Honeywell Vista 32FB User Manual
Honeywell Vista 32FB User Manual
Programming Guide
Programming Field Settings for UL864 Compliance 2 Alpha Descriptor Vocabulary ..................................30
Recommended Programming Procedure .................6 Relay Voice Descriptors and Custom Word
Program Field Index .................................................7 Substitutes Vocabulary........................................39
VISTA-32FB Programming Form .............................8 System Layout Worksheets ....................................40
Partition-Specific Fields ..........................................14 Output Devices Worksheets ...................................47
Programming With #93 Menu Mode.......................16 Scheduling Menu Prompts......................................53
5800 Series Transmitters Loop Designations ........20 Scheduling Worksheets ..........................................54
–2–
Program feature or option Permitted in Possible settings Settings permitted in UL 864
UL864? Y/N
∗80 ZONE TYPE RESTORES N 0 = disable Must be set to “1” (enable) for zone
FOR TYPES 9, 10 & 14 1 = enable type 9.
1∗12 PROGRAM Y 0 = no Must be set to “1” (yes).
NOTIFICATION SIGNAL 1 = yes
1∗13 SYSTEM SENSOR N 0=use neither Zone 1 or Zone 2 inputs Not Used. Must be set to “0”.
REVERSING RELAY 1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
1∗18 AFFECTS LOBBY N 0 = disable Must be set to “0” (disabled) for
1 = enable partition 1.
1∗19 ARMS LOBBY N 0 = disable Must be set to “0” (disabled) for
1 = enable partition 1.
1∗22thru 1∗25 CROSS-ZONING N Enter 001-032 Must be set to “000,000” (disabled)
PAIRS (1 – 4) Enter 000,000 to disable for fire zones.
1∗28 RF TRANSMITTER LOW N 0 = disarmed state only Must be set to “1” (both armed and
BATTERY SOUND 1 = both armed and disarmed states disarmed states).
1∗29 RF TRANSMITTER LOW N 0 = disable Must be set to “1” (enable).
BATTERY REPORTING 1 = enable
1∗30 RF RECEIVER N Enter 02–15 times 2 hours (4–30 Maximum is 02 (4 hours) for fire
SUPERVISION CHECK-IN hours) installations.
INTERVAL Enter 00 to disable receiver
supervision
1∗31 RF TRANSMITTER N Enter 02–15 times 2 hours (4–30 Maximum is 02 (4 hours) for fire
CHECK-IN INTERVAL hours) installations.
Enter 00 to disable transmitter
supervision
1∗35 ACCESS CONTROL N 0 = disable Not used. Must be set to “0”.
DIALER ENABLES 1 = enable
1∗44 WIRELESS KEYPAD N 0 = disable Not used. Must be set to “0”.
TAMPER DETECTION 1 = enable
1∗45 EXIT DELAY SOUNDING N 0 = disable Must be set to “0” (disable) for
(PARTITION SPECIFIC) 1 = enable partition 1.
1∗48 WIRELESS KEYPAD N 0 = none Not used. Must be set to “0”.
ASSIGNMENT 1-2 = partition number
1∗49 SUPPRESS TX N 0 = disable Must be set to “0” (disable).
SUPERVISION SOUND 1 = enable
1∗53 DISABLE DOWNLOAD N 0 = callback required Must be set to “0” (callback
CALLBACK 1 = no callback required required).
1∗57 5800 RF BUTTON N 0 = disable Must be set to “0” (disable).
GLOBAL ARM 1 = enable
1∗58 5800 RF BUTTON FORCE N 0 = disable Must be set to “0” (disable).
ARM 1 = enable
1∗60 ZONE 5 AUDIO ALARM N 0 = disable Must be set to “0” (disable).
VERIFICATION 1 = enable
1∗72 EVENT LOG PRINTER N 0 = disable Not used. Must be set to “0”.
ONLINE 1 = enable
1∗73 PRINTER BAUD RATE N 0 = 1200 Not used.
1 = 300
1∗76 CONTROL RELAY (PART- N 01-96 = relay number Must be set to “00” (relay not used)
SPECIFIC) 00 = relay not used. for partition 1.
2∗07 AUTO-DISARM DELAY N 00 = no delay. Must be set to “15” (no auto
(PART SPECIFIC) 01-14 times 4 minutes (04-56) delay. disarming) for partition 1.
15 = no auto disarming.
2∗18 ENABLE GOTO FOR THIS N 0 = disable Must be set to “0” (disable) for
PARTITION (partition-specific) 1 = enable partition 1.
2∗21 SUPERVISION PULSES N 0 = disable Not used. Must be set to “00000”
FOR COMMUNICATIONS 1 = enable (disable).
DEVICE
2∗22 DISPLAY FIRE ALARMS N 0 = disable Must be set to “0” (disable) for
OF OTHER PARTITIONS 1 = enable partition 1.
2∗23 DISPLAY BURG, PANIC N 0 = disable Must be set to “0” (disable) for
AND CO ALARMS FOR OTHER 1 = enable partition 1.
PARTITIONS
–3–
Program feature or option Permitted in Possible settings Settings permitted in UL 864
UL864? Y/N
2∗24 DISPLAY TROUBLES OF N 0 = disable Must be set to “0” (disable) for
OTHER PARTITIONS 1 = enable partition 1.
3∗01 EVENTS DISPLAY LOCK N 0 = disable Must be set to “1” (enable).
1 = enable
3∗12 ZN TYPE 18 DELAY USE N 0 = disable Must be set to “0” (disable).
1 = enable
3∗13 FIRE SUPERVISORY N 0 = Trouble on open/Supv on short Must be set to “0”.
RESPONSE TO OPEN/SHORT 1 = Supv on open/Supv on short
(APPLIES TO ZONE TYPE 18)
3∗14 WATERFLOW ALARM N 0 = Silenced by User Code + OFF Must be set to “0” (Silenced by User
SILENCE OPTION 1 = Silenced when zone restores Code + OFF).
3∗16 DELAY FOR ZONE N Enter 01-15 times 2 seconds Must be set to ‘00’ (no delay).
TYPES 17 & 18 Enter 00 for no delay
(Waterflow/Supervisory)
3∗18 EXTENDED DELAY FOR N 0 = no extended delay Must be set to ‘0’ (no extended
ZONE TYPES 17 & 18 Multiplies 1 = multiply delay by 4 delay).
delay in 3∗16 x 4)
3∗19 AUXILIARY INPUT N 0 = disable Must be set to ‘0’ (disable).
ALTERNATE FUNCTION 1 = enable
ENABLE
3∗20 TRIGGER OUTPUTS N 0 = remote keypad sounder Must be set to ‘0’ (remote keypad
FUNCTION SELECTION 1 = keyswitch LEDs sounder).
3∗21 MAXIMUM NUMBER OF Y 1-8 Must be set at 3, 4 or 5.
DIALER ATEMPTS
3∗50 ZONE TYPE RESTORE N 0 = disable Must be set to “1” (enable).
ENABLES FOR TYPES 16-18 1 = enable
3∗55 RESET ON SECOND OFF N 0 = disable Must be set to “0” (disable).
FOR BELL 1 1 = enable
3∗56 RESET ON SECOND OFF N 0 = disable Must be set to “0” (disable).
FOR BELL 2 1 = enable
3∗57 BELL 2 AND AX RELAY N 0 = disable Must be set to “0, 0” (disable).
CONFIRM ARMING DING 1 = enable
3∗59 ENABLE BELL 2 & N 0 = disable Must be set to “0” (disable) if Bell 2
AUXILIARY RELAY CHIME 1 = enable or Aux Relay is used for Fire.
ANNUNCIATION
3∗60 BELL 2 & AUX RELAY Y Enter 01-15 multiplied by 2 minutes. Must be set to “3” (Minimum of 6
TIMEOUT 00 = no timeout. minutes).
3∗82 BURGLARY FEATURES N 0 = disable Must be set to “0” (disable).
ON PARTITION 1 ENABLE 1 = enable
RESTRICTION FOR FIRE Y Yes Restriction for # 70 must be set to
RELAYS No Yes when programming fire relays.
–4–
The purpose of this document is to provide a quick and easy way to program your entire system. A recommended
programming procedure is included, followed by a list of program fields with the corresponding program group they belong to
(system-wide, partition-specific, scheduling, etc.). Two program forms are included. One contains all the programming fields,
and the other contains the partition-specific fields. If you are setting up a single-partition system, the partition-specific fields
become system-wide fields.
Following the program forms are system layout worksheets. We recommend that you use these sheets to plan your system
before programming is performed. If you need further information about specific programming options, see the VISTA-32FB
Installation and Setup Guide.
Make sure that one two-line alpha keypad is connected to the control and is set to device address "00."
Single-Partition System
The system default is for a single-partition system. Use the VISTA-32FB SINGLE PARTITION PROGRAMMING FORM
when programming for single-partition usage. Follow the steps outlined in RECOMMENDED PROGRAMMING
PROCEDURE of this document for proper programming procedure.
Multiple-Partition System
You must enter the number of partitions you are using in data field 2∗00 to set the system for multiple partitions. Use the
VISTA-32FB SINGLE PARTITION and the PARTITION-SPECIFIC PROGRAM FORMS when programming the system
for multiple partitions. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document
for proper programming procedure.
SUMMARY OF PROGRAMMING COMMANDS
• To enter program mode, enter installer code + [8] + [0] + [0]
• To set standard defaults, press ∗97
• To change to next page of program fields, press ∗94
• To return to previous set of fields, press ∗99
• To erase account and phone number field entries, press [∗] + field number + [∗]
• To assign zone descriptors, press #93 + follow menu prompts
• To add custom words, press #93 + follow menu prompts
• To enter Installer's Message, press #93 + follow menu prompts
• To exit program mode, enter ∗99 OR ∗98: ∗99 allows re-access to programming mode by installer code.
∗98 prevents re-access to programming mode by installer code. The only way to re-access programming mode
is by depressing both the [∗] and [#] keys at the same time within 30 seconds of power-up.
Standard default (∗97) values are shown in brackets [ ], otherwise default = 0.
–5–
Recommended Programming Procedure
The following is a step-by-step procedure recommended for programming your VISTA-32FB system.
1. Set the keypads (and other peripheral devices) to the appropriate addresses.
2. Set factory defaults by pressing ∗97.
This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these
addresses.
3. Program system-wide (global) data fields.
Using the programming form as a guide, enter program mode and program all system-wide programming
fields. These options affect the entire system, regardless of partitions. They include control options,
downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for a
listing of the program fields and their function.
Note that field 2∗00 (number of partitions) must be programmed before continuing.
4. Program partition-specific fields.
When the system-wide fields have been programmed, program all partition-specific programming fields by
first pressing ∗91 to select a partition (while still in data field program mode). Then enter the first partition-
specific field number ∗09. When you are finished, the next partition-specific field is automatically displayed.
Partition-specific fields can have different values for each partition. To program the fields for the next partition,
press ∗91, enter the desired partition number, then enter field ∗09. Refer to the MECHANICS OF
PROGRAMMING section in the VISTA-32FB Installation and Setup Guide for detailed instructions.
5. Use #93 Menu Mode for device programming.
Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for each
keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF
receivers, relay modules, and Communicators (7845i-ent).
6. Use #93 Menu Mode for zone programming.
Refer to Zone Programming in this guide to program zone response types, assign right loop zones and
wireless zones, assign zones to partitions, and to program alarm report codes.
7. Use #93 Menu Mode for programming outputs.
Refer to Output Programming in this guide to program desired output operation.
8. Program Communication options.
Refer to System Communication section in the VISTA-32FB Installation and Setup Guide for detailed
instructions. Then use #93 menu mode to program report codes.
9. Use #93 Menu Mode for programming alpha descriptors.
Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer's
message.
10. Use #80 Mode for programming schedules.
Refer to the Scheduling Menu Prompts in the VISTA-32FB Installation and Setup Guide to program
open/close schedules, temporary and holiday schedules, limitation of access schedules, and time-driven
events.
11. Define user access codes.
Refer to User Access Codes in the VISTA-32FB Installation and Setup Guide to program authority level, O/C
reporting option, partition assignments, and wireless key assignments for each user.
12. Exit Programming Mode.
Exit programming mode by pressing either ∗98 or ∗99. Additional entries of ∗99 are required if the exit is being
done from fields 1∗00 and above.
To prevent re-access to programming mode using the Installer's code, use ∗98. The only way to re-access
programming mode is by depressing both the [∗] and [#] keys at the same time within 30 seconds of power-
up.
Exiting by using ∗99 always allows reentry into programming mode using the Installer code. Either way of
exiting allows access via downloading. Note that if local programming lockout is set via downloading,
programming mode cannot be entered at the keypad.
–6–
Program Field Index
On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the
fields on the programming form.
Field Group Field Group Field Group
∗00 System-Wide ∗66 Communications 1∗58 System-Wide
∗08 System-Wide ∗67 Communications 1∗60 System-Wide
∗09 Partition-Specific ∗68 Communications 1∗70 System-Wide
∗10 Partition-Specific ∗69 Communications 1∗71 System-Wide
∗11 Partition-Specific ∗70 Communications 1∗72 System-Wide
∗12 Partition-Specific ∗71 Communications 1∗73 System-Wide
∗13 Partition-Specific ∗72 Communications 1∗74 System-Wide
∗15 System-Wide ∗73 Communications 1∗75 System-Wide
∗16 Partition-Specific ∗74 Communications 1∗76 Partition-Specific
∗17 System-Wide ∗75 Communications 1∗77 System-Wide
∗19 System-Wide ∗76 Communications 2∗00 System-Wide
∗20 System-Wide ∗77 Communications 2∗01 System-Wide
∗22 Partition-Specific ∗79 Communications 2∗02 System-Wide
∗23 Partition-Specific ∗80 Communications 2∗05 Partition-Specific
∗24 System-Wide ∗83 Communications 2∗06 Partition-Specific
∗25 System-Wide ∗84 Partition-Specific 2∗07 Partition-Specific
∗26 Communications ∗85 Partition-Specific 2∗08 Partition-Specific
∗27 Communications ∗87 Partition-Specific 2∗09 Partition-Specific
∗28 System-Wide ∗88 Partition-Specific 2∗10 Partition-Specific
∗29 Partition-Specific ∗89 Communications 2∗11 System-Wide
∗30 Communications ∗90 Partition-Specific 2∗18 Partition-Specific
∗31 Communications 1∗12 System-Wide 2∗19 Partitioning
∗32 Partition-Specific 1∗13 System-Wide 2∗20 Partition-Specific
∗33 Communications 1∗17 System-Wide 2∗21 System-Wide
∗34 Communications 1∗18 Partition-Specific 2∗22 Partition-Specific
∗35 System-Wide 1∗19 Partition-Specific 2∗23 Partition-Specific
∗36 System-Wide 1∗20 System-Wide 2∗24 Partition-Specific
∗37 System-Wide 1∗21 System-Wide 3∗00 System-Wide
∗38 Partition-Specific 1∗22 System-Wide 3∗01 System-Wide
∗39 Partition-Specific 1∗23 System-Wide 3∗12 System-Wide
∗40 Communications 1∗24 System-Wide 3∗13 System-Wide
∗41 System-Wide 1∗25 System-Wide 3∗14 System-Wide
∗42 Communications 1∗26 Partition-Specific 3∗16 System-Wide
∗43 Communications 1∗28 System-Wide 3∗17 System-Wide
∗44 Communications 1∗29 System-Wide 3∗18 System-Wide
∗45 Communications 1∗30 System-Wide 3∗19 System-Wide
∗46 Communications 1∗31 System-Wide 3∗20 System-Wide
∗47 Communications 1∗33 Communications 3∗21 System-Wide
∗48 Communications 1∗34 Communications 3∗30 System-Wide
∗49 Communications 1∗35 Communications 3∗31 System-Wide
∗50 Communications 1∗42 Communications 3∗50 System-Wide
∗51 Communications 1∗43 Partition-Specific 3∗55 System-Wide
∗52 Communications 1∗44 System-Wide 3∗56 System-Wide
∗53 Communications 1∗45 Partition-Specific 3∗57 Partition-Specific
∗54 System-Wide 1∗47 Partition-Specific 3∗59 Partition-Specific
∗56 Communications 1∗48 System-Wide 3∗60 Partition-Specific
∗57 Communications 1∗49 System-Wide 3∗61 System-Wide
∗58 Communications 1∗52 Partition-Specific 3∗82 System-Wide
∗59 Communications 1∗53 System-Wide 3∗85 System-Wide
∗64 Communications 1∗56 System-Wide
∗65 Communications 1∗57 System-Wide
–7–
VISTA-32FB Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (∗97) values are shown in brackets [ ];
otherwise, default = 0.
∗09 ENTRY DELAY #1 [02] | ∗24 IGNORE EXPANSION ZONE TAMPER [0]
00, 02-15 times 15 seconds 1=Ignore; 0=Enable tamper for RF and V-Plex.
Maximum "03" for Commercial Burglary installations. Must be "0" for Commercial Burglary and Commercial Fire
installations if using these devices.
∗10 EXIT DELAY #1 [03] | ∗25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
00, 03-15 times 15 seconds 1=enable; 0=disable
Maximum "04" for Commercial Burglary installations.
∗26 INTELLIGENT TEST REPORTING [0]
1=enable (no report sent if any other report was recently sent);
∗11 ENTRY DELAY #2 [06] | 0=disable (send report at programmed interval, field ∗27)
00, 02-15 times 15 seconds (must be longer than Entry Delay Must be “0” for Commercial Burglary and Commercial Fire
#1). Maximum "03" for Commercial Burglary installations. installations.
–8–
∗35 DOWNLOAD PHONE NO.
∗51 DUAL REPORTING [0]
1=yes; 0=no If used with Spilt Reporting "1" option (1∗34),
alarms and alarm restores go to both primary and secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go
Enter 0-9 for each digit. Enter #11 for ∗, #12 for #, to both, open/close and test messages go to secondary only,
#13 for 2-second pause while all other reports go to primary. If used with Split
Reporting “3” option, fire alarms and fire restores signals go to
∗36 DOWNLOAD ID NO. both, all other reports go to secondary only.
| | | | | | | |
∗52 STANDARD/EXPANDED REPORT FOR PRIMARY
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
[0 0 0 0 0 0]
∗37 DOWNLOAD COMMAND ENABLES Alarm Rstr Byp Trbl O/C LoBat
0=standard; 1=expanded;
0 NOTE: Expanded overrides 4+2 format.
Dlr ShtdwnSys ShtdwnNot UsedRmt BypRmt DisarmRmt ArmUpld PgmDwnld Pgm
See field 1∗53 for Callback disable option; [1=enable]; ∗53 STANDARD/EXPANDED REPORT FOR SECONDARY
0=disable. For Commercial Burglary and Commercial Fire
installations, all entries must be "0."
