0% found this document useful (0 votes)
176 views15 pages

BS Compact Fuse Links

The document provides detailed specifications for BS compact fuse links, including various ratings, dimensions, and catalogue numbers. It also outlines the selection criteria for motor circuit protection and includes a fuse equivalent chart for compatibility with different manufacturers. Additionally, it highlights the compliance with BS 88 and the ASTA certification for breaking capacity.

Uploaded by

andrew.cormick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views15 pages

BS Compact Fuse Links

The document provides detailed specifications for BS compact fuse links, including various ratings, dimensions, and catalogue numbers. It also outlines the selection criteria for motor circuit protection and includes a fuse equivalent chart for compatibility with different manufacturers. Additionally, it highlights the compliance with BS 88 and the ASTA certification for breaking capacity.

Uploaded by

andrew.cormick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

Refer catalogue NF

■ Complies with BS 88
BS compact fuse links ■ Reduced dimensions
■ Low watts loss
Clip-in offset tags
Overall Overall
BS 88 length Dia.
Rating (A) ref. (mm) (mm) Cat. No. 1)

2 F1 60 14 NNS 2
VIDE 4 NNS 4
S PRO ORT
FUSERIOR SH 6 NNS 6
SUPECIRCUITON
ECTI 10 NNS 10
PROT
16 NNS 16
20 NNS 20
25 NNS 25
32 NNS 32
20M25 NNS 20M25
20M32 NNS 20M32
20 F2 68 17 NES 20
25 NES 25
NNS 2
32 NES 32
40 NES 40
50 NES 50
63 NES 63

Bolted pattern offset tags


Fixing
BS 88 centres
Rating (A) ref. (mm) Cat. No. 1)
2 A1 44.5 NNIT 2
4 NNIT 4
6 NNIT 6
NES 20 10 NNIT 10
16 NNIT 16
20 NNIT 20
25 NNIT 25
32 NNIT 32
20M25 NNIT 20M25
20M32 NNIT 20M32
32M40 NNIT 32M40
32M50 NNIT 32M50
32M63 NNIT 32M63
NNIT 16 2 A2 73 NTIA 2
4 NTIA 4
6 NTIA 6
10 NTIA 10
16 NTIA 16
20 NTIA 20
25 NTIA 25

11 32
32M40
NTIA 32
NTIA 32M40
32M50 NTIA 32M50
NTIA 16 32M63 NTIA 32M63

1
Note: ) ‘M’ in catalogue No. denotes motor starting type.
Refer catalogue NF
BS compact fuse links
FU
SUPESES PROV
RIO IDE
C R SHO
PROITRCUIT RT
ECTIO
Bolted pattern offset tags (cont.) N
Fixing
Rating (A) BS 88 Ref centres (mm) Cat. No. 1)
35 A3 73 NTIS 35
40 NTIS 40
50 NTIS 50
63 NTIS 63
63M80 NTIS 63M80
NOS 100M125 63M100 NTIS 63M100
80 HYBRID A3 73 NOS 80
100 NOS 100
100M125 NOS 100M125
100M160 NOS 100M160
80 A4 94 NTCP 80
100 NTCP 100
100M125 NTCP 100M125
100M160 NTCP 100M160
125 HYBRID A4 94 NTFP 125
160 NTFP 160
200 NTFP 200
NTFP125
200M250 NTFP 200M250

Bolted pattern centre tags


2 - 97 NTB 2
4 NTB 4
6 NTB 6
10 NTB 10
16 NTB 16
20 NTB 20
25 NTB 25
32 NTB 32
40 NTB 40
NTB 16 50 NTB 50
63 NTB 63
63M80 NTB 63M80
63M100 NTB 63M100
2 B1 111 NTBC 2
4 NTBC 4
6 NTBC 6
10 NTBC 10
16 NTBC 16
20

1
NTBC 20
11
Note: ) ‘M’ in catalogue number denotes motor starting type
NTBC 20
Refer catalogue NF
BS compact fuse links
FU
SUPESES PROV
RIO IDE
C R SHO
PROITRCUIT RT
ECTIO
N

Bolted pattern centre tags (cont.)


Fixing
Rating (A) BS 88 Ref. centres (mm) Cat. No. 1)
25 B1 111 NTBC 25
32 NTBC 32
40 NTBC 40
50 NTBC 50
63 NTBC 63
63M80 NTBC 63M80
NTF 200
63M100 NTBC 63M100
80 B1 111 NTC 80
100 NTC 100
100M125 NTC 100M125
100M160 NTC 100M160
100M 200 NTC 100M200
125 B2 111 NTF 125
160 NTF 160
200 NTF 200
200M 250 NTF 200M250
200M 315 NTF 200M315
NTM 400
250 B3 111 NTKF 250
315 NTKF 315
315M 400 NTKF 315M400
250 133 NTKM 250
315 NTKM 315
355 B4 111 NTMF 355
400 NTMF 400
355 C1 133/184 NTM 355
400 NTM 400
450 C2 133/184 NTTM 450
500 NTTM 500
NTLT 710
560 NTTM 560
630 NTTM 630
450 165/229 NTT 450
500 NTT 500
560 NTT 560
630 NTT 630
710 C3 133/184 NTLM 710
800 NTLM 800
710 165/229 NTLT 710
800 NTLT 800
NTXU 1250
1000 D1 149 NTXU 1000

11 1250 NTXU 1250

1
Note: ) ‘M’ in catalogue number denotes motor starting type.
DIN and BS fuse link selection chart
BS Fuses
Fuse type
Switch-fuses
Cat. No.
800 630 400 315 250 200 160 125 Prefix
NNS_
NNIT_
✔ ✔ NTIA_
✔ ✔ NTIS_
✔ ✔ NOS_
✔ NTCP_
NTFP_
NTSL00_
✔ ✔ ✔ ✔ NTBC_
✔ ✔ ✔ ✔ NTC_
✔ ✔ ✔ ✔ NTF_
✔ ✔ ✔ NTKF_
NTSL3_
✔ NTMF_
✔ ✔ NTM_
✔ ✔ NTTM_
✔ NTLM_

NHP HRC fuse holders Fuse type


Cat. No.
NC (Bolt-in) NV (Clip-in)
Prefix
315 200 100 63 32 20 63
20 32 20
✔ ✔ NNS_
✔ NES_
Quick - Link
fuse reference ✔ ✔ NNIT_
guide ✔ 1) ✔ ✔ NTIA_
✔ )1 ✔ ✔ 2) NTIS_
✔ 1) ✔ NOS_
✔ NTCP_
✔ NTFP_
✔ NTBC_
✔ NTC_
✔ NTF_
✔ NTKF_

DIN Fuses
Fuse type
Switch-fuses
Cat. No.
800 630 400
630 250 160 125 Prefix
✔ ✔ N00_

11 ✔
✔ N1_
N2_
✔ ✔ N3_
Legend: ✔ Fuse links fit direct.
✔ 1) Fuses require 100MFLK adaptor, see page 11-107.
✔ 2) ‘M’ type (motor rated) NTIS not suitable for NC63_. Use NC100 fuse holder.
BS compact fuse links
Bolted pattern - Centre tag
Motor rated fuse links
BS 88 aligns with international fuse specification IEC 269. Special motor rated fuse links are listed and are available in various
barrel sizes, in each case fitted with special fuse elements. Their selection frequently permits the use of lower rated switch and/or
fusegear than would be the case if using Class gG fuse links. This range of fuse-links has been ASTA certified for a breaking capacity
of 80 kA at 415 V AC.
NHP Compact industrial bolted pattern fuse links conform with BS 88: Part 2: 1998 and have been ASTA certified for a breaking
capacity of 80 kA at 415 V AC or 550 V AC and have utilisation categories gG.
NHP Compact fuse-links are suitable for back-up protection in motor circuits, having excellent time delay characteristics with low
fusing factor and high rupturing capacity.
Fuses for use in motor circuits should be selected in accordance with the requirements for the protection of motor control gear as
specified by the control gear manufacturer.
As a guide, the following table shows the minimum fuse sizes that may be associated with motors based on the assumption that the
starting conditions for typical 3 phase 4 pole 415 V motors are; 8 x FLC for 6 secs [DOL] and 4 x FLC for 12 secs [Star-delta].

