Fs DPR 2000-Energe en
Fs DPR 2000-Energe en
DPR 2000
Description
The DPR 2000 rectifier is a new 96 %, high efficiency
product, and part of Delta’s new EnergE Series. Com-
bined with market’s leading power density of this
product family is ensuring cutting edge total energy
efficiency. This rectifier is optimal for 1U solutions and
provides up to 8 kW in one shelf. Compact, CAPEX
effective solutions for a higher demand can be pro-
vided with the DPR 2900 product series.
Installation is simplified as all Delta rectifiers have
their connectors at rear and are hot-pluggable. Retrofit Delta rectifiers are market leaders in power
is easy ensuring new level efficiency.
density offering solutions for compact space and
weight requirements. In addition to that, the
Main features highest efficiency ensures lower total energy
• OPEX & energy saving – leading efficiency 96 % consumption and leads to smaller environmental
• Space saving – world’s leading packaging of high
efficiency technology – up to 8 kW in 1U shelf footprint.
• Power density 23.5 W / in³
• Easy retrofit to existing DPR 2700 Series installa-
tions With a focus on continuous improvement of total
• Integrated AC overvoltage protection cost of ownership, Delta’s total cost of ownership
concept covers the highest energy efficiency and
Applications power density rectifiers, advanced controlling
DPR 2000 is used in Delta InD and OutD systems for: and monitoring. Leading system level efficiency
• Network base stations
is unconditional way to reduce environmental
• Wireless applications
• Fixed line applications, data communications footprint and help reducing both CAPEX and
OPEX. The EnergE rectifiers meet the new stan-
dard of energy efficiency.
•
Rectifier
DPR 2000
Technical specifications
1. Input 3. General
Mains voltage 80 - 300 Vrms Efficiency 96.2 %
Mains frequency 50 / 60 Hz Power density 23.5 W / in3
Harmonic distortion (THD) 5% Control and monitoring PSC 3
EMI (conducted) EN 55022, class B User interface Status indication
Protection Internal fuse 16 A 125.5 x 41.0 x 269.9 mm
Dimensions (W x H x D)
4.9 x 1.6 x 10.6 in
AC over voltage protection Incl. loss of neutral
Weight 2.0 kg / 4.4 lb
Standards
2. Output • Safety EN / IEC 60950
UL 60950
Nominal system voltage 54 V
CAN / CSA - C22.2
Operating voltage range 40 - 59.5 V • EMI (radiated) EN 55022, class B
Power limitation 2000 W • Environment RoHS compliant
Current limitation 42 A Cooling Fan cooled
Overvoltage protection 59 V Acoustics 50 dB (A)
EMI (conducted) EN 55022, class A -40 to +75 °C
Operating temperature
Load sharing Yes -40 to +167 °F
Protection Internal fuse
Subject to change without notice.
Ordering information
DPR 2000B-48
Description
ESR 48/40B F
www.deltapowersolutions.com
•
FS_DPR2000-EnergE_en.doc / Rev. 02 / RPä 3791280800