51 1SBP 26 0010 R 1001 0,355


8 digital 6 relay 16 kb 32 kb 120/ 230 V AC 07 KR 51 1SBP 26 0011 R 1001 0,800
07 KR 51
8 digital 6 transistor 16 kb 32 kb 24 V DC 07 KT 51 1SBP 26 0012 R 1001 0,355

Programmable Controllers Series 90


Distributed expansibility up to approx. 1000 I/O, with RAM and FLASH-EPROM
real-time clock, interface to CS31 field bus, online program modification, bit and word processing, electrically isolated;
digital inputs 24 V DC, digital outputs transistor (T) 24 V DC, 0,5 A; analogue inputs, resolution 12 Bit
0...10 V, 0...5 V and 0...20 mA on 07 KT 95, +/- 10 V, 0...20 mA, 4...20 mA, +/-5 V, -50 °C...+400 °C and -30 °C...+70 °C on
07 KT 97/98 (can also be used as digital I/O);
analogue outputs, resolution12 Bit, +/-10 V on 07 KT 95,
+/-10 V, 0...20 mA and 4...20 mA on 07 KT 97/98 (I/O number 07 KT 98 identical with 07 KT 97).
Power Supply 24 V DC. 2 serial ports, both configurable for programming

07 KT 97 Integrated Integrated Counter Pr ogram Type Order No. Weight


inputs outputs inputs memory kg

12 DI, 4 AI 8 DO, T, 2 AO 2 480 kB 07 KT 95 GJR 525 2800 R 0100 1,3


24 DI 16 DO, T 2 480 kB 07 KT 96 GJR 525 2900 R 0100 1,3
24 DI, 8 DC, 8 AI 16 DO, T, 4 AO 2 480 kB 07 KT 97 GJR 525 3000 R 0100 1,3

Programmable Controllers Series 90 with integrated communication processors


Description Type Order No. Weight, kg

07 KT 97 with ARCNET networking 07 KT 97-ARCNET GJR 525 3000 R 0160 1,3


07 KT 97 with Profibus DP 07 KT 97-Profibus GJR 525 3000 R 0120 1,3
07 KT 98 07 KT 97 with ARCNET and Profibus DP 07 KT 97-ARCNET-Profibus GJR 525 3000 R 0162 1,3
07 KT 98 with ARCNET 07 KT 98-ARCNET GJR 525 3100 R 0160 1,3

Programmable Contoller as PC-Card (PCI fullsize)


distributed expanibility up to approx. 1000 I/O, with RAM and FLASH-EPROM, real-time clock, interface to CS31 field
bus, online program modification, bit and word processing, own power supply 24 V DC, 1 serial port, configurable for
programming/communication, integrated ARCNET connection, PC operating system Windows NT. Optional Smar t
Media Card for data storage and backup of user defined controller program (ref. accessories).
Description Program memory Type Order No. Weight, kg

07 SL 97 with ARCNET networking 480 kB 07 SL 97-ARCNET GJR 525 3400 R 0160 1,0
07 SL 97 with ARCNET and Profibus DP 480 kB 07 SL 97-ARCNET-Profibus GJR 525 3400 R 0162 1,0
07 SL 97 07 KT 97 with ARCNET and DeviceNet 480 kB 07 SL 97-ARCNET-DeviceNet GJR 525 3400 R 0165 1,0

19
Input/output devices
Ordering data
Expansible digital I/O bus modules (for Series 50 and 90)
Expansible with 6 I/O devices, up to approx. 100 I/O, (6 digital or 4 digital and 2 analogue)
Digital inputs 24 V DC - digital outputs relay 250 V AC, 2 A / transistor 24 V DC, 0.5 A
Integrated CS31 bus connection

Integrated Integrated Supply Type Order No. Weight


inputs outputs voltage kg

8 digital 6 relay 24 V DC ICMK 14 F1 1SBP 26 0050 R1001 0,355


8 digital 6 relay 120/ 230 V AC ICMK 14 F1 1SBP 26 0051 R1001 0,800
8 digital 6 transistor 24 V DC ICMK 14 N1 1SBP 26 0052 R1001 0,355
ICMK 14 F1

Digital I/O devices (for programmable controllers Series 40, 50 und I/O bus modules)
Power supply via programmable controllers and I/O bus modules

Integrated Type Order No. Weight


inputs and outputs kg

16 inputs 24 V DC XI 16 E1 1SBP 26 0100 R1001 0,220


16 outputs 24 V DC, 0.5 A transistor XO 16 N1 1SBP 26 0105 R1001 0,220
8 outputs 250 V AC, 2 A relay XO 08 R1 1SBP 26 0101 R1001 0,220
8 configurable inputs/outputs 24 V DC – 24 V DC, 0.5 A XC 08 L1 1SBP 26 0102 R1001 0,220
XI 16 E1
4 inputs 24 V DC and 4 outputs 250 V AC, 2 A relay XK 08 F1 1SBP 26 0104 R1001 0,220

Analogue I/O devices (for programmable controllers Series 40, 50 and I/O bus modules)
Power supply via programmable controllers and I/O bus modules

Integrated Type Order No. Weight


inputs and outputs kg
4 inputs, -/+ 10 V, -/+ 20 mA, 4…20 mA, Pt100, Pt1000 XM 06 B5 1SBP 26 0103 R1001 0,220
2 outputs, -/+ 10 V, 0… 20 mA, 4…20 mA
8 inputs, -/+ 10 V, -/+ 20 mA, 4…20 mA, Pt100, Pt1000 XE 08 B5 1SBP 26 0106 R1001 0,220
XM 06 B5

Distributed digital I/O devices (for Series 50 und 90)


Supply voltage 24 V DC, integrated CS31 bus connection

Integrated Type Order No. Weight


inputs and outputs kg

32 inputs 24 V DC 07 DI 92 GJR 525 2400 R0101 0,450


16 inputs, 8 outputs, 8 configurable inputs/outputs, 24 V DC, 0.5 A 07 DC 91 GJR 525 1400 R0202 0,450
32 configurable inputs/outputs 24 V DC, 0.5 A 07 DC 92 GJR 525 2200 R0101 0,450
07 DC 92

Distributed analogue I/O devices (for Series 50 und 90)


Supply voltage 24 V DC, integrated CS31 bus connection

Integrated Type Order No. Weight


inputs and outputs kg

8 inputs 12-bit, -/+ 50 mV, -/+ 500 mV, -/+ 10 V, 0…20 mA, 07 AI 91 GJR 525 1600 R0202 0,450
4…20 mA, Pt100, Pt1000, thermocouple
16 configurable channels as input and output 07 AC 91 GJR 525 2300 R0101 0,450
1.) 16 channels can be set in pairs 0…10 V, 0…20 mA, 4…20 mA, 8-bit
2.) 8 inputs and 8 outputs, -/+ 10 V, 0…20 mA, 4…20 mA, 12-bit

07 AC 91

20
Input/output devices, communication
Ordering data
Distributed digital I/O devices (for Series 50 and 90) IP 67
Supply voltage 24 V DC, integrated CS31 bus connection

Integrated inputs and outputs Type Order No. Weight


kg
16 inputs 24 V DC 07 DI 93-I GJV 307 5613 R 0202 0,470
8 outputs 24 V DC, 2 A transistor 07 DO 93-I GJV 307 5611 R 0202 0,470
8 inputs and 4 outputs 24 V DC, 2 A transistor 07 DK 93-I GJV 307 5623 R 0202 0,470

07 DO 93-I
Communication processors, Series 90
Description Supply *) Type Order No. Weight
voltage kg
RCOM+ and RCOM protocol, Master/Slave for 24 V DC 07 KP 90 GJR 525 1000 R 0303 0,450
dedicated line and dial-up connection A
MODBUS protocol, 2 communication channels, 24 V DC 07 KP 93 GJR 525 3200 R 1161 0,450
Master and Slave operation
Interfaces RS232/422/485
AF100 24 V DC 07 KP 99 in preparation 0,450
07 KP 90
*) A Special communication software required

21
Operating panels
Ordering data
Operating panels ability class text
Lines/ Characters/ Display- Fkt.-/alpha- Device driver/ Type Order No. Weight
Width height type and system interface per piece
(mm) (mm) keys/softkeys kg
2/82,5 20/18 LCD 4/8/- upload/RS232 MT30 GATS 111 100 R 0001 0,45
8/71 20/40 LCD 8/23/- upload/RS232 MT45*) GATS 110 091 R 1001 0,45
8/71 20/40 LCD 8/23/- upload/RS485 MT45*) GATS 110 091 R 1201 0,45
8/71 20/40 LCD 8/23/- upload/ARCNET MT45*) GATS 110 091 R 1401 0,45
*) MT45 is identical to MT40 as far as hardware and projecting are concerned

MT 45

Operating panels ability class graphics

Lines/ Characters/ Display- Fkt.-/alpha- Device driver/ Type Order No. Weight
width height type and system- interface per piece
(mm) (mm) keys/softkeys kg
8/240 40/64 LCD 16/23/8 upload/RS232 MT65*) GATS 110 092 R 1001 0,75
8/240 40/64 LCD 16/23/8 upload/RS485 MT65*) GATS 110 092 R 1201 0,75
8/240 40/64 LCD 16/23/8 upload/ARCNET MT65*) GATS 110 092 R 1401 0,75
—/120 —/64 VFD 16/23/8 upload/RS232 MT91 GATS 110 167 R 0001 0,75
—/120 —/64 VFD 16/23/8 upload/RS485 MT91 GATS 110 167 R 0201 0,75
MT 91
—/120 —/64 VFD 16/23/8 upload/ARCNET MT91 GATS 110 167 R 0401 0,75
*) MT65 is identical to MT60 as far as hardware and projecting are concerned

22
Operating panels
Ordering data

Programming cable
Operating panel Type Order No. Weight
per piece
kg

MT30/45/65/91 VB30 GATS 110 094 R 0001

Communications cable
Operating panel Commu- CPU Port CPU Type Order No. Weight
nications type port per piece
driver kg
MT30/45/ AC31 Series90 RS232 COM1
60/65/91 AC31 07KP62 RS232 COM1
MODBUS Series90 RS232 COM2 VB86 GATS 110 093 R 0011
T200 T200 RS232 PG-SS VB43 GATS 110 093 R 0201
MODBUS 07KP93 RS232 COM3/4 VB58 1SAY 110 700 R 0001
AC31 Series50 RS232 COM1
MODBUS Series50 RS232 COM1 VB67 1SAY 111 102 R 0001

Cable for RS485 interface


Operating panel Port type Description Type Order No. Weight
per piece
kg
MT45/65/91 RS485 open on
CPU side VB69 1SAY 111 103 R 0001

Programming software for operating panels


Documentation is included in all versions of the programming software 935SPSPLUS

Operating panel Drivers AC31/ Programming Type Order No. Weight


T200/ MODBUS/ software per piece
ARCNET included kg
MT30/45
MT65/91 yes 935SPSPLUS WIN GATS 110 095 R 0003

Documentation
Manuals without software

Documentation for Language Type Order No. Weight


per piece
kg
Projecting manual SPSPLUS Win German GATS 111 104 R 0001
SPSPLUS Win English GATS 111 104 R 0002
Device manual MT30/40/45/60/65/91 German GATS 111 106 R 0001
MT30/40/45/60/65/91 English GATS 111 106 R 0002

23
Operating panels
Ordering data
Operating panel TC50
Lines/ Characters/ Display Fkt.-/alpha- Device driver/ Type Order No. Weight
width height type and system interface per piece
(mm) (mm) keys/Softkeys kg
2/73 20/11 LCD 5/7/- MODBUS Master,
AC31/RS232 TC50 1SBP 26 0150 R 1001 0,5
2/73 20/11 LCD 5/7/- MODBUS Master,
and Slave/RS232
and RS485 TC50-2 1SBP 26 0151 R 1001 0,5
TC 50

Programming software
Programming software TCWIN includes programming cable for Windows 95/NT and quick start guide.

Operating panel Programming driver included Type Order No. Weight


software, cable per piece
included kg
TC50 yes MODBUS Master,
AC31 TCWIN 1SBS 260 280 R 1001

Programming cable
Cable for the conncection of the operating panel with a PC

Description Connection with Type Order No. Weight


PC per piece
kg
Programming cable D-SUB 9pol. jack 07 SK 55 1SBN 260 205 R 1001

Communications cable
Operating panel Communications CPU CPU Type Order No. Weight
driver port per piece
kg
TC50 AC31/MODBUS Series 40..50 COM1 07 SK 54 1SBN 260 204 R 1001
TC50 AC31/MODBUS Series 30/90 COM1/2 07 SK 57 1SBN 260 207 R 1001
TC50-2 MODBUS Series 40..50 COM1 07 SK 58 1SBN 260 208 R 1001

Documentation
Manuals without software

Documentation for Language Type Order No. Weight


per piece
kg
Softwaremanual TCWIN
Hardwaremanual TC50 German 1SBC 0055 99 R 1201
Softwaremanual TCWIN
Hardwaremanual TC50 English 1SBC 0055 99 R 1202

