KA001A/05/e/03.
02
t-switch ATT11
Flow Limit Switch for Liquids and Gases
Contents
Safety Notes Handling Mounting and Installation Electrical Connection Operation DIL Switch Explanations Quick Set-up Guidelines Set-up Explanation Set-up Procedure: Set Zero Flow Set Maximum Flow Set Setpoint (AUTO) Set Setpoint (MANUAL) Set Medium Selection Set Relay Mode Diagnostics/Error Codes Technical Data Contact Addresses 17 18 19 20 21 21 22 23-24 25-26 3 3 4-10 11 12 13-14 15 16
Safety Notes
The t-switch ATT11 is designed for flow limit detection in liquids and gases. The ATT11 should be installed, connected, commissioned, operated and maintained by qualified and authorised personnel only, under strict observance of these operating instructions, any relevant standards, legal requirements and where appropriate, the certificate. Do not attempt to install or remove the instrument under pressurised conditions.
Handling
Hold by housing or extension tube; do not hold by sensor.
Place sensor end up. Sensor impact may cause damage.
Mounting and Installation
Guidelines for Threaded Process Connections
BSP 3/4" (G) Use appropriately sized sealing washer.
3/4" NPT Use a suitable thread tape to achieve a reliable seal.
Always use a spanner to tighten the t-switch process connection. Do not use housing to turn.
Note For other types of process fittings follow standard good working practices.
Mounting and Installation
Sensor Orientation Markings
Every process connection has an orientation mark stamped on it. The locations of these marks are shown below and for optimum performance it is important that it is facing the flow.
Mounting and Installation
Sensor Orientation and Flow Direction It is important that the sensor is installed, such that the orientation mark is positioned upstream to the flowing fluid.
If the sensor is not installed as above it may affect the performance of the instrument.
Note Welding instructions are provided with each sensor and care should be taken to read them prior to installation.
Mounting and Installation
Insertion Depth For optimum measuring performance the active area should be positioned anywhere between 5% and 50% of the internal pipe diameter. The sensor tip should be in contact with the medium at all times.
5%
10%
50%
50%
For pipe diameters <DN250
For pipe diameters DN250
Each form of process connector has an orientation mark that should or = to sign be positioned in line facing the oncoming flow.
5 Flow Direction 5
Mounting and Installation
Vertical Pipeline Flow Direction
Liquid Gas Liquid Gas
Horizontal Pipeline Positioning
LIQUID GAS LIQUID (Partially Full)
LIQUID GAS
LIQUID GAS
LIQUID GAS LIQUID (Dirty)
Mounting and Installation
Good installation Practice Summary
Avoid installing in areas of extreme flow turbulence. For example; Directly after bends or expansions/reductions.
>10 dia
>2 dia
Directly downstream of isolation and control valves especially if partially opened.
>50 dia
>2 dia
Directly after pumps, fans and compressors.
>25 dia
>2 dia
Note All downstream dimensions provided are to be used as a guideline only and whenever possible greater dimensions should be considered.
Mounting and Installation
Sanitary Sensor Positioning (EHEDG/3A)
Standard Version
Extended Version
Sanitary Sensor Mounting Guideline (EHEDG/3A) It is the responsibility of the user to ensure that the volume enclosed by the mounting boss has sufficient dimensions to ensure adequate cleaning takes place. Typically the height should be kept to less than one third of the diameter of the boss (H 1/3D). For example (in mm)
DN40 DN50 D 42.7 54.8 H 14.2 18.2
H D
Guidelines provided relate to the dimensions of the mounting boss and not the process pipe!
10
Electrical Connection
1 2 3 4 5 6 7 8
OFF ON AUTO MANUAL
LCD
1 Power 2
Warning!
Fuse 0.5A
Fuse 0.5A
Power supply u: 18-30V AC/DC
PE
(Ground)
Output Potential-free contact 24V DC @ 0.5A 120V AC @ 0.5A
Note
+ 1 2 3
For AC operation terminals 1+2 are not polarity sensitive.
In order to meet EMC requirements, screened or shielded cable is recommended. The screen or shield should be earthed at the sensor end only.
11
Operation
DIL Switches (Dual in Line) The dual-in-line (DIL) switches are used to configure the following parameters within the device. Zero Flow Display socket Maximum Flow Setpoint LED for Medium (liq/gas) Switchpoint/Error Selection Indication Relay Setpoint Mode
ATT11 : t-switch
1 2 3 4 5 6 7 8
OFF ON AUTO MANUAL
8 DIL Programming Switches
LCD
1 +
Power
LED (Light Emitting Diode) Illuminated when measured flow above setpoint. Off when measured flow below setpoint. Flashes to indicate an error.
LCD (Liquid Crystal Display) Optional Used to indicate flow as a percentage of the maximum. Also displays programming information and status/error codes. The display is not essential for programming.
12
DIL Switch Explanations
The operation of DIL 1-4 depends on the position of DIL 8.
If DIL 8 = AUTO Then DIL 1-4 are used for AUTOLOAD features. AUTOLOAD is the means by which actual process flow conditions can be sampled and stored in memory, as either Zero Flow, Maximum Flow or Setpoint. Each parameter has a designated DIL switch combination as described on the following page.
If DIL 8 = MANUAL Then DIL 1-4 are used to select a setpoint from a table of available values (%). Each value has a designated DIL switch combination (see page 19). DIL 8 is used to set the operation mode of DIL 1-4. DIL 7 is used to configure the relay switching operation. DIL 5 and 6 are used to select the medium and its appropriate calibration curve. DIL 1-4 are used to set all parameters related to flow i.e. zero flow, maximum flow and setpoint.
13
DIL Switch Explanations
All of the AUTOLOAD features and their corresponding DIL switch combinations are shown below. (DIL Switch 8 = Auto)
DIL 1 OFF OFF-ON-OFF OFF-ON-OFF OFF-ON-OFF OFF-ON-OFF ON DIL 2 OFF ON OFF OFF ON ON DIL 3 OFF OFF ON OFF ON ON DIL 4 OFF OFF OFF ON ON OFF Description Normal Run Mode Autoload Zero Flow Autoload Maximum Flow Autoload Setpoint Restore Defaults View Autoload Status Value
DIL 1 Operation Toggling of DIL 1 (off-on-off) within 2.5 seconds initiates the relevant AUTOLOAD functions selected by the positions of DIL 2-4. This action causes the instrument to sample the process flow signal for 3 seconds and store it in the microprocessor memory. Restore Defaults To clear all stored AUTOLOAD values set DIL switch positions to configuration shown in above table. Status (display only) When the DIL switches are set to View Autoload Status a code will appear on the display (if fitted). Each digit represents one of the three AUTOLOAD parameters. 0 and 1 represent no data stored and data stored respectively. e.g. S110 zero and max. stored, but not setpoint.
Displayed Status Values S000 S1XX SX1X SXX1 Description Factory Defaults Zero Autoloaded Maximum Autoloaded Setpoint Autoloaded
14
Quick Set-up Guidelines
These instructions are intended to allow a first time user to set up a flow switch to meet it's basic requirement. Ensure that the device is fitted with appropriate sensor (flat face = liquid, probe = gas). AUTOLOAD Zero This function is used to set the zero-point at operating conditions with no flow. This operation is crucial to the operation of the device and must be carried out every time, a) a new device is installed. b) the process changes significantly. c) the sensor is restored to factory defaults. AUTOLOAD Maximum (Optional) This function is used to set an actual process flow as the 100% flow value. This action will, a) allow the optional display to indicate a meaningful value (%). b) assign a meaningful range to the MANUAL setpoints. Setpoint There are two alternative methods for selecting the setpoint. Option 1) AUTOLOAD Setpoint This function is used to set a setpoint at an actual process flow anywhere between zero and maximum. Using AUTOLOAD to set the setpoint provides the best resolution. Option 2) MANUAL Setpoint This function is used to set a setpoint at fixed percentage intervals up to 90% of the maximum flow value. The available values are shown in the table on page 20. The values in the table refer to the factory default range or, if the AUTOLOAD max is used, the users maximum flow range.
15
Set-up Explanation
There are basically two set-up procedures. They are,
Option 1
(2) AUTOLOAD Max Flow
Signal
(3) AUTOLOAD Setpoint
(Step1) AUTOLOAD Zero
Flow
Option 2 (2) AUTOLOAD Max Flow
Signal
(3) Set MANUAL Setpoint
Flow (Step1) AUTOLOAD Zero
16
Set-up Procedure Set Zero Flow
This function is used to set the zero-point and appropriate operating curve. 1) Ensure switch is installed at process operating conditions with no flow. 2) Set DIL switches as shown.
1 2 3 4 5 6 7 8
(X = Position not relevant) 3) Sample flow signal by toggling DIL 1 (OFF-ON-OFF within 2.5 seconds). If a display is fitted it will show ZERO for 3 seconds during sampling or an error message will be displayed. 4) If no further AUTOLOAD functions are required, return DIL switches to NORMAL RUN MODE as below otherwise proceed to next AUTOLOAD function.
1 2 3 4 5 6 7 8
(X = Position not relevant) The LED will change state during sampling, returning to its initial state at the end of the sampling period. If the LED flashes the AUTOLOAD has not been accepted (see page 22).
17
Set-up Procedure Set Maximum Flow
This function is used to set an actual process flow condition as the 100% flow value. 1) Ensure switch is installed at process conditions with flow running at maximum. 2) Set DIL switches as below.
1 2 3 4 5 6 7 8
(X = Position not relevant) 3) Sample flow signal by toggling DIL 1 (OFF-ON-OFF within 2.5 seconds). If a display is fitted and the AUTOLOAD has been successful it will show FULL for 3 seconds during sampling. 4) If no more AUTOLOAD functions are required return DIL switches 1-4 to NORMAL RUN MODE as below otherwise proceed to next AUTOLOAD function.
1 2 3 4 5 6 7 8
(X = Position not relevant) The LED will change state during sampling, returning to its initial state at the end of the sampling period. If the LED flashes the AUTOLOAD has not been accepted (see page 22).
18
Set-up Procedure Set Setpoint (AUTO)
This function is used to set a setpoint at an actual process flow anywhere in between the zero and maximum flow settings. 1) Ensure switch is installed at process conditions with flow running at required setpoint. 2) Set DIL switches as below.
1 2 3 4 5 6 7 8
(X = Position not relevant) 3) Sample flow signal by toggling DIL 1 (OFF-ON-OFF within 2.5 seconds). If a display is fitted and the AUTOLOAD is successful it will show SON for 3 seconds followed by the value for 3 seconds during sampling. 4) In order to utilise the AUTOLOADed setpoint return DIL 1-4 to the NORMAL RUN MODE as below and leave DIL 8 = AUTO.
1 2 3 4 5 6 7 8
(X = Position not relevant) The LED will change state during sampling, returning at the end of the sampling period. If the LED flashes the AUTOLOAD has not been accepted (see page 22).
19
Set-up Procedure Set Setpoint (MANUAL) DIL 8 = Manual
This function is used to set a setpoint as a percentage of the maximum using DIL switch combinations from the table shown.
DIL 1 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON DIL 2 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON DIL 3 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON DIL 4 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Setpoint (% of Maximum) 5 10 15 20 25 30 35 40 45 50 55 60 65 70 80 90
1) In order to utilise the MANUAL setpoint DIL 8 must be left set to MANUAL. If a display is fitted it will show Son for 3 seconds followed by the value for 3 seconds after any change of DIL 1-4.
Important Note: Zero and maximum values can be set using Autoload function and will remain active if setpoint is set by using Manual operation.
20
Set-up Procedure Set Medium Selection
This function is used to select a calibration curve for either liquid or gas. This operation is independent of the position of DIL8.
DIL 5 OFF OFF ON ON DIL 6 OFF ON OFF ON Selection L1 L3 A2 A3 Flat Face X (liquids only) DO NOT USE DO NOT USE DO NOT USE DO NOT USE X (gas only) Probe
If a display is fitted it will show F1 for 3 seconds followed by the selected curve for 3 seconds after any change of DIL 5-6.
Set Relay Mode
This function is used to configure the relay action at the switching point. This operation is independent of the position of DIL8.
