1B-6070 Gce MS CD PJW 0005 0
1B-6070 Gce MS CD PJW 0005 0
Specification Reference(s):
Equipment / Material Specified Equipment / Material Offered
Manufacturer: N/A Manufacturer: N/A
Brand: N/A Brand: N/A
Country of Origin: N/A Country of Origin: N/A
Model No.: N/A Type: N/A
Purpose / Remark:
SAFETY TEAM
Mr. Alvin Canlas
WORK PACKAGE
MANAGER
Engr. Norly Borja
`
CONSOLIDATED COMMENTS: Please add separate sheet if required:
Prepared by:
1. Check and adjust the elevator car and all landing doors.
2. Ensure all landing doors are mechanically adjust in respect to the dimensions
of installation drawing.
3. Ensure all leveling plate and final limit is in accordance to the landing finishes.
High Speed Commissioning and Load Test
1. Check and verify again the mechanical adjustment of landing doors, safety
chain& limit switches, check also if safety features are all activated
2. After the elevator is done with the mechanical adjustments, check if the wirings
are correctly connected then perform high speed.
1. Check and ensure the mechanical and electrical are as per OTIS Standard
2. Check and ensure the mechanical and electrical are as per OTIS Standard
3. Check and ensure all safety features are operational and functioning
4. Check and ensure all builders work are compliance as per OTIS Standard
5. Check and ensure all testing are done in accordance to OTIS Testing
methodology
6. Rectify punch list provided after Pre-NIS inspection
Activation of ARD
1. Make a call for going down or car from top floor
2. Turn off the main breaker power supply
3. Activate the ARD and releveling at nearest floor. Door will open automatically.
Activation of Intercom
1. Press the button bell at COP for alarm and connection to lobby/machine room.
2. Press 1 Button>PE1, 2 Button>PE2, 3 Button>PE3
Alternate Homing:
1. Activate general alarm set at ground floor through FDAS module panel
setting.
2. Observe the elevator alarm
3. Check the COP display if fire alarm indicator is ON.
4. Check if the car is moving up to next floor level or alternate home floor.
5. Alternate homing successfully activated.
Note: FDAS contractor shall provide a dry contact to OTIS for termination
Car Door or Gate Switch Contact. Hoistway / Door Interlock or Gate contact locks.
1. Switch to inspection mode of elevator unit.
2. Operate manually moving down of car unit to nearest floor to access the car
top.
3. Operate manually of elevator unit into car top switch bottom.
4. Open the landing door or unlock the door contact to stop the car movement
and to activate the car door or gate switch contact.
Counterweight Buffers
1. Set to inspection mode of control panel switch (bypass)
2. Operate the car manually when moving up. While the car is moving down
check if the counterweight buffer spring is closed.
3. Operate manually when the car is going down and while the counterweight is
moving up to see the reaction of buffer spring.
4. Operate manually when the car is going up and while the counterweight is
moving down to see the reaction of buffer spring and if it will automatically
return to normal position.
Car Buffers
1. Set to inspection mode of control panel switch (bypass)
2. Operate the car manually when moving up. While the car is moving down
check if the counterweight buffer spring is closed.
3. Operate the car manually check to see the reaction of car buffer spring if it will
automatically return to normal position.
EMS Activation
1. Wiring, communication to control panel and control panel to elevator up to
EMS computer system.
2. Communicate from EMS computer system to elevator unit.
FDAS Interface
1. FDAS contractor shall provide a dry contact to OTIS termination at control
panel to interface.
2. OTIS will interface the FDAS dry contact on elevator system parameters
3. FDAS con will activate the general alarm.
Note: FDAS contractor shall provide a dry contact to OTIS for termination
1. OIMM
2. Hann/Mace Elevator Requirement
3. Elevator Technical Seminar & Training (Trapped Passenger Rescue
Training)
4. As-Built Plans
5. E-File Documentation
Protection
Upon delivery at site all car panel are protected by plastic vinyl protection and to be
remove prior the final hand-over.
Rectification Method
• Dents – Replacement
• Scratches – Buffing
• If water damage occurred, warranty will be voided.
➢ Replacement of parts will be charge accordingly to the responsible
group.
Acceptance/Criteria:
- Hann/Mace Acceptance.