Bus-Bar Protection_091600
Bus-Bar Protection_091600
Relay checks
Ok,Yes,No
Visual Inspection Yes
Relay damaged No
Rating information correct for installation Yes
Case earth installed Yes
Test block connections checked Yes
Relay energized
Measured auxiliary supply Yes
Relay healthy (green) LED working Yes
Trip (red) LED working Yes
Data
Rated Frequency 50 Hz
VT Ratio 132 kV / 110 V
CT Ratio 1600 / 1 A
Remarks:
All testing results are found satisfactory.
All protection relays are in overall healthy condition, and the testing results have been found
satisfactory.
Line 2's distance relay has Line differential protection disabled.
SCADA fails to display VT fuse fail alarm for Line 1 and Line 2 distance protection relays.
In WTG-14 relay, despite issuing a tripping command through the relay, the circuit breaker
does not trip.