[0 0 0 0 0 0]
∗38 PREVENT ZONE XXX BYPASS [000] | | Alarm Rstr Byp Trbl O/C LoBat
0=standard; 1=expanded;
001-032; 000 if all zones can be bypassed NOTE: Expanded overrides 4+2 format.
∗39 ENABLE OPEN/CLOSE REPORT FOR [1] ∗56 DYNAMIC SIGNALING DELAY [03] |
INSTALLER CODE 1=enable; 0=disable Select the delay time (00-15) times 15 seconds before sending
to second destination.
∗40 OPEN/CLOSE REPORT FOR KEYSWITCH [0] NOTE: When Communicator is used as a backup to the dialer,
1=enable; 0=disable the Dynamic Signaling Delay (∗56) should be set to a
minimum of 1 minute.
∗41 NORMALLY CLOSED or EOLR (Zones 3-8) [0]
∗57 DYNAMIC SIGNALING PRIORITY [0]
1=N.C.loops; 0=EOLR supervision.
Must be "0" for Commercial Burglary and Commercial Fire 0=Primary dialer; 1=Communicator, as first reporting
installations. destination.
∗44 RING DETECTION COUNT [00] | ∗59 COMM CENTRAL STATION #2 CATEGORY ENABLE
01-14; 15=answering machine; 00=no detection.
[0 0 0 0 0 0]
Must be "00" for Commercial Burglary and Commercial Fire Alarm Trbl Byp O/C Syst Test
installations. 0=disable, 1=enable for reports for secondary subs ID of
communicator.
∗45 PRIMARY FORMAT [1]
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;
∗64 through ∗76 (PAGER OPTIONS) - Not Used. Must
Be Set To “0”.
3= ADEMCO Express
∗48 LOW SPEED FORMAT (Sec.) [0] Option 2 is ONLY for use if the system is used as a slave
communicator only, and NOT if the system is used for Fire
0= ADEMCO Low Speed; 1=Sescoa/Radionics Alarm Detection.
∗49 CHECKSUM VERIFICATION [0] [0] ∗79 ZONE TYPE RESTORE ENABLES FOR ZONE TYPES
1=enable; 0=disable Prim Sec
1-8
∗50 SESCOA/RADIONICS SELECT [0] 1 2 3 4 5 6 7 8
1=Sescoa; 0=Radionics 1=enable; [0=disable]
–9–
∗80 FOR TYPES 9, 10 and 14 ∗20 EXIT ERROR LOGIC ENABLE
1∗ [0]
9 10 14 0=No; 1=Bypass E/E and Interior zones faulted after exit
1=enable; [0=disable] delay.
Restores must be set to “1” for Commercial Fire installations. Must be "0" for Commercial Burglary installations.
∗83 FIRST TEST REPORT TIME | | | ∗21 EXIT DELAY RESET
1∗ [0]
[Day 00; hour 12; min 00]. Days 01-07, Hours 00-23, Min 00- 0=No; 1=Resets Exit Delay to programmed value after zone
59; 00 in all boxes = instant (Day 01= Monday) is closed and then faulted prior to end of exit delay.
Must be "0" for Commercial Burglary installations.
∗84 SWINGER SUPPRESSION [00] |
FIELDS 1∗22-1∗25: Allow four sets of two zones each to be linked
01-15 alarms so that both must fault within a 5-minute period to cause an alarm.
Must be "00" (disabled) for Commercial Burglary Default for these fields = [000], [000].
∗85 ENABLE DIALER REPORTS FOR PANICS & DURESS ∗22 CROSS-ZONING PAIR ONE
1∗ | | | |
1=enable; [0=disable]
∗23 CROSS-ZONING PAIR TWO
1∗ | | | |
995 996 999 Duress
∗24 CROSS-ZONING PAIR THREE
1∗ | | | |
∗87 ENTRY WARNING [1]
1=continuous; 0=3 beeps ∗25 CROSS-ZONING PAIR FOUR
1∗ | | | |
∗88 BURG. ALARM COMM. DELAY [0] ∗26 PANIC BUTTON OR SPEEDKEY
1∗
1=30 seconds; 0=no delay
[00, 00, 00, 00]
| | | |
Must be "0" for Commercial Burglary installations.
A B C D
∗89 ALARM RESTORE REPORT TIMING [0] Enter speedkey macro # (01-32) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro
0 = Restore is sent when zone is restored or at disarming,
# 01-32, or 00 to select macro when key is pressed.
whichever occurs first.
1 = Restore is sent at disarming whether zone is restored or
not, or at bell timeout, but only if restored. ∗28 RF TX LOW BATTERY SOUND
1∗ [0]
2 = Restore is sent at disarming, whether the zone is restored
or not. 1=immediate; 0=when disarmed
This field applies only to Burglary zone types. It does not Must be 1 for UL installations.
apply to Fire or Panic zone types.
Must be "2" for Commercial Burglary installations. ∗29 RF TX LOW BATTERY REPORTING
1∗ [0]
1=enable; 0=disable
∗90 SEC. SUBS. ACCT # | | | | Must be 1 for UL installations.
Enter 00-09; B-F (11-15) [15 15 15 15]
∗30 RF RCVR CHECK-IN INTERVAL
1∗ [02] |
2nd Page Programming Fields (press ∗94) 02-15 times 2 hours; 00 disables supervision
Maximum is 2 (4 hr) for UL installations.
∗12 PROGRAM NOTIFICATION SIGNAL
1∗ [1]
1=yes; 0=no
∗31 RF XMITTER CHECK-IN INTERVAL
1∗ [02] |
Must be "1" for Commercial Fire installations. 02-15 times 2 hours; 00 disables transmitter supervision
∗13 SYSTEM SENSOR REVERSING RELAY – Not Used.
1∗ Maximum is 2 (4 hr) for UL installations.
– 10 –
∗72 EVENT LOG PRINTER ON-LINE - Not Used. Must Be
1∗
∗43 PERM. KEYPAD BACKLIGHT
1∗ [0] Set To “0”.