24
Accessories
Ordering data
Accessories for devices of Series 40…50
Description Type Or der No. Weight
kg
2-tier terminal for easy connection of 3-wire sensors 07 ST 50 1SBN 26 0300 R 1001 0,052
and actuators, 2 ea.
2-tier terminal for easy connection of analogue sensors, 07 ST 51 1SBN 26 0301 R 1001 0,052
2 ea.
2-tier spring-loaded terminal for easy connection of 3-wire sensors 07 ST 52 1SBN 26 0302 R 1001 0,052
and actuators, 2 ea.
07 ST 50
Spring-loaded terminal set for CPUs and bus modules 07 ST 54 1SBN 26 0311 R 1001 0,052
Spring-loaded terminal set for XI 16 E1 07 ST 55 1SBN 26 0312 R 1001 0,052
Spring-loaded terminal set for XO 08 R1 or XC 08 L1 07 ST 56 1SBN 26 0313 R 1001 0,052
Spring-loaded terminal set for XM 06 B5 07 ST 57 1SBN 26 0314 R 1001 0,052
Lables for labelling the I/O channels 1SBN 26 0310 R 1001

Accessories for devices of Series 90


Description *) Type Or der No. Weight
kg
Programming cable, PC-Sub D25 connector A 07 SK 90 GJR 525 0200 R 0001 0,220
Communication cable MODBUS/ASCII, PC-Sub D25 connector A 07 SK 91 GJR 525 0300 R 0001 0,220
Smart Memory Card for 07 KT 95/96/97 07 MC 90 GJR 525 2600 R 0101 0,050
Battery for programmable controllers, Series 90 07 LE 90 GJR 525 0700 R 0001 0,200
*) A including adapter Sub D25/9

CS31 bus accessories


Description Supply voltage Type Order No. Weight
kg

Repeater for CS31 bus 24 V DC NCB FPR 347 1200 R 1002 0,340
Max. lenght 2000 m (3 repeaters)
Repeater for CS31 bus 24 V DC NCBR FPR 347 1300 R 1002 0,340
for redundant, ring or radial
bus configuration

Programming and test software


Programming and test software to IEC 61131-3 for 07 KT 95, 07 KT 96 and 07 KT 97 in FDB, LD, IL, SFC, ST
Sampling-Trace, offline simulation, integrated visualisation, for Windows 95 and Windows NT on CD-ROM including
documentation.

Description Type Order No.

Programming and test software German 907 AC 1131 GJP 520 6900 R 0102
Programming and test software English 907 AC 1131 GJP 520 7000 R 0102

Documentation
Description Type Order No.

Documentation (without software) for 907 AC 1131 German 1SAC 1339 47 R 0101
English 1SAC 1339 47 R 0201
Complete system description German 1SAC 1316 99 R 0101
Configuration and operating instructions English 1SAC 1316 99 R 0201

25
Dimension diagrams ( dimensions in mm)

93

85
35 mm EN 50022
C0333D

C0334D
2
120 84 104

C0332D
Series 40 and 50, CPUs and expansible distributed units

85
93

35 mm EN 50022
C0310D

C0311D
2
65 84.5 49
C0309D

Series 40 and 50, expansions for CPUs or expansible distributed units


140

130
35 mm EN 50022
C0302D

C0301D

C0303D
240 85
230

Series 90, CPUs


140

130
35 mm EN 50022
C0319D

C0318D

5
C0320D

120 85
94

Series 90, distributed units

26
Dimension diagrams ( dimensions in mm)

63
208 + 0,5
220

4,6

Series 90, distributed units with enclosure IP 67


140

130
35 mm EN 50022

C0315D
C0316D

85 5 C0317D
120
94

Series 90, communication processors


80

35 mm EN 50022

28.2

C0330D
C0305D

C0331D

92 56 48
120
C0304D

NCB/NCBR bus repeater 07 ST 50/51 connector

27
... should you still have any questions ...

die botschafter,HD
... take advantage of the all-in ABB service. By
telephone or fax from ABB staff at regional of-
fices or via our hotline, including e-mail.

The Hotline team consists of experts who them-


selves configure and program and who can thus
pass on their day-to-day practical product and
application experience.

(03.01 - 3 - DAD) subject to modifikation


You can also receive immediate assistance via
the Hotline by phone or modem, particularly also
advice on programming.

Publication No. SAC 105899 W0202 Printed in the Federal Republic of Germany
But ABB will also be more than willing to help
you in other questions or should you have other
queries relating distributed automation. We
organise seminars and training courses on this
topic the whole year round in relation to specific
tasks in automation of machinery and systems.
On request, we can also train on site on your
premises. Simply talk to your regional advisor.

ABB STOTZ-KONTAKT GmbH


P. O. Box 10 16 80
D-69006 Heidelberg
Telephone ++49 62 21 / 701-0
Telefax ++49 62 21 / 701-1115
Internet http://www.abb.de/sst

You might also like