Fuse link selection for motor circuit protection


Start assisted
Motor rating Approx. DOL starting Motor rated standard fuse
kW hp FLC (A) fuse link (A) fuse-link (A) link (A)
0.19 0.25 0.7 4 2
0.37 0.5 1.3 6 4
0.55 0.75 1.6 6 4
0.75 1.0 1.8 10 4
1.1 1.5 2.6 10 6
1.5 2.0 3.4 10 10
2.2 3.0 5.0 16 10
3.0 4.0 6.5 16 10
4.0 5.5 8.0 20 20M25 16
5.5 7.5 11.0 25 20M32 16
7.5 10 15 40 32M40 25
11.0 15 22 50 32M50 32
15.0 20 28 63 32M63 40
18.5 25 36 80 63M80 50
22 30 39 80 63M80 63
30 40 52 100 63M100 63
37 50 69 160 100M160 80
45 60 79 160 100M160 100
55 75 96 200 160
75 100 125 200 200M250 160
90 125 156 250 200M250 160
110 150 189 315 200
132 175 224 355 250
150 200 255 355 250
160 220 275 400 315
185 250 318 450 315
200 270 339 500 355
220
257
300
350
400
374
450
560
630
710
400
450
500
11
295 500
315 430 535 710 560
355 483 580 800 630
400 545 646 800 710
450 612 725 1000 800
Fuse equivalent chart
This chart is designed to help choose the correct fuse to fit a particular switch-fuse (or vice versa) and to help choose the correct
replacement fuse. Some data is from other manufacturers publications and as such cannot be guaranteed by NHP. Beware that some
motor start fuses are in a larger body size than a normal fuse. It is wise to consult the fuse manufacturer’s data to determine their
particular fuse sizes (i.e. A2-C3).
Fuse manufacturer’s part numbers - Australian/British standard
BS EATON/ Alstom
Ref. Amps MEM Holec GEC Bussmann PDL Siemens
F1 2…32 NNS SN2 NS NS NSD N20C 3NW NS
F2 20…63 NES SP MES ES ESD N63E 3NW ES
A1 2…32 NNIT SA2 NIT NIT NITD N20B 3NW NIT
A2 2…32 NTIA SB3 TIA TIA AAO N32B 3NW TIA
A3 35…63 NTIS SB4 TIS TIS BAO N63B 3NW TIS
Hybrid (A3) 80…100 NOS SO - OS OSD NOSD 3NW OS
Hybrid (A3) 125…160 NTSL00 – – – – – –
A4 80…100 NTCP SD5 TCP TCP CEO N100B 3NW TCP
Hybrid (A4) 125…200 NTFP 1) SD6 TFP TFP DEO N200B 3NW TFP
- 2…32/40…63 NTB SE3/SE4 TB TB AC/BC N_TB 3NW TB
B1 2…32/40…63 NTBC SF3/SF4 TBC TBC AD/BD N63B_ 3NW TBC
B1 80…100 NTC SF5 TC TC CD N100B_C 3NW TC
B2 125…200 NTF SF6 TF TF DD N200B_C 3NW TF
B3 250…315 NTKF SF7 TKF TKF ED N315B_C 3NW TKF
- 250…315 NTKM SG7 TKM TKM EFS N315B_C 3NW TKM
B4 355…400 NTMF SF8 TMF TMF ED N400B_C 3NW TMF
Hybrid (B4) 450…630 NTSL3 – – – – – –
C1 355…400 NTM SH8 TM TM EF N404B_C 3NW TM
C2 450…630 NTTM SH9 TTM TTM FF N504B_C 3NW TTM
- 450…630 NTT SY9 TT TT FG N630B_C 3NW TT
C3 710…800 NTLM SH10 TLM TLM GF N804B_C 3NW TLM
- 710…800 NTLT SY10 TLT TLT GG B804B_C 3NW TLT
D1 1000…1250 NTXU SJ11 TXU TXU GH N_U44 3NW TXU
DIN pattern
00 6…160 N00 NH00 - NHG-00 NH00G - 3NA5
1 25…250 N1 NH01 - NHG-1 NH1G - 3NA4 144
2 80…400 N2 NH02 - NHG-2 NH2G - 3NA4 260
3 315…800 N3 NH03 - NHG-3 NH3G - 3NA1
Fuse holders
Clip-in 20A NV20FW V20FF - SC20H - FC20FW -
32A NV32FW V32FF - SC32H 32NNSF NC32FW 3NW 32NNSF
Front wired 20A N20FW 20MFB - RSM20H - FB20FW 3NWCM20FC
32A NC32FW 32MFB 200846 RSM32H - FB32FW 3NW CM32F
63A NC63FW 63MFB LCF63FCFC RSM63H - FB63FW 3NW CM63F
100A NC100FW 100MFB - RSM100H - FB100FW 3NW CM100F
200A NC200FW 200MFB - RSM200H - FB200FW 3NW 200DF
Stud/ 20A N20SFW 20MFD - RSM20PH - FB20SF -
front wired 32A NC32SFW 32MFD LCF32FCBC RSM32PH - FB32SF -

11 63A
100A
NC63SFW
NC100SFW
63MFD
100MFD
LCF63FCBC
-
RSM63PH
RSM100PH
-
-
FB63SF
FB100SF
-
-
200A NC200SFW 200MFD - RSM200PH - FB200SF -

1
Note: ) This hybrid type fuse is actually an A4 size fuse, but as it is over 100 amps it cannot be called an A4 fuse to AS 2005.
HRC cartridge fuse-links NHP Compact fuses