1=enable; 0=disable, when disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity. [0]
0=disable; 1=enable
∗44 WIRELESS KEYPAD TAMPER DETECTION – Not
1∗
Used. Must be set to “0”. ∗73 PRINTER BAUD RATE - Not Used. Must Be Set To
1∗
“0”..
[0]
1=enable; 0=disable.
[0]
1=300; 0=1200
∗45 EXIT DELAY SOUNDING
1∗ [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
∗74 RELAY TIMEOUT XXX MINUTES
1∗ [000] | |
NOTES: Enter relay timeout, 0-127 in multiples of 2 minutes, desired
Must be set to “0” in partition 1 for fire systems. for #80 Menu Mode time-driven event relay command
See page 31, “SOUND OPTION”, prompt for disabling the numbers "04/09" and #93 Menu Mode Output Programming
entry/exit beeps on individual keypads. output command "56."
[0]
∗76 CONTROL RELAY
1∗ [00] |
0=disable; enter partition in which RF keypad used, 1-2.
Relay will be pulsed for 2 seconds whenever code + [0] is
∗49 SUPPRESS TX SUPERVISION SOUND
1∗ [1] pressed. Enter relay number 01-96; 00=none.
Must be "00" for Commercial Burglary and Commercial Fire
1=disable; 0=enable. installations.
Must be "0" for Commercial Burglary and Fire installs.
∗77 LOG FIRST MAINTENANCE SIGNAL
1∗ [0]
∗52 SEND CANCEL IF CODE + OFF
1∗ [0]
0=No Log; 1=Log first maintenance signal from each smoke
1=no restriction; 0=within bell timeout period only. detector.
∗53 DOWNLOAD CALLBACK
1∗ [0] 3rd Page Programming Fields (press ∗94)
1=callback not required; 0=callback required.
Must be "0" for Commercial Burglary and Commercial Fire ∗00 NUMBER OF PARTITIONS
2∗ [1]
installations.
Enter 1-2
∗55 EUROPEAN DATE FORMAT
1∗ [0]
∗01 DAYLIGHT SAVING TIME [03, 11]
2∗ | |
0=disable (mm/dd/yy); 1=enable (dd/mm/yy).
START/END MONTH Start End
∗56 AC 50/60 Hz CLOCK SPEED
1∗ [0] 00-12; if no daylight saving time, enter 00,00
1=50 Hz; 0=60 Hz. ∗02 DAYLIGHT SAVING TIME
2∗ [2, 1] |
∗57 5800 RF BUTTON GLOBAL ARM
1∗ [0] START/END WEEKEND Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next
1=enable; 0=disable
to last; 7=3rd from last [1,5]
Must be "0" for Commercial Burglary and Commercial Fire
installations. ∗05 AUTO-ARM DELAY
2∗ [15] |
∗58 5800 RF BUTTON FORCE ARM
1∗ [0] Enter the time between the end of the arming window and the
start of auto-arming warning period, in values of 1-14 times 4
1=enable. If a zone is faulted after pressing button, console
minutes 00=instant; [15=no auto arm at all]. When this delay
will beep once. User should press button again within 4 sec.
expires, the Auto-Arm Warning Period begins.
to force bypass those zones. 0=disable.
Must be "0" for Commercial Burglary and Commercial Fire ∗06 AUTO-ARM WARNING PERIOD
2∗ [15] |
installations.
This is the time during which the user is warned to exit the
∗60 ZONE 5 AUDIO ALARM VERIFICATION
1∗ [0] premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
Enter 1 if 2-way audio (AAV) is being used; Enter 0 if it is not.
00=instant at end of arming delay.
Must be "0" for Commercial Burglary and Commercial Fire
installations. ∗07 AUTO-DISARM DELAY
2∗ [15] |
This is the time between the end of the disarming window
∗70 EVENT LOG TYPES
1∗
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
[1 0 0 0 1 0]
Alarm Chk Byp O/C Syst Test ∗08 ENABLE FORCE ARM FOR AUTO-ARM
2∗ [0]
1=enable; 0=disable
0=disable; 1=enable
∗71 12/24 HOUR TIME STAMP FORMAT
1∗ [0]
0=12 hour; 1=24 hour
– 11 –
∗09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
2∗ ∗12 ZN TYPE 18 DELAY USE
3∗ [1]
1=enable; 0=disable 0=disable; 1=enable
If enabled, only openings and closings occurring outside the NOTE: Must be set to “0” for Commercial Fire Installations.
scheduled opening/closing windows will trigger dialer reports.
Opening reports will also be suppressed during the closing
window, in order to prevent false reports when the user arms
∗13 FIRE SUPERVISORY RESPONSE TO OPEN/SHORT
3∗
the system and then reenters the premises to retrieve a (Applies to Zone Type 18) [0]
forgotten item.
0=Trouble on open/Supervisory on short
∗10 ALLOW DISARMING ONLY DURING
2∗ [0] 1=Supervisory on open/Supervisory on short
NOTE: Must be set to “0” for Commercial Fire Installations.
ARMING/DISARMING WINDOWS
0=disable; 1=enable ∗14 WATERFLOW SILENCE OPTION
3∗ [0]
See system-wide field 2∗11 if enabling field 2∗10. This
0=silence on code = off; 1=silence when waterflow restores
feature adds high security to the installation.
NOTE: Must be set to “0” for Commercial Fire Installations.
∗11 ALLOW DISARM OUTSIDE WINDOW
2∗ [0]
∗16 DELAY FOR ZONE TYPE 17 & 18
3∗ [00] |
IF ALARM OCCURS Enter 00-15 times 2 seconds
Used only if field 2∗10 is set to "1." If this field is enabled Delay cannot exceed 90 seconds in UL installations.
("1") the system can be disarmed outside the disarm window NOTE: Must be "00" for Commercial Fire installations.
if an alarm has occurred. If "0," disarming can only be done
during the disarm window. If field 2∗10 is set to "0" for a ∗17 ALTERNATE FUNCTION (TAMPER)
3∗ [0]
partition, this field has no effect for that partition. FOR ZONE 6 0=disable; 1=enable
∗18 ENABLE GOTO FOR THIS PARTITION
2∗ [0] ∗18 EXTENDED DELAY FOR TYPES 17 & 18
3∗ [0]
1=Allow log-on from other partitions; 0=disable 0=disable; 1=enable
NOTE: Must be disabled for partition 1 in Commercial Fire NOTE: Must be "0" for Commercial Fire installations.
installations.
∗19 AUX INPUT ALTERNATE FUNC ENABLE
3∗ [0]
∗19 USE PARTITION DESCRIPTORS
2∗ [0]
0=pins 5 and 9 function as per filed 3∗20;
0=disable; 1=enable 1=pins 5 and 9 function as RXD and DTR
NOTE: Must be set to “0” for Commercial Fire Installations.
∗20 ENABLE J2 TRIGGERS FOR PARTITION
2∗ [1]
0=disable; 1=enable for displayed partition ∗20 TRIGGER OUTPUT SELECTION
3∗ [0]
∗21 ENABLE SUPERVISION PULSES FOR COMM -
2∗ 0=Communicator full connection & remote console sounder;
Not Used. Must Be Set To “00000”. 1=Communicator limited connection and keyswitch LEDs
2=Communicator fire only connection and 5140LED
NOTE: Must be set to “0” for Commercial Fire Installations.
00000]
F B P S T ∗21 MAX NUMBER OF DIALER ATTEMPTS
3∗ [8]
Used only for supervised connection to Communicators (e.g.
7845i-ent). 1-8 (3, 4 or 5 for NFPA72 compliant systems when a
Enter 0 to disable or 1 to enable the listed outputs. secondary phone number is programmed (field ∗34))
F= Fire; B= Burglary/Audible Panic; P= Silent Panic/Duress;
S= Supervisory; T= Trouble. ∗30 DIALER SELECTION
3∗ [1,0]
0=disable; 1=enable Main Backup
∗22 DISPLAY FIRE ALARMS OF
2∗ [0] NOTE: If 3∗30 is disabled (0, 0), the panel does not report at
all via Communicator.
OTHER PARTITIONS
0=disable; 1=enable. ∗31 BACKUP DIALER TOUCHTONE/ROTARY
3∗ [0]
Must be set to “0” (disable) for partition 1.
1=TouchTone; 0=Rotary
∗23 DISPLAY BURG, PANIC and CO
2∗ [0]
∗50 ZONE TYPE RESTORE ENABLES
3∗
ALARMS OF OTHER PARTITIONS
0=disable; 1=enable. FOR ZONE TYPES 16-18
Must be set to “0” (disable) for partition 1. 1=enable; [0=disable]
Restores must be set to “1” for Commercial Fire installations.
∗24 DISPLAY TROUBLES OF OTHER
2∗ [0]
∗55 RESET ON SECOND OFF FOR BELL 1
3∗ [0]
PARTITIONS
0=disable; 1=enable 0=disable; 1=enable
Must be set to “0” (disable) for partition 1. NOTE: Must be set to “0” for Commercial Fire Installations.
4th Page Programming Fields (press ∗94) ∗56 RESET ON SECOND OFF FOR BELL 2
3∗ [0]
0=disable; 1=enable
∗00 DISPLAY TRBL INSTEAD OF CHECK
3∗ [0] NOTE: Must be set to “0” for Commercial Fire Installations.
0=CHECK; 1=TRBL
– 12 –
∗57 BELL 2 & AUX RELAY CONFIRM
3∗ [0,0] ∗61 AUX RELAY FUNCTION
3∗ [1]
ARMING DING Bell 2 Aux 0=trouble/supervisory; 1=alarm, silenced by code = off;
0=disable; 1=enable. 2=smoke detector reset; 3=battery save; 4=alarm, silenced
NOTE: If using a keyfob, when the button is pressed, either by code = # = 67
for arming or disarming, the bell will ding indicating that the NOTE: See Data Field Descriptions in the Installation and
button is working. Setup Guide for specific information.
Must be “1” for Commercial Burglary installations.
∗82 ENABLE BURG FEATURES ON PART 1
3∗ [1]
∗59 ENABLE BELL 2 & AUX RELAY
3∗ [0,0] 0=disable (disables AWAY, STAY, MAX, TEST, INSTANT
CHIME ANNUNCIATION Bell 2 Aux and CHIME); 1=enable;
0=disable; 1=enable NOTE: Must be "0" for Commercial Fire installations.
NOTE: Must be “0, 0” if Bell 2 or Aux. Relay is used for fire ∗85 ENABLE FIRE & SYSTEM ZONE BYPASS [1]
3∗
application. 0=disable; 1=only installer can bypass;
2=only installer and master can bypass.
∗60 BELL 2 & AUX RELAY TIMEOUT
3∗ | | Applies to fire zone types 9, 16, 17, and 18 and system
Bell 2 Aux zones 970-977 and to partition 1 only.
Enter 00-15 times 2 minutes; 00=no timeout [00,00]
Minimum 16 minutes for Commercial Burglary installations.
– 13 –
Partition-Specific Fields
(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press ∗91 to select a partition.
2. Enter a partition-specific field number (ex. ∗09).
3. Make the required entry.
4. Repeat steps 1-3 for each partition in the system.
– 14 –
∗45 EXIT DELAY SOUNDING
1∗ [0] ∗18 ENABLE GOTO FOR THIS PARTITION
2∗ [0]
1=enable; 0=disable Produces quick beeping during exit 1=Allow log-on from other partitions; 0=disable
delay if enabled. NOTE: Must be disabled (0) for partition 1 in Commercial
NOTES: Fire installations.
Must be set to “0” in partition 1 for fire systems.
See page 31, “SOUND OPTION”, prompt for disabling the ∗20 ENABLE J2 TRIGGERS BY PARTITION
2∗ [1]
entry/exit beeps on individual 0=disable for displayed partition; 1=enable for displayed
partition
∗47 CHIME ON BELL 1
1∗ [0]
1=enable; 0=disable ∗22 DISPLAY FIRE ALARMS OF
2∗ [0]
Enter the time between the end of the arming window and 4th Page Fields
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When ∗57 BELL 2 & AUX RELAY CONFIRM
3∗ [0,0]
this delay expires, the Auto-Arm Warning Period begins.
ARMING DING Bell 2 Aux
∗06 AUTO-ARM WARNING PERIOD
2∗ [15] | 0=disable; 1=enable.
