Bus-Bar Protection_091600

The document details the inspection and testing results of the Bus-Bar Protection Relay model 7SS85 for Gul Ahmed Energy Limited, confirming that all protection relays are in a healthy condition with satisfactory test results. It notes issues with the distance relay for Line 2, SCADA alarms not displaying correctly, and a malfunction in WTG-14 where the circuit breaker fails to trip despite a command. Overall, the inspection highlights the operational status and some areas needing attention.

Uploaded by

TUF TETRATON
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views4 pages

Bus-Bar Protection_091600

The document details the inspection and testing results of the Bus-Bar Protection Relay model 7SS85 for Gul Ahmed Energy Limited, confirming that all protection relays are in a healthy condition with satisfactory test results. It notes issues with the distance relay for Line 2, SCADA alarms not displaying correctly, and a malfunction in WTG-14 where the circuit breaker fails to trip despite a command. Overall, the inspection highlights the operational status and some areas needing attention.

Uploaded by

TUF TETRATON
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Bus-Bar Protection Bay E03

Customer Gul Ahmed Energy Limited Make Siemens


Project EOW Inspection Type 7SS85
Location Bay E03 Bus Bar Protection Relay

Relay information Remarks


Relay type Bus-Bar Differential
Model number 7SS85
Rated current In 1A
Auxiliary Voltage Uaux 110 VDC

Relay checks
Ok,Yes,No
Visual Inspection Yes
Relay damaged No
Rating information correct for installation Yes
Case earth installed Yes
Test block connections checked Yes

Relay energized
Measured auxiliary supply Yes
Relay healthy (green) LED working Yes
Trip (red) LED working Yes

Data
Rated Frequency 50 Hz
VT Ratio 132 kV / 110 V
CT Ratio 1600 / 1 A

Page 147 of 150


Tripping Characteristics: Differential Idiff>
Diff Set Idiff>: 1.3 I/In Time Setting tdiff>: 0.0 s
Trip Test
Phase Bay No CT Ratio Set Pick up Injected Measured Trip Actual Trip
Current(A) current (A) time(s) time (s)
R 1.30 A 1.30 A 25 msec 0 msec
Y E01 1600/1 A 1.30 A 1.30 A 24 msec 0 msec
B 1.30 A 1.30 A 23 msec 0 msec
R 1.30 A 1.30 A 24 msec 0 msec
Y E02 1600/1 A 1.30 A 1.30 A 24 msec 0 msec
B 1.30 A 1.30 A 24 msec 0 msec
R 1.30 A 1.30 A 24 msec 0 msec
Y E03 BB-1 1600/1 A 1.30 A 1.30 A 23 msec 0 msec
B 1.30 A 1.30 A 23 msec 0 msec
R 1.30 A 1.30 A 23 msec 0 msec
Y E03 BB-2 1600/1 A 1.30 A 1.30 A 24 msec 0 msec
B 1.30 A 1.30 A 24 msec 0 msec
R 1.30 A 1.30 A 24 msec 0 msec
Y E04 1600/1 A 1.30 A 1.30 A 23 msec 0 msec
B 1.30 A 1.30 A 24 msec 0 msec
R 1.30 A 1.30 A 24 msec 0 msec
Y E05 1600/1 A 1.30 A 1.30 A 24 msec 0 msec
B 1.30 A 1.30 A 23 msec 0 msec

Tripping Characteristics: Breaker Failure Protection


CBF Stage-1: 150 msec CBF Stage-2: 250 msec
Trip Test
Phase Bay No Set Pick up Injected Stage-1 (msec) Stage-2 (msec) Results
Current(A) current (A)
R 0.200 A 0.200 A 175 msec 275 msec Ok
Y E01 0.200 A 0.200 A 176 msec 276 msec Ok
B 0.200 A 0.200 A 174 msec 274 msec Ok
R 0.200 A 0.200 A 175 msec 272 msec Ok
Y E02 0.200 A 0.200 A 176 msec 271 msec Ok
B 0.200 A 0.200 A 178 msec 271 msec Ok
R 0.200 A 0.200 A 172 msec 272 msec Ok
Y E03 BB-1 0.200 A 0.200 A 174 msec 273 msec Ok
B 0.200 A 0.200 A 175 msec 272 msec Ok
R 0.200 A 0.200 A 176 msec 278 msec Ok
Y E03 BB-2 0.200 A 0.200 A 178 msec 271 msec Ok
B 0.200 A 0.200 A 175 msec 275 msec Ok
R 0.200 A 0.200 A 174 msec 274 msec Ok
Y E04 0.200 A 0.200 A 176 msec 271 msec Ok
B 0.200 A 0.200 A 176 msec 271 msec Ok
R 0.200 A 0.200 A 175 msec 278 msec Ok
Y E05 0.200 A 0.200 A 174 msec 275 msec Ok
B 0.200 A 0.200 A 175 msec 271 msec Ok

Page 148 of 150


Tripping Characteristics: End Fault Protection
Setting: 0.5 A Time: 50 msec
Trip Test
Phase Bay No Set Pick up Injected current Trip Time (msec) Results
Current(A) (A)
R 0.500 A 0.500 A 75 msec Ok
Y E01 0.500 A 0.500 A 76 msec Ok
B 0.500 A 0.500 A 74 msec Ok
R 0.500 A 0.500 A 75 msec Ok
Y E02 0.500 A 0.500 A 76 msec Ok
B 0.500 A 0.500 A 78 msec Ok
R 0.500 A 0.500 A 74 msec Ok
Y E04 0.500 A 0.500 A 76 msec Ok
B 0.500 A 0.500 A 76 msec Ok
R 0.500 A 0.500 A 75 msec Ok
Y E05 0.500 A 0.500 A 74 msec Ok
B 0.500 A 0.500 A 75 msec Ok

Remarks:
All testing results are found satisfactory.

Page 149 of 150


Overall Conclusion and Recommendations

All protection relays are in overall healthy condition, and the testing results have been found
satisfactory.
Line 2's distance relay has Line differential protection disabled.

SCADA fails to display VT fuse fail alarm for Line 1 and Line 2 distance protection relays.

In WTG-14 relay, despite issuing a tripping command through the relay, the circuit breaker
does not trip.