NHP Compact 415V fuse-links are available in As a guide, the following table shows the minimum
ratings from 2A up to 1250A and advanced design fuse sizes that may be associated with motors based
techniques mean that watts loss figures have been on the assumption that the starting conditions for
substantially reduced whilst protection typical 3 phase 4 pole 415V motors are; 8 x F.L.C. for
characteristics remain unchanged. 6 secs [D.O.L.] and 4 x F.L.C. for 12 secs [Star Delta].
All NHP Compact HRC fuse-links are manufactured Should more specific information be required to assist
using precision assembly methods to ensure that their on individual projects please contact your nearest
performance will conform with the published NHP office or distributor.
characteristics within very close tolerances.
Cartridge barrels are extruded under vacuum to fuse-link selection for motor circuit protection
prevent the occurrence of air pockets. Each fuse is
Motor rating D.O.L. Starting Assisted start
then fully filled, using a vibratory method, with Approx standard motor standard
specially prepared, dried and graded powdered silica. f.l.c. fuse-link circuit fuse-link
The end caps are press fitted on to the precision kW hp amps amps fuse-link amps
ground barrels ensuring a very tight fit. 0.19 0.25 0.7 4 2
0.37 0.5 1.3 6 4
Fuse elements are accurately shaped and 0.55 0.75 1.6 6 4
manufactured for consistency and reliability. 0.75 1.0 1.8 10 4
1.1 1.5 2.6 10 6
All NHP Compact fuse-links are subjected to a 1.5 2.0 3.4 10 10
resistance test to prove correct assembly. 2.2 3.0 5.0 16 10
3.0 4.0 6.5 16 10
NHP Compact HRC fuse-links, other than motor
4.0 5.5 8.0 20 20M25 16
rated patterns, have utilisation categories gG. 5.5 7.5 11.0 25 20M32 16
Schedules of equivalent fuse-links made by certain 7.5 10 15 40 32M40 25
11.0 15 22 50 32M50 32
other manufacturers are included in the following
15.0 20 28 63 32M63 40
pages. No claim is made of identical performance 18.5 25 36 80 63M80 50
under all conditions, the schedules being provided to 22 30 39 80 63M80 63
assist on the selection of fuse-links having similar 30 40 52 100 63M100 63
ratings, dimensions and fixing centres. Characteristic 37 50 69 160 100M160 80
45 60 79 160 100M160 100
curves and associated data are provided to aid
55 75 96 200 160
accurate discrimination. 75 100 125 200 200M250 160
90 125 156 250 200M250 160
Motor rated fuse-links 110 150 189 315 200
BS88 now aligns with the international fuse 132 175 224 355 250
150 200 255 355 250
specification IEC 269. The concept of “fusing factor” 160 220 275 400 315
has been replaced with “utilisation category”. Class 185 250 318 450 315
Q1 fusing factor is now referred to as “gG” and motor 200 270 339 500 355
rated fuse-links are referred to as “gM”. Special motor 220 300 374 560 400
257 350 450 630 450
rated fuse-links are also listed and are available in
295 400 500 710 500
various barrel sizes, in each case fitted with special 315 430 535 710 560
fuse elements. Their selection frequently permits the 355 483 580 800 630
use of lower rated switch and/or fusegear than would 400 545 646 800 710
be the case using Class gG fuse-links. This range of 450 612 725 1000 800
fuse-links has been ASTA certified for a breaking
capacity of 80kA at 415V AC.
NHP Compact industrial bolted pattern fuse-links
conform with BS 88: Part 2: 1988 and, have been ASTA
certified for a breaking capacity of 80kA at 415V AC
or 550V AC and have utilisation categories gG.
NHP Compact fuse-links are suitable for back-up
protection in motor circuits, having excellent time
delay characteristics with low fusing factor and high
rupturing capacity.
Fuses for use in motor circuits should be selected in
accordance with the requirements for the protection of
motor control gear as specified by the control gear
manufacturer.
Fuse-link terminology NHP Compact fuses

HRC Discrimination (refer tables 4 and 5)