NOTE: If using a keyfob, when the button is pressed, either
This is the time during which the user is warned to exit the
for arming or disarming, the bell will ding indicating that the
premises prior to the auto-arming of the system (beeps every
button is working.
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
Must be set to “1” for Commercial Burglary installations.
00=instant at end of arming delay.
This is the time between the end of the disarming window CHIME ANNUNCIATION Bell 2 Aux
and the start of auto-disarming. Enter 01-14 times 4 minutes; 0=disable; 1=enable
00=instant at end of window; 15=no auto-disarm NOTE: Must be “0, 0” if Bell 2 or Aux. Relay is used for fire
application.
∗08 ENABLE FORCE ARM FOR AUTO-ARM
2∗ [0]
∗60 BELL 2 & AUX RELAY TIMEOUT
3∗ | |
0=disable; 1=enable
Bell 2 Aux
∗09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
2∗ Enter 00-15 times 2 minutes; 00=no timeout [00, 00]
Minimum 16 minutes for Commercial Burglary installations.
1=enable; 0=disable. If enabled only openings and closings
occurring outside the scheduled opening/closing windows SUMMARY OF PROGRAMMING COMMANDS
trigger dialer reports. Opening reports will also be
suppressed during the closing window, in order to prevent • To enter program mode, enter installer code + [8] + [0] + [0]
false reports when the user arms the system and then re- • To set standard defaults, press ∗97
enters the premises to retrieve a forgotten item. • To change to next page of program fields, press ∗94
• To return to previous set of fields, press ∗99
∗10 ALLOW DISARMING ONLY DURING
2∗ [0]
• To erase account and phone number field entries, press [∗] +
ARMING/DISARMING WINDOWS field number + [∗]
See system-wide field 2∗11 if enabling field 2∗10. This • To assign zone descriptors, press #93 + follow menu prompts
feature adds high security to the installation. • To add custom words, press #93 + follow menu prompts
0=disable; 1=enable • To enter Installer's Message, press #93 + follow menu prompts
• To exit program mode, enter ∗99 OR ∗98: ∗99 allows re-access
to programming mode by installer code. ∗98 prevents re-access
to programming mode by installer code.
– 15 –
Programming With #93 Menu Mode
NOTE: The following field should be preset before beginning: 2∗00 Number of Partitions. In addition, receivers should
be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu
selection. Pressing 0 will display the next choice in sequence.
DEVICE PROG? For defining the following device characteristics for addressable devices, including keypads, RF receivers
(5881ENHC, 5883H), output relay modules (4204/4204CF), and Communicators (7845i-ent).
1 = YES 0 = NO 0
• Device Address
• Device Type
• Keypad Options (incl. partition assignment)
• RF House ID
• Communicator Options (incl. programming communicators)
– 16 –
PROMPT EXPLANATION
Zone Programming
PROMPT EXPLANATION
ZONE PROG? Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [∗] to display the next
screen. Press # to display a previous screen.
1 = YES 0 = NO 0
SET TO CONFIRM? This prompt appears once upon entering Zone Programming Mode.
1 = YES 0 = NO 0 If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been
entered later.
ENTER ZONE NO. Enter the 3-digit zone number to be programmed, as follows:
000 = QUIT 010 Protection Zones = 001–032
Relay Zones = 601–632 (use for relays on 4204CF modules only).
Zone 010 entered ↑ ECP Device Supervisory Zones = 800–830
System Supervisory Zones = 988, 990, 992 (duress), 997
Keypad Panic Zones = 995 (Do not use in Fire Alarm applications), 996, 999
Press [∗] to continue.
010 ZT P RC In L This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P =
Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the
00 1 10 00 1
sensor is connected.
Some devices can support more than one zone by means of individual loops (for example 5817CB, etc.). If
the zone is not programmed, the display appears as shown here. If you are checking a zone's programming,
and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.
Press [∗] to continue.
– 17 –
PROMPT EXPLANATION
010 ZONE TYPE Each zone must be assigned a zone type, which defines the way in which the system responds to faults in
that zone. Refer to the Zone Type Definitions section in the VISTA-32FB Installation and Setup Guide for
PERIMETER 03
detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available
Zone number 010 and zone types are listed below.
Zone Type 03 entry shown 00 = Assign for Unused Zones 14 = CO Detector Alarm
† These are special zone 01 = Entry/Exit #1, Burglary 16 = Fire With Verification
types used with 5800
02 = Entry/Exit #2, Burglary 17 = Waterflow
Series Wireless
Pushbutton Units that 03 = Perimeter, Burglary 18 = Fire Supervisory
result in arming the system 04 = Interior Follower, Burglary 19 = 24-Hour Trouble
in the STAY or AWAY 05 = Trouble Day/Alarm Night 20 = Arm–STAY†
mode, or disarming the 06 = 24 Hr. Silent Alarm 21 = Arm AWAY†
system, depending on the
selection made. 07 = 24 Hr. Audible Alarm 22 = Disarm†
08 = 24 Hr. Auxiliary 23 = No Alarm Response (e.g., relay activation)
09 = Fire Without Verification 27 = Access Point – Not Used
10 = Interior Delay, Burglary 28 = MLB Supervision (if VGM installed) – Not Used
12 = Panel Link Supervision – Not
29 = Momentary Exit (used with VistaKey module) - Not Used
Used
13 = Remote P/S
Press [∗] to continue.
010 PARTITION Enter the partition number (1–2) you are assigning this zone to.
1 Press [∗] to continue.
010 REPORT CODE Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
1st 03 2nd 12 3C
(Refer to the System Communication section in the Installation and Setup Guide for more information about
report codes and reporting formats.)
Press [∗] to continue.
010 BELL/RLY SEL Each zone can be assigned to activate either one or both Notification Appliance Circuits and/or the system’s
auxiliary relay. Enter one of the following assignments:
0
0=none; 1=bell 1; 2=bell 2; 3=bell 1 & bell 2; 4=aux relay; 5=bell 1 & aux relay; 6=bell 2 & aux relay; 7=bell 1
& bell 2 & aux relay.
Press [∗] to continue.
– 18 –
PROMPT EXPLANATION
010 SMART CONTACT If input type 3 or 6 was selected, this prompt will be displayed. Enter 1 for devices that monitor maintenance
signals (ex. 5193SD, 5193SDT) or can be used to limit fault signals in the disarmed state (ex. Quest
1 = YES 0 = NO
2260SN). Otherwise, enter 0.
NOTES:
1. The Smart Contact option must ONLY be selected for devices that support the feature, otherwise
unpredictable results may occur.
2. if using the new 5193SD/SDT V-Plex smoke detectors (or older 5192SD/SDT with the maintenance DIP
sw enabled) the "Smart" option must be selected in zone programming or when they enroll unpredictable
results may occur if the smoke goes into a High Sens or Low Sens condition.
010 V-PLEX RELAY? If you selected input type 6, this prompt is displayed. Enter 1 if using a 4101SN Relay Module for this
zone. Otherwise enter 0.
1 = YES 0 = NO
Press [∗] to continue.
010 CONS ECP ADDR If you selected input type 09, this prompt is displayed. Enter the ECP address of the keypad that is being
used for entry/exit for this access point (00-30).
(00-30) 01
Press [∗] to continue.
010 INPUT S/N: L For Serial Number entry and Loop Number entry, do one of the following:
AXXX-XXXX 1 a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad.
Then press the [∗] key, the cursor moves to the “L” position. You can edit the loop number, if necessary.
When the loop number is acceptable, press [∗].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Press [∗] to accept.
010 INPUT S/N: L The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number
displayed.
A022-4064 1
Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).
To Delete an Existing Serial Number, enter “0“ in the loop number field. The serial number will change to
“0”s.
If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to
the display.
Press [∗] to accept.
010 INPUT S/N: L The system will then check for a duplicate serial/loop number combination.
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display
A022-4064 1
the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number.
If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial
number and loop number entry.
Press [∗] to continue.
– 19 –
5800 Series Transmitters Loop Designations
PROMPT EXPLANATION
XMIT TO CONFIRM Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system
enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate
PRESS ∗TO SKIP
the loop input or button that corresponds to this zone. At any time during this step, you may press the [∗] key
on the keypad to save the serial and loop number combination without confirming.
Entd A022-4063 1 If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it is also displayed.
Rcvd A022-4064
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display does not appear), press the [#] key twice and then enter or transmit the correct serial number.
010 ZT P RC In L If the serial number transmitted does match the serial number entered, the system beeps 3 times and a
summary display appears, showing that zone’s programming. Note that an “s” indicates that a transmitter’s
03 1 3C RF 1s
serial number has been enrolled.
Press [∗] to accept the zone information.
ENTER ZONE NO. The system now returns to the “ENTER ZONE NO.” prompt for the next zone.
000 = QUIT 011 When all zones have been programmed, enter “000” to quit.
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information
(zone number, zone type, etc.) relevant to that device.
When you have finished programming all zones, test each using the system's Test Mode. Do not use the
Transmitter ID Sniffer Mode. The system checks only for transmission of one zone on a particular
transmitter, NOT the zones assigned to each additional loop, and also does not verify polling loop type
zones.
– 20 –
Expert Mode Zone Programming
Expert mode allows you to program zones using the minimum number of screens and keystrokes.
Enter the Programming mode with [Installer Code] + 8 0 0
Before programming your zones, do the following:
1. Program field 2∗00: Number of Partitions.
2. Enable your RF Receiver in Device Programming menu mode.
To program your zones, press ∗93 to display the "ZONE PROG?" prompt. Enter “0” (NO) to each prompt until the “EXPERT
MODE?” prompt appears.
PROMPT EXPLANATION
SET TO CONFIRM? This prompt appears once upon entering Expert Mode.
0 = NO 1 = YES 0 If you select “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have
been entered later.
Zn ZT P RC In L A summary display appears, showing zone 1’s current programming or default values.
001 03 1 10 HW -
Zn ZT P RC In L Enter all zone information except for Loop number, or press “C” to copy the zone information on this screen
from the last saved zone (including Loop).
010 03 1 10 RF -
ZT = Zone Type
P = Partition
RC = Report Code
In = Input Device Type
L = Loop number to which the sensor is connected.
NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the
input type. Verify this information is correct for this zone.
On this screen:
• Use the [A] key to move to the right.
• Use the [B] key to move to left and to back up to “ZT” field.
Press [∗] to accept the existing or newly-entered zone information.
ZN B M V A C E AD Enter the remainder of the zone’s information, or press the [C] key to copy the zone attributes on this screen
from the last saved zone.
010 2 1 1 0 1 1 01
B = Bell/Relay Assignment
M = Maintenance (only used if “In” = 3 or 6)
V = Do Not Use. Must be set to “0”.
AC = Access Point (only used if In = 6)
E = Do Not Use. Must be set to “0”.
AD = Address (only used if “In” = 9)
If “In” = 9, enter the Device Address
NOTE: Pressing the [C] copies the zone attributes from the last saved zone. Verify the attributes for
this zone are correct.
On this screen:
• Use the [A] key to move to the right.
• Use the [B] key to move to left and to back up to “V” field.
Press [∗] to accept existing information.
– 21 –
PROMPT EXPLANATION
010 INPUT S/N: L If you entered RM, RF, BR, UR or SL for the Input Type, this screen displays. Otherwise the summary
screen for the next zone displays.
A XXX-XXXX -
Enter the 7-digit serial number, using one of the following methods:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the alpha keypad.
Then press the [∗] key, the cursor will move to the “L” position. You can edit the loop number, if
necessary. When the loop number is acceptable, press [∗].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Remember, you can use the [A] key to move to the right or the [B] key to move to the left.
You can also use the [#] key to back up without saving.
010 INPUT S/N: L Press [∗] to accept the serial number and advance to the “L” position (if method “a” or “c” was used), then
enter the loop number.
A022-4064 1
If necessary, press the [#] key to back up without saving, and re-enter or edit the serial number before
pressing [∗] to save
The system checks for a duplicate. If a duplicate serial/loop number combination is found, the keypad will
emit a single long beep, and display the serial number along with a “?” for the loop number, allowing you to
re-enter the correct loop number.
010 INPUT S/N: L To Delete an Existing Serial Number, enter “0“ in the loop number field. The serial number will change to
“0”s.
A000-0000 1
If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to
the display.
XMIT TO CONFIRM The prompt to confirm appears. This prompt only appears if you answered “Yes” at the “SET TO
CONFIRM?” prompