5310
DEEP SEA ELECTRONICS J1939 ENABLED
AUTO-START
MODULE
UL508 Issue 1
pending 02/12/03 AM
FEATURES
DESCRIPTION
The Model 5310 is an Autostart Control
Ø CANBus option to connect Module. The module is used to
to the industry standard SAE automatically start a generator set, upon
J1939 ‘Eco friendly’ engine application of a remote signal or by manual
management systems providing control. The module also provides
engine protection and indication of operational status and fault
instrumentation without requiring conditions, automatically shutting down the
additional senders. genset and indicating failures by means of
Ø Comprehensive remote an LCD display.
communication via optional Alterations to the system are made using
RS232 port. Provides RS232 the 5xxx PC configuration software in
Modem link to PC via either PSTN conjunction with the 810 interface. This
line or GSM network (using a interface also provides real time diagnostic SPECIFICATION
suitable modem). The module can facilities.
also signal engineers via their cell DC Supply:
Selected timers and alarms can be altered 8V to 35V Continuous.
phones using the GSM SMS by the customer or site engineer, via the
messaging system to advise of front panel. This can be PIN code Cranking Dropouts:
system alarms. protected to prevent unauthorised access. Able to survive 0V for 50mS, providing
Ø Optional RS485 ‘Modbus’ output. supply was at least 10V before dropout
Easy push button control and supply recovers to 5V. This is
Using industry standard
Operation of the module is via pushbutton achieved without the need for internal
communication protocol allows
controls (with security locking facility) batteries.
full system integration into new
mounted on the front panel with
and existing building Max. Operating Current:
STOP/RESET, AUTO, MANUAL and
management and control 12V – 400mA
START pushbuttons. The first three
schemes.
pushbuttons feature LED ‘selected’ 24V – 200mA
Ø Engine diagnostic information indications. Further pushbuttons provide
removes the need for both service Sleep Mode Current:
LCD DISPLAY SCROLL, LAMP TEST and
equipment and cryptic diagnostic 12V – 70mA
MUTE functions.
lamp (when used in conjunction 24V – 45mA
with J1939 engines) Microprocessor control
Standby Current (when in auto):
The module features 16-Bit microprocessor
Ø LCD 4-line text based display to 12V – 230mA
control and a comprehensive list of timers
provide ‘at-a-glance’ diagnosis of 24V – 120mA
and pre-configured sequences. This
fault conditions, instrumentation allows demanding industry specifications to Auxiliary Outputs 1-3:
and operating state. be achieved. Relay outputs 5A DC at supply voltage.
Ø Comprehensive PC configuration Switches to battery negative when active.
Accessed via the LCD DISPLAY SCROLL
and status monitoring using 5xxx Dimensions:
push-buttons, the 5310 module provides
PC software.
the following instrumentation displays: 240mm x 172mm x 57mm
Ø PIN number protected front panel (9½” x 6¾” x 2¼”)
programming of selected trip Generator Instruments:
points and timers, allows field Volts, Hz, Amps, kW, kVA, cosθ Panel cutout:
changes to be made to the 220mm x 160mm
Engine Instruments: (8.7” x 6.3”)
module settings. RPM, Oil Pressure, Coolant Temperature,
Ø Built in exercise timer. Hours Run, Charging voltage, Battery Operating Temperature Range:
Volts. -30°C to +70°C
Ø ‘Sleep mode’ to ensure very low
battery power usage when in SAE J1939: Enclosure protection: IP55 with
“Off” mode. Enhanced instrumentation and Engine optional gasket
Ø Multiple LCD languages (English, ECU diagnostics via industry standard SAE Engine ECU interface:
French, Spanish, German etc) J1939 interface when used in conjunction
possible. with J1939 engine ECU. SAE J1939 CANbus
Ø Automatic and Manual operation
modes. Deep Sea Electronics plc. reserve the right
to change specification without notice.
Ø Six configurable auxiliary inputs
for connection to external fault
detection equipment. Deep Sea Electronics Plc. Deep Sea Electronics inc.
Highfield House, Hunmanby Industrial Estate, 5301 E. State St. – Suite 202
Ø Three configurable outputs to North Yorkshire. YO14 0PH. Rockford, Illinois 61108
help produce complex ENGLAND U.S.A.
applications. Tel:+44 (0)1723 890099. Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303. Fax: +1 (815) 316-8708
Ø Integral load switch control Email: [email protected] Email: [email protected]
capability. Web: www.deepseaplc.com Web: www.deepseausa.com
DIMENSIONS
172mm [6 3/4"]
57mm [2 1/4"] 240mm [9 1/2"]
Panel cut-out 220mm x 160mm (8.7” x 6.3”)
TYPICAL CONNECTIONS