Presentation A high-adaptability, 3-phase UPS that meets the unique requirements of medium to
large data centers, industry, buildings, and mission-critical environments. This UPS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
includes ECO Mode, with cost-saving energy efficiency, and SPoT operation mode,
which increases on-site test capability without additional load bank.
Lead Time Special Order - Call for Quoted Lead Times
Main
Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
450 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
415 V
440 V
Rated Power In W 270000 W
Rated Power In Va 300000 VA
Output Connector Type Hard wire 4-wire (3P + E) 1
Hard wire 5-wire (3P + N + E) 1
Hard wire 3-wire (3P) 1
Hard wire 4-wire (3P + N) 1
Hard wire 4-wire (3P + PEN) 1
Battery Type VRLA
Provided Equipment Installation guide
Network management card
User manual
Batteries & Runtime
Efficiency View Efficiency Graph action_new_window
Number Of Battery Filled Slots 0
Number Of Battery Free Slots 0
Additional Information Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Battery Power In Vah 0 VAh runtime
Extended Runtime 0
General
Bypass Wiring Configuration 4 wire (3P + N)
5 wire (3P + N + E)
21 May 2024 1
Bypass Voltage Tolerance +/- 10 % settable from +/- 4/6/8 and 10 %
Max Bypass Input Current 506 A
Bypass Current Protection 630 A
Number Of Power Module Free 0
Slots
Number Of Power Module Filled 0
Slots
Redundant No
Physical
Colour Grey
Height 190 cm
Width 141.2 cm
Depth 85.5 cm
Net Weight 960 kg
Mounting Preference No preference
Usb Compatible No
Input
Network Frequency 45...65 Hz
Number Of Input Connectors 1 hard wire 5-wire (3P + N + E)
Input Voltage Limits 340...460 V 400 V
Maximum Input Current 442 A
Switching Current Capacity 630 A
Max Short Time Withstand 200 kA
Current
Input Harmonic Distortion Less than 3 % for full load
Input Protection Type 3-pole circuit breaker
Inrush Current 200 A peak
Load Power Factor 0.9
Input Power Factor At Full Load 1
Output
Maximum Configurable Power In 270000 W
W
Harmonic Distortion Less than 2 %
Output Frequency 50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
Crest Factor 2.5 : 1
Wave Type Sine wave
Output Harmonic Distortion < 2% linear load and < 3% non-linear load
Required Output Current 433 A
Protection
Neutral Output Current 563 A
Bypass Type Built-in maintenance bypass
2 21 May 2024
Maximum Output Current 1281 A
Maximum Configurable Power In 300000 VA
Va
Conformance
Product Certifications CE
LCIE
Standards EN 60950
EN/IEC 62040-2
EN/IEC 62040-3
ISO 14001
ISO 9001
VFI-SS-111
Environmental
Ambient Air Temperature For 0…35 °C
Operation
Relative Humidity 20…80 %
Operating Altitude 0...3333 ft
Ambient Air Temperature For -25…40 °C
Storage
Storage Relative Humidity 20…80 %
Storage Altitude 0.00…9144.00 m
Acoustic Level 70 dBA
Ip Degree Of Protection IP20
Communications & Management
Free Slots 1
Preinstalled Device Network management card 2 with environmental monitoring, out of band access and
Modbus - Schneider
Control Panel Multifunction LCD status and control console
Emergency Power Off Yes
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 203 cm
Package 1 Width 96 cm
Package 1 Length 152 cm
Package 1 Weight 980 kg
Pallet Unit Layers 1
Pallet Layers 1
Contractual warranty
Warranty 1 year repair or replace