DIL 7 OFF ON Mode Energise at setpoint De-Energise at setpoint
If a display is fitted it will show either EnEr or dEEn for 3 seconds after changing DIL 7.
21
Diagnostics/Error Codes
Sensor Faults E001 E002 Output Faults E010 Power Faults E100 E200 E300 Internal Power Fault Power Supply out of range E100 + E200 Relay not functioning Sensor Open Circuit Sensor Short Circuit
Action Replace sensor Replace sensor
Remove electronic insert, check board connections.
AUTOLOAD Errors Err1 AUTOLOAD Zero Err2 AUTOLOAD Max. Err3 AUTOLOAD Setpoint
Cause Zero being set is higher than FS FS being set below zero value Being set above or below FS or zero
LED Operation (normal running) LED on for 2 sec off for 0.25 sec LED off for 2 sec on for 0.25 sec
Cause Measurement over-range Measurement below zero setting
22
Technical data
Process Conditions Nominal Process Diameters: DN25 ... 1000 Process Pressure Range: 25 Bar g (Process fitting dependent) Process Temperature Range: -10 to +80C Materials Meter Body: 1.4404/1.4435/316L Transducers: 1.4404/1.4435/316L Polyester Housing: PBT-FR (polyester) with cover in PBT-FR or with transparent cover in PA 12, Seal of cover; EPDM Steel Housing: 1.4301 (AISI 304), seal of cover silicone Cable Gland: Polyamide Process Connections Parallel thread BSP 3/4" (includes brass 3/4" compression fitting for insertion sensors only) Tapered thread 3/4" NPT (includes brass 3/4" compression fitting for insertion sensors only) Sanitary coupling DN40, 50 to DIN 11851 Varivent DN50 to factory standard Tuchenhagen Triclamp 1 1/2", 2" to ISO 2852 Aseptic coupling DN50 to DIN 11864 Performance Limits Accuracy: 5% of full scale Repeatability: 1% of full scale Time Response Flat Face: 5 sec rising, < 5 sec falling Time Response Probe: 15 sec rising, 10 sec falling Flow Ranges Liquid: 0-3m/sec ref. to water Flow Ranges Gas: 0-50Nm/sec ref. to air
23
Human interface Electronic Insert: 8 DIL switches for commissioning Red LED to indicate switching status, flashes under fault condition Optional Display: 4 numeric characters with bar graph Electrical Power Supply: 18-30V DC / AC (50/60 Hz) Power Consumption: <3W Relay Output: Selectable Normally Closed (NC) or Normally Open (NO) (NO as factory default) Environment Storage Temperature Range: -20 to +80C (without LCD) Ambient Temperature Range: -10 to +65C (without LCD) Degree of Protection: Polyester and steel housings: IP66 to EN 60529 Vibration Resistance: Up to 1g, 10....150Hz to IEC 60068-2-6 Shock Resistance: to IEC 60068-2-31 Electromagnetic Compatibility (EMC): IEC 801 part3: E = 10V/m (30MHz...1GHz) Approvals EHEDG, all wetted materials FDA listed. Meets the requirements of 3A. Approvals Pending CSA General Approval, FM General Approval.
24
Contacts
Argentina Endress+Hauser (Argentina) S.A. +54 (11) 45227970 +54 (11) 45227909 endress_argentina@arnet. com.ar Australia Endress+Hauser (Australia) PTY.LTD. +61 (2) 97747444 +61 (2) 97744667 Austria Endress+Hauser GmbH +43 (1) 88056-0 +43 (1) 88056-335 [email protected] Belgium Endress+Hauser S.A./N.V. +32 (2) 2480600 +32 (2) 2480553 [email protected] Bosnia-erzegowina Endress+Hauser Instruments International +387 (33) 650409 +387 (33) 467740 [email protected] Brazil Samson Endress+Hauser Ltda. +55 (11) 50313455 +55 (11) 50313067 [email protected]
Canada Endress+Hauser (Canada) Ltd. +1 (905) 6819292 +1 (905) 6819444 [email protected] Chile Endress+Hauser (Chile) Ltd. +56 (2) 3213009 +56 (2) 3213025 [email protected] China Endress+Hauser (Shanghai) Instrumentation Co. Ltd. +86 (21) 54902300 +86 (21) 54902303 [email protected] China Endress+Hauser (Beijing) Instrumentation Com.LTD +86 (10) 65882468 +86 (10) 65881725 [email protected] Croatia Endress+Hauser GmbH+Co. Zagreb Office +385 (1) 6637785 +385 (1) 6637823 [email protected] Czech Republic Endress+Hauser (Czech Republik) s.r.o. +420 (2) 66784200 +420 (2) 66784179 [email protected]
Denmark Endress+Hauser A/S +45 (70) 131132 +45 (70) 132133 [email protected] Finland Metso Endress+Hauser Oy +358 (9) 204 83 160 +358 (9) 204 83 161 [email protected] France Endress+Hauser S.A. +33 (389) 696768 +33 (389) 694802 [email protected] Germany Endress+Hauser Messtechnik GmbH+Co. +49 (7621) 97501 +49 (7621) 975555 [email protected] Hong Kong Endress+Hauser (H.K.) Ltd +852 25283120 +852 28654171 [email protected] Hungary Endress+Hauser (Budapest) Magyarorszag +36 (1) 4120421 +36 (1) 4120424 India Endress+Hauser (India) Pvt. Ltd. +91 (22) 6938333 +91 (22) 6938330 [email protected]
25
Ireland Flomeaco Endress+Hauser Ltd. +353 (45) 868615 +353 (45) 868182 [email protected] Italy Endress+Hauser S.p.a. +39 (02) 92106421 +39 (02) 92107153 [email protected] Japan Sakura Endress Co. Ltd. +81 (422) 540611 +81 (422) 550275 [email protected] Korea Endress+Hauser (Korea) Co. Ltd. +82 (2) 6587200 +82 (2) 6592838 [email protected] Malaysia Endress+Hauser (M) Sdn. Bhd. +60 (3) 7464848 +60 (3) 7468800 [email protected] Mexico Endress+Hauser (Mxico)S.A. de .V. +52 (5) 568-2405 +52 (5) 568-7459 [email protected] Netherlands Endress+Hauser B.V. +31 (35) 6 95 86 11 +31 (35) 6 95 88 25 [email protected]
Norway Endress+Hauser A/S +47 32 85 98 50 +47 32 85 98 51 [email protected] Philippines Endress+Hauser Philippines Inc. +63 (2) 6 38 80 41 +63 (2) 6 38 80 42 Poland Endress+Hauser Polska Sp. z o.o. +48 (22) 7 20 10 90 +48 (22) 7 20 10 85 [email protected] Rep. South Africa Endress+Hauser (Pty.) Ltd +27 (11) 2628000 +27 (11) 2628062 [email protected] Russia Endress+Hauser GmbH+Co +7 (095) 1587564 +7 (095) 1589871 [email protected] Singapore Endress+Hauser (S.E.A.) Pte. Ltd +65 5 66 82 22 +65 5 66 68 48 [email protected] Slovenia Endress+Hauser Slovenija) D.O.O. +386 (61) 5192217 +386 (61) 1592298 [email protected]
Spain Endress+Hauser S.A. +34 (93) 4 80 33 66 +34 (93) 4 73 38 39 [email protected] Sweden Endress+Hauser AB +46 (8) 55 51 16 00 +46 (8) 55 51 16 55 [email protected] Switzerland Endress+Hauser Metso AG +41 (61) 7 15 75 75 +41 (61) 7 11 16 50 [email protected] Thailand Endress+Hauser Thailand) Ltd. +66 (2) 9 96 78 11-20 +66 (2) 9 96 78 10 United Kingdom Endress+Hauser Ltd +44 (161) 2 86 50 00 +44 (161) 9 98 18 41 [email protected] USA Endress+Hauser Systems & Gauging Inc. +1 (770) 447 92 02 +1 (770) 447 57 67 [email protected] USA Endress+Hauser Inc. +1 (317) 5 35 71 38 +1 (317) 5 35 84 98 [email protected]
26
KA001A/05/e/03.02