Rectiverter Outdoor system
6 kVA AC + 12,8-21 kW DC
The Rectiverter outdoor system combines both AC and DC feed into one
common unit. Simultaneously it provides AC backup power for 230 VAC
loads, and 48 VDC power for DC loads and battery charging.
The total DC output can be configured up to 21 kW DC load where the
limitation for AC load is set to max 6 kVA.
Together with our Type 3 cabinet platform it’s designed for a variety of
applications and can be tailored to fit your specific needs, with a protection
class of IP55.
Rectiverter Outdoor system
Up to 6 kVA AC & up to 21 kW 48 VDC output
Doc CTEJ0834.DS3 – rev1
MODULAR ARCHITECTURE APPLICATIONS KEY FEATURES
RECTIVERTER MODULE 230VAC SINGLE PHASE INPUT
The 3 port converter simultaneously TELECOM-MOBILE/WIRELESS 230 VAC THREE PHASE (Δ) INPUT
provides power for AC and DC loads.
During mains outage the Rectiverter LTE/4G/WiMAX 400 VAC THREE PHASE (Y) INPUT
48/1200 HE feeds AC loads using energy Distributed antenna system SINGLE PHASE OUTPUT
stored in the battery. Broadband 48 VDC INPUT/OUTPUT
Radio base stations/cell sites MAX 6 KVA AC OUTPUT
The modular architecture, industry-leading MAX 21 KW DC OUTPUT
efficiency, compact size, innovative design RAILWAY & METRO INFRASTRUCTURE
and comprehensive monitoring and control 1 POLE AC DISTRIBUTION OPTION
features provide significant benefits over Control & protection 2 POLE AC DISTRIBUTION OPTION
the current industry standard. Signaling -48 VDC DISTRIBUTION OPTION
GSM-R BUILT IN TRANSFER TECHNOLOGY
Safety Systems
150% OVERLOAD CAPABILITY, 15S
600% QUICK TRIP CURRENT, 20MS
POWER UTILITIES
HOT PLUGGABLE
Control & protection SMARTPACK 2 CONTROLLER
SCADA system
SMARTPACK S CONTROLLER
OPERATES IN PARALELL WITH
FLATPACK2 RECTIFIERS
GLOBAL COMPLIANCE
Rectiverter Module PATENTED HE TECHNOLOGY
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Rectiverter Outdoor system
Doc CTEJ0834.DS3 – rev1
FRONT VIEW 6KVA+12,8 KW DC
MODEL 6 KVA+12,8 KW DC
Part number CTEJ0834.4000
INPUT DATA
Voltage range AC (3 phase Y) 320-475 V
Voltage range DC 40-58 V
Maximum current AC (per phase) 28-48 A
Frequency 47-53 / 57-63 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC 200-240 V
Adjustable range DC 43-58 V
Max output power AC 6,0 kVA
Max output power DC 12,8 kW
Power factor 0,8
Frequency 50Hz, 60 Hz
OTHER SPECIFICATIONS
1 pole AC distribuition 4 pc, 6-10 A, C
-48 VDC distribution 14 pc, 10-63 A, C
Battery breaker (plug-in) 2 pc, 100 A, D
LVLD 1 pc, 150 A
Specifications are subject to change without notice Rectiverter 6 kVA+12,8 kW single phase outdoor system
SINGLE LINE 6KVA+12,8 KW DC
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Rectiverter Outdoor system
Doc CTEJ0834.DS3 – rev1
FRONT VIEW 6KVA+16,8 KW DC
MODEL 6 KVA+16,8 KW DC
Part number CTEJ0834.4001
INPUT DATA
Voltage range AC (3 phase Y) 320-475 V
Voltage range DC 40-58 V
Maximum current AC (per phase) 28-48 A
Frequency 47-53 / 57-63 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC 200-240 V
Adjustable range DC 43-58 V
Max output power AC 6,0 kVA
Max output power DC 16,8 kW
Power factor 0,8
Frequency 50Hz, 60 Hz
OTHER SPECIFICATIONS
1 pole AC distribuition 4 pc, 6-10 A, C
-48 VDC distribution 12 pc, 10-63 A, C
Battery breaker (plug-in) 2 pc, 200 A, D
LVLD 1 pc, 150 A
Specifications are subject to change without notice Rectiverter 16,8 kW+6 kVA single phase outdoor system
SINGLE LINE 6KVA+16,8 KW DC
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Rectiverter Outdoor system
Doc CTEJ0834.DS3 – rev1
FRONT VIEW FLEXIBLE AC INPUT 6KVA+16 KW DC
FLEXIBLE AC INPUT 6KVA + 16 KW DC
Part number CTE20834R1.4000
INPUT DATA
Voltage range AC Flexibel AC input
Voltage range DC 40-58 V
Maximum current AC (per phase) 35 A
Frequency 47-53 / 57-63 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC 200-240 V
Adjustable range DC 43-58 V
Max output power AC 6,0 kVA
Max output power DC 16,0 kW
Power factor 0,8
Frequency 50Hz, 60 Hz
OTHER SPECIFICATIONS
1 pole AC distribuition 4 pc, 6-10 A, C
-48 VDC distribution 14 pc, 10-63 A, C
Battery breaker (plug-in) 2 pc, 200 A, D
LVLD 1 pc, 150 A
Specifications are subject to change without notice Rectiverter 16,0 kW+6 kVA single phase outdoor system
SINGLE LINE FLEXIBLE AC INPUT 6KVA+16 KW DC
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Rectiverter Outdoor system
Doc CTEJ0834.DS3 – rev1
FRONT VIEW FLEXIBLE AC INPUT 6KVA+21 KW DC
FLEXIBLE AC INPUT 6 KVA + 21 KW DC
Part number CTE30834R1.4000
INPUT DATA
Voltage range AC Flexibel input
Voltage range DC 40-58 V
Maximum current AC (per phase) 58 A
Frequency 47-53 / 57-63 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC 200-240 V
Adjustable range DC 43-58 V
Max output power AC 6,0 kVA
Max output power DC 21,0 kW
Power factor 0,8
Frequency 50Hz, 60 Hz
OTHER SPECIFICATIONS
1 pole AC distribuition 4 pc, 2-10 A, C
-48 VDC distribution 10 pc, 10-63 A, C
Battery breaker (plug-in) 2 pc, 250 A, D
Specifications are subject to change without notice Rectiverter 21,0 kW+6 kVA single phase outdoor system
SINGLE LINE FLEXIBLE AC INPUT 6KVA+21KW DC
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Rectiverter Outdoor system
Doc CTEJ0834.DS3 – rev1
Models / ordering information 6kVA+12,8 kW DC 6kVA+16,8kW DC 6kVA+ 16,0 kW DC 6kVA+21,0kW DC
Part number CTEJ0834.4000 CTEJ0834.4001 CTE20834R1.4000 CTE30834R1.4000
AC OUTPUT DATA
Voltage (default) / (adjustable range) 230 VAC / 200 - 240 VAC
Frequency (default inverter mode) 50 Hz (adaptive)
Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive)
Power maximum (continuous / overload (<15s) ) 4800 W (6000 VA) / 8000 VA
Current maximum (continuous / overload (<15s) ) 26ARMS / 34,8ARMS
Current (maximum) Quick trip (20ms) 120A (6 x nominal)
Hold up (Voltage dips) (before switching to
> 5 ms @ 4800W load
battery)
THD < 1.5 % at resistive load
Output features Fuse in L and N, Hot pluggable
DC OUTPUT DATA
Voltage (default) / (adjustable range) 53.5 VDC / 43 - 58 VDC
Power (maximum @nominal input) 12,8 kW 1) 16,8 kW 1) 16,0 kW 1) 21,0 kW 1)
Current (maximum @VOUT ≤ 48 VDC) 267 A 1) 350 A 1) 333 A 1) 437 A 1)
Hold up time, maximum output power >10ms; VOUT > 41 VDC
Output features Short circuit proof, Over voltage Shutdown
INPUT DATA
AC Mains Input Voltage (3 phase Y) 400 VAC
Surge Protection OVP Class 2
AC Current/Phase(at nominal output voltage) (depending on type) 28-58 ARMS 3)
Frequency (default: sync range) 47-53 Hz
Frequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)
Power Factor / THD > 0.99 at 50% load or more / < 3.5%
DC Voltage nominal / extended range (no
45 - 58 VDC / 40 - 45 VDC
overload)2)
DC Current (maximum) 128 A / 180A during overload (15s)
Fuse in L and N, Hot pluggable, Varistor, Hot pluggable
Input features AC input individual screw terminals 10 mm2 for L1, L2, L3, N & PE
Battery breaker (plug-in type), LVBD default
LOAD DISTRIBUTION 6kVA+12,8kW DC 6kVA+16,8kW DC 6kVA+16,0 kW DC 6kVA+21,0 kW DC
LVLD 150 A -
1 pole AC distribution (L connection on MCB) 2*6A, 2*10A C
-48 VDC distribution ( priority load ) 2*10A,2*16A,2*32A,2*63A 2*10A, 2*32A,2*63A 2*10A,2*16A,2*32A,2*63A 2*10A,2*16A,3*32A,3*63A
-48 VDC distribution (no priority load) 2*10A, 2*32A, 2*63A -
Battery breaker 2*100 A, D (plug-in) 2*200 A, D (plug-in) 2*200 A, D (plug-in) 2*250 A, D (plug-in)
OTHER SPECIFICATION
Control and monitoring (see Smartpack2 datasheet) Smartpack S panel mount Smartpack 2
Efficiency >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC))
Operating temperature -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensing
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxDxH] / Weight 700 x 823x 1800mm (27,6 x 32,4 x 71”) / 250kg (551 lbs)
Protection class IP 55
Colour RAL 7035
DESIGN STANDARDS
Electrical safety EN 60950-1, EN 62040-1 UPS safety
EMC ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15
EN 61000-6-1 /-2/-3/-4
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
Environment
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant
1) AC load has priority. Maximum available DC output power and current is dependent on 3) If DC voltage is pulled below 43V the input current may increase above this level
instant AC load and AC input voltage; i.e maximum 10,9 kW/18,9 kW at full AC power and
nominal input for 230VAC.
2) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on AC
output
Specifications are subject to change without notice
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com