High rupturing capacity (HRC) or High breaking Discrimination is the ability of fuse-links to operate
capacity denotes the ability of a fuse-link to interrupt selectively and to disconnect only the parts of the
extremely high fault currents, usually up to 80kA. circuit that are subject to faults. Discrimination can
be checked by ensuring that the time current
Current limiting fuse-link
characteristics, including their tolerances, do not
A fuse-link that limits the circuit current during it’s
overlap at any point and that the total let through
operation to a value much lower than the peak value
energy (I2t) of the downstream (or minor) fuse-link
of the prospective current. In practice, the terms HRC
does not exceed the pre-arcing energy (I2t) of the
and current limiting are synonymous.
upstream (or major) fuse-link at the applied system
Rated breaking capacity voltage. Discrimination is normally achieved with
The highest value of fault current that a fuse-link has the ratio of 1.6 between upstream and downstream
been tested to interrupt eg. 80kA. fuses.
Rated voltage Table 1
The maximum system voltage that the fuse-link is
designed to interrupt. Rated voltages may be in AC,
DC, or both.
Current rating
The value of current that a fuse-link will carry
continuously without deterioration under specified
conditions.
Minimum fusing current
The minimum value of current that will cause melting Typical time current curves
of the fuse element.
Table 2
Power dissipation
The power released in a fuse-link carrying rated
current under a specified condition, usually expressed
I2t
in watts.
Time current characteristics (refer table 1)
A curve detailing the pre-arcing or operating time as a
function of prospective current.
Fuse rating
Let through characteristics (I2t) (refer table 2)
A curve or chart showing values ‘pre-arcing’ and Operating and pre-arcing I2t values
‘operating’ let through energies as a function of
prospective current, I2t is proportional to energy in Table 3
Amp2 seconds.
Cut off characteristics (refer table 3)
A curve detailing the cut off current as a function of
prospective current. Cut off current being the
maximum instantaneous value of current let through
by the fuse-link during operation.

Cut off characteristics

Table 4 Table 5

Discrimination achieved Discrimination NOT achieved


HRC cartridge fuse-links Cross reference guide

NNS-Type staggered contacts breaking capacity 80kA at 415V AC to BS 88: Part 6: 1988 Ref. F1
Overall Overall Cross reference
Current rating A length dia. NHP Brush/ Bussman/
Normal Motor mm mm Cat No. MEM GEC/Lawson Siemens Hawker Dorman Smith
2 NNS2 2SN2 NS2 3NW NS2 2F06 NSD2
4 - NNS4 4SN2 NS4 3NW NS4 4F06 NSD4

}
6 - NNS6 6SN2 NS6 3NW NS6 6F06 NSD6
10 - NNS10 10SN2 NS10 3NW NS10 10F06 NSD10
16 - NNS16 16SN2 NS16 3NW NS16 16F06 NSD16
20 - 60 14 NNS20 20SN2 NS20 3NW NS20 20F06 NSD20
20 25 NNS 20M25 20SN2M25 NS20M25 3NW M25 20M25F06 NSD20M25
20 32 NNS 20M32 20SN2M32 NS20M32 3NW M32 20M32F06 NSD20M32
25 - NNS25 25SN2 NS25 3NW NS25 25F06 NSD25
32 - NNS32 32SN2 NS32 3NW NS32 32F06 NSD32

NES-Type staggered contacts breaking capacity 80kA at 415V AC to ASTA certified to BS 88: Part 6: 1988

}
20 NES20 20SP - - - ESD20
25 NES25 25SP - - - ESD25
32 NES32 32SP - - - ESD32
68 17
40 NES40 40SP 40ES 3NWES40 40G05 3SD40
50 NES50 50SP 50ES 3NWES50 50G05 ESD50
63 NES63 63SP 63ES 3NWES63 63G05 ESD63

Industrial bolted pattern. Offset contacts ASTA certified to BS 88: Part 2: 1988.
Complies with IEC 269 Parts 1 and 2. Tested to 80kA at 415V AC
Cross reference
Current rating A Fixing BS88 NHP Brush/ Bussman/
Normal Motor centres ref Cat No. MEM GEC/Lawson Siemens Hawker Dorman Smith
2 NNIT2 2SA2 NIT2 3NWNIT2 2F21 NITD2

}
}
4 - NNIT4 4SA2 NIT4 3NWNIT4 4F21 NITD4
6 - NNIT6 6SA2 NIT6 3NWNIT6 6F21 NITD6
10 - A1 NNIT10 10SA2 NIT10 3NWNIT10 10F21 NITD10
16 - NNIT16 16SA2 NIT16 3NW NIT16 16F21 NITD16
20 - NNIT20 20SA2 NIT20 3NWNIT20 20F21 NITD20
20 25 44.5 - NNIT20M25 20SA2M25 NIT20M25 3NWNIT20M25 20M25F21 NITD20M25
20 32 - NNIT20M32 20SA2M32 NIT20M32 3NWNIT20M32 20M32F21 NITD20M32
25 - - NNIT25 25SA2 - 3NWNIT25 25F21 NITD25
32 - - NNIT32 32SA2 - 3NWNIT32 32F21 NITD32
32 40 - NNIT32M40 32SA2M40 - 3NWNIT32M40 - -
32 50 - NNIT32M50 32SA2M50 - 3NWNIT32M50 - -
32 63 - NNIT32M63 32SA2M63 - 3NWNIT32M63 - -
2 - NTIA2 2SB3 TIA2 3NWTIA2 2H07 AA02

}
4 - NTIA4 4SB3 TIA4 3NWTIA4 4H07 AA04
6 - NTIA6 6SB3 TIA6 3NWTIA6 6H07 AA06
10 - NTIA10 10SB3 TIA10 3NWTIA10 10H07 AA010
16 - NTIA16 16SB3 TIA16 3NWTIA16 16H07 AA016
20 - 73 A2 NTIA20 20SB3 TIA20 3NWTIA20 20H07 AA020
25 - NTIA25 25SB3 TIA25 3NWTIA25 25H07 AA025
32 - NTIA32 32SB3 TIA32 3NWTIA32 32H07 AA032
32 40 NTIA32M40 32SB3M40 TIA32M40 3NWTIA32M40 32M40H07 AA032M40
32 50 NTIA32M50 32SB3M50 TIA32M50 3NWTIA32M50 32M50H07 AA032M50
32 63 NTIA32M63 32SB3M63 TIA32M63 3NWTIA32M63 32M63H07 AA032M63
35 - NTIS35 35SB4 TIS35 3NWTIS35 35KO7 BAO35
40
50
63
63
63
80
-
-
-
80
100
-
} 73 A3
NTIS40
NTIS50
NTIS63
NTIS63M80
NTIS63M100
N0S80
40SB4
50SB4
63SB4
63SB4M80
63SB4M100
80SO
TIS40
TIS50
TIS63
TIS63M80
TIS63M100
OS80
3NWTIS40
3NWTIS50
3NWTIS63
3NWTIS63M80
3NWTIS63M100
3NW0S80
40KO7
50KO7
63KO7
63M80KO7
63M100KO7
80KO7R
BAO40
BAO50
BAO63
BAO63M80
BAO63M100
OSD80
100
100
100
80
-
125
160
-
} 73
N0S100
NOS100M125
NOS100M160
NTCP80
100SO
-
-
80SD5
OS100
OS100M125
OS100M160
TCP80
3NW0S100
-
-
3NWTCP80
100KO7R
100M125KO7R
100M160KO7R
80L14
OSD100
OSD100M125
OSD100M160
CEO80
100
100
100
125
-
125
160
-
} 94 A4
NTCP100
NTCP100M125
NTCP100M160
NTFP125
100SD5
100SD5M125
100SD5M160
125SD6
TCP100
TCP100M125
TCP100M160
TFP125
3NWTCP100
3NWTCP100M125
3NWTCP100M160
3NWTFP125
100L14
100M125L14
100M160L14
125M14
CEO100
CEO100M125
CEO100M160
DEO125
160 - NTFP160 160SD6 TFP160 3NWTFP160 160M14 DEO160
200 - NTFP200 200SD6 TFP200 3NWTFP200 200M14 DEO200
200 250 94 NTFP200M250 200SD6M250 TFP200M250 - 200M250M14 DEO200M250
HRC cartridge fuse-links Cross reference guide

NHP Compact industrial bolted pattern. Centre contacts, ASTA certified to BS 88: Part 2: 1988.
Complies with IEC 269 parts 1 and 2. Tested to 80kA at 415V AC. *550V AC.
Cross reference
Current rating A Fixing BS88 NHP Brush/ Bussman/
Normal Motor centres ref Cat No. MEM GEC/Lawson Siemens Hawker Dorman Smith
2 - NTB2* 2SE3 TB2 3NWTB2 2KO8 AC2

}
4 - NTB4* 4SE3 TB4 3NWTB4 4KO8 AC4
6 - NTB6* 6SE3 TB6 3NWTB6 6KO8 AC6
10 - NTB10* 10SE3 TB10 3NWTB10 10KO8 AC10
16 - NTB16* 16SE3 TB16 3NWTB16 16KO8 AC16
20 - NTB20* 20SE3 TB20 3NWTB20 20KO8 AC20
25 - 97 – NTB25* 25SE3 TB25 3NWTB25 25KO8 AC25
32 - NTB32* 32SE3 TB32 3NWTB32 32KO8 AC32
40 - NTB40* 40SE3 TB40 3NWTB40 40KO8 BC40
50 - NTB50* 50SE3 TB50 3NWTB50 50KO8 BC50
63 - NTB63* 63SE3 TB63 3NWTB63 63KO8 BC63
63 80 NTB63M80 63SE4M80 TB63M80 3NWTB63M80 - -
63 100 NTB63M100 63SE4M100 TB63M100 3NWTB63M100 - -
2 - NTBC2 2SF3 TBC2 3NW TBC2 2KO9 AD2

}
4 - NTBC4 4SF3 TBC4 3NW TBC4 4KO9 AD4
6 - NTBC6 6SF3 TBC6 3NW TBC6 6KO9 AD6
10 - NTBC10 10SF3 TBC10 3NW TBC10 10KO9 AD10
16 - NTBC16 16SF3 TBC16 3NW TBC16 16KO9 AD16
20 - NTBC20 20SF3 TBC20 3NW TBC20 20KO9 AD20
25 - 111 B1 NTBC25 25SF3 TBC25 3NW TBC25 25KO9 AD25
32 - NTBC32 32SF3 TBC32 3NW TBC32 32KO9 AD32
40 - NTBC40 40SF3 TBC40 3NW TBC40 40KO9 AD40
50 - NTBC50 50SF3 TBC50 3NW TBC50 50KO9 AD50
63 - NTBC63 63SF3 TBC63 3NW TBC63 63KO9 AD63
63 80 NTBC63M80 63SF4M80 TBC63M80 3NW TBC63M80 - -
63 100 NTBC63M100 63SF4M100 TBC63M100 3NW TBC63M100 - -
80 - NTC80 80SF5 TC80 3NW TC80 80LO9 CD80
100
100
100
-
125
160
} 111 B1 NTC100
NTC100M125
NTC100M160
100SF5
100SF5M125
100SF5M160
TC100
TC100M125
TC100M160
3NW TC100
3NW TC100M125
3NW TC100M160
100LO9
100M125LO9
100M160LO9
CD100
CD100M125
CD100M160
100 200 NTC100M200 100SF5M200

}
125 - NTF125 125SF6 TF125 3NW TF125 125MO9 DD125
160 - 111 B2 NTF160 160SF6 TF160 3NW TF160 160MO9 DD160
200 - NTF200 200SF6 TF200 3NW TF200 200MO9 DD200
200 250 NTF200M250 200SF6M250 TF200M250 3NW TF200M250 200M250MO9 DD200M250
200 315 NTF200M315 200SF6M315 TF200M315 3NW TF200M315 200M315M09
250 - B3 NTKF250 250SF7 TKF250 3NW TKF250 250NO9 ED250
315 - } 111 NTKF315 315SF7 TKF315 3NW TKF315 315NO9 ED315
315 400 NTKF315M400 315SF7M400 3NW TKF315M400
250 - 133 – NTKM250 250SG7 TKM250 3NW TKM250 250N11 EFS250
315 -
} NTKM315 315SG7 TKM315 3NW TKM315 315N11 EFS315
NTMF355
355
400
-
-
} 111 B4
NTMF400
355SF8
400SF8
TMF355
TMF400
3NW TMF355
3NW TMF400
355PO9
400PO9
ED355
ED400
355
400
-
-
} 133/
184
C1 NTM355
NTM400
355SH8
400SH8
TM355
TM400
3NW TM355
3NW TM400
355P11
400P11
EF355
EF400
450 - NTTM450 450SH9 TTM450 3NW TTM450 450R11 FF450
500
560
630
-
-
-
} 133/
184
C2 NTTM500
NTTM560
NTTM630
500SH9
560SH9
630SH9
TTM500
TTM560
TTM630
3NW TTM500
3NW TTM560
3NW TTM630
500R11
560R11
630R11
FF500
GF550
GF630
450 165/ – NTT450 450SY9 TT450 3NWTT450 450R12 FG450
500
560
630
} 229 NTT500
NTT560
NTT630
500SY9
560SY9
630SY9
TT500
TT560
TT630
3NWTT500
3NWTT560
3NWTT630
500R12
560R12
630R12
FG500
FG560
FG630
710 165/ – NTLT710 710SY10 TLT710 3NWTLT710 710S12 GG710
800 229 NTLT800 800SY10 TLT800 3NWTLT800 800S12 GG800
710 - 133/ C3 NTLM710 710SH10 TLM710 3NW TLM710 700S11 GF710
800 -
} 184 NTLM800 800SH10 TLM800 3NW TLM800 800S11 GF800
1000 - NTXU1000 1000SJ11 TXU1000 - 1000U44 GH1000
- 149 D1
1250 NTXU1250 1250SH11 TXU1250 - 1250U44 GH1250
HRC cartridge fuse-links Dimensions

Dimensions (mm)
Fuse A B D E F G H J
link max. max. max. nom.
type mm mm mm mm mm mm mm mm
NNIT 36 14 55 11 0.8 44.5 4.8 -

NTIA
NTIS } 56 21 86 9 1.2 73 5.5 7.5

NTIS(M) 58 26 90 13 1.6 73 5.5 -


NOS 58 27 90 13 1.6 73 5.5 -

NTCP 62 27 110 19 2.4 94 8.7 -


NTCP(M) 62 30 110 19 2.4 94 8.7 -
NTFP 77 30 110 19 2.4 94 8.7 10.3
NTFP(M) 77 40 110 19 2.4 94 8.7 10.3

Dimensions (mm)
Fuse A B D E F G H J L
link max. max. max. nom.
type mm mm mm mm mm mm mm mm mm
NTB 57 21 114 13 1.6 97 7.2 11 -

NTB...M... 57 26 116 13 1.6 97 7.2 11 -

NTBC 57 21 134 16 2.0 111 8.7 16 -

NTBC...M... 58 26 136 16 3.2 111 8.7 16 -

NTC 66 36 135 19 3.6 111 8.7 16 -


NTF 76 41 137 19 3.6 111 8.7 16 -
NTKF 76 51 137 26 4.0 111 8.7 16 -
NTMF 81 58 136 26 5.2 111 8.7 16 -

NTKM 76 51 158 26 4.0 133 8.7 16 -

NTM 81 58 210 26 5.2 133/184 10.3 16 25.4


NTTM 83 74 210 26 6.5 133/184 10.3 16 25.4
NTLM 84 82 210 26 10 133/184 10.3 16 25.4

NTT 83 74 267 38 6.5 165 10.3 16 32


NTLT 84 82 267 38 10 165 10.3 16 32

NTXU 83 100 198 63.5 9.5 149 14.3 19 32

NTT, NTLT, NTM,


NTTM, NTLM
types

NTXU type
I2t characteristics BS fuses I 2t data

I2t characteristics
Rating I2t I2t total I2t total
(amperes) pre-arcing @ 240 volts @ 415 volts
2 2 2 4

4 10 15 21

6 34 52 74

10 188 289 408

16 92 211 412

20 155 355 690

20M25 574 1084 1809

20M32 574 1561 2605

25 826 1084 1809

32 826 1561 2605

35 1200 2400 4100

32M40 2482 4416 7019

32M50 3305 5879 9345

32M63 5875 10452 16612

40 2482 4416 7019

50 3305 5879 9345

63 5875 10452 16612

80 & 63M80 7800 15500 26000

100 & 63M100 14000 28000 46000

125 & 100M125 30000 51000 75500

160 & 100M160 58500 99000 145000

200 & 100M200 120000 205000 300000

250 & 200M250 210000 360000 530000

315 & 200M315 270000 460000 680000

355 365000 620000 915000

400 & 315M400 480000 820000 1200000

450 755000 1300000 1900000

500 1100000 1850000 2700000

560 1200000 2400000 4000000

630 1550000 3100000 5150000

710 1903565 2992861 4306813

800 3820349 6006505 8643534

1000 7000000 1500000 16000000

1250 12000000 20500000 30000000


Fuse curves BS fuse curves

NHP Compact
BS fuses from 20
to 250 amps

8
6 630
560
500
450
4 400
355
315
250
200
2 160

125
100
10 80
CUT-OFF CURRENT PEAK kA

8 63

6 50
40
4
32
NHP Compact
BS fuses cut-off
2 20
current data from
20 to 630 amps
1
8
6

0.1
0.1 2 4 6 8 1 2 4 6 8 10 2 4 6 8
PROSPECTIVE CURRENT kA (R.M.S. SYMMETRICAL)
Fuse curves BS fuse curves

10000
80 & 63M80
6 100 & 63M100
4 100SOM125

FUSE RATING (A)


125 & 100M125
2 160 & 100M160
200 & 100M200
1000 250 & 200M250
315 & 200M315
6 355
4 400 & 315M400
450
2 500
560
630
100
6
4
NHP Compact
TIME (SECONDS)

2
BS fuses from 10
80A to 630 amps 6
4
(including motor
2
rated fuses)
1
6
4
2

0.1
6
4
2
0.01
100 2 4 6 8 1000 2 4 6 8 10000 2 4 6 8
CURRENT (AMPERES)

8
6 630
560
500
450
4 400
355
315
250
200
2 160

125
100
10 80
CUT-OFF CURRENT PEAK kA

8
6
NHP Compact BS 4
fuses cut-off
current data from 2
80 to 630 amps
1
8
6

0.1
0.1 2 4 6 8 1 2 4 6 8 10 2 4 6 8
PROSPECTIVE CURRENT kA (R.M.S. SYMMETRICAL)
DIN fuses curves and data DIN fuses curves
and data

NHP Compact DIN fuses


Pre-arcing and Total I2t energies,
from 6 to 630 amps

NHP Compact DIN fuses


cut-off current data
from 6 to 500 amps

NHP Compact DIN fuses


Fuse curves