PRODUCT-DETAILS
AX18-30-10-80
AX18-30-10-80 220-230V50Hz/230-240V60Hz
Contactor
General Information
Extended Product Type AX18-30-10-80
Product ID 1SBL921074R8010
EAN 3471522395801
Catalog Description AX18-30-10-80 220-230V50Hz/230-240V60Hz Contactor
AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits
up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1
Long Description
built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for
front or side mounting and a wide range of accessories.
Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
Popular Downloads
Instructions and Manuals 9AKK107492A7057
Dimensions
AX18-30-10-80 2
Product Net Width 44 mm
Product Net Depth / 74 mm
Length
Product Net Height 74 mm
Product Net Weight 0.326 kg
Technical
Number of Main Contacts 3
NO
Number of Main Contacts 0
NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 0
Contacts NC
Rated Operational Voltage Auxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f) Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 28 A
Thermal Current (I th ) acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current (690 V) 40 °C 27 A
AC-1 (I e ) (690 V) 70 °C 20 A
(220 / 240 V) 55 °C 25 A
Rated Operational Current (220 / 230 / 240 V) 55 °C 18 A
AC-3 (I e ) (380 / 400 V) 55 °C 18 A
(415 V) 55 °C 18 A
(440 V) 55 °C 12 A
(500 V) 55 °C 12 A
(690 V) 55 °C 9 A
Rated Operational Power (220 / 230 / 240 V) 4 kW
AC-3 (P e ) (380 / 400 V) 7.5 kW
(415 V) 9 kW
(440 V) 5.5 kW
(500 V) 7.5 kW
(690 V) 7.5 kW
Rated Operational Current (220 / 240 V) 4 A
AC-15 (I e ) (24 / 127 V) 6 A
(400 / 440 V) 2 A
(500 V) 2 A
(690 V) 2 A
(380 / 440 V) 3 A
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 145 A
Withstand Current (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 28 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Maximum Electrical (AC-1) 600 cycles per hour
Switching Frequency (AC-15) 1200 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Rated Operational Current (110 V) 1.1 A / 121 W
DC-13 (I e ) (220 V) 0.55 A / 121 W
(400 V) 2.8 A / 134 W
(500 V) 2 A / 144 W
AX18-30-10-80 3
(125 V) 1.1 A / 138 W
(24 V) 6 A / 144 W
(250 V) 0.55 A / 138 W
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
(U i )
Rated Impulse Withstand 6 kV
Voltage (U imp )
Maximum Mechanical 3600 cycles per hour
Switching Frequency
Rated Control Circuit 50 Hz 220 ... 230 V
Voltage (U c ) 60 Hz 230 ... 240 V
Operate Time Between Coil De-energization and NC Contact Closing 9 ... 16 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type Screw Terminals
Technical UL/CSA
General Use Rating (600 V AC) 30 A
UL/CSA
Horsepower Rating (120 V AC) Single Phase 1 Hp
UL/CSA (240 V AC) Single Phase 3 Hp
(200 ... 208 V AC) Three Phase 5 Hp
(220 ... 240 V AC) Three Phase 5 Hp
(440 ... 480 V AC) Three Phase 10 Hp
(550 ... 600 V AC) Three Phase 15 Hp
Tightening Torque Auxiliary Circuit 9 in·lb
UL/CSA Control Circuit 9 in·lb
Main Circuit 9 in·lb
Environmental
Ambient Air Temperature Close to Contactor for Storage -60 ... +80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Near Contactor for Operation in Free Air -40 ... +70 °C
Climatic Withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating 3000 m
Altitude Permissible
RoHS Status Following EU Directive 2002/95/EC August 18, 2005 and amendment
Certificates and Declarations (Document Number)
CB Certificate 9AKK107492A7072
CCC Certificate 9AKK107492A7089
CCS Certificate 9AKK107492A7096
CQC Certificate CQC2013010304646608
Declaration of Conformity 2020980304001066
- CCC
Declaration of Conformity 1SBD250011U1000
- CE
AX18-30-10-80 4
Instructions and Manuals 9AKK107492A7057
RoHS Information 1SBD251301E1000
Container Information
Package Level 1 Units 1 piece
Package Level 1 Width 48 mm
Package Level 1 Depth / 78 mm
Length
Package Level 1 Height 79 mm
Package Level 1 Gross 0.34 kg
Weight
Package Level 1 EAN 3471522395801
Package Level 2 Units 30 piece
Package Level 2 Width 240 mm
Package Level 2 Depth / 295 mm
Length
Package Level 2 Height 145 mm
Package Level 2 Gross 10.2 kg
Weight
Classifications
Object Classification Code Q
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
UNSPSC 39121529
IDEA Granular Category 4755 >> Contactors
Code (IGCC)
E-Number (Finland) 3707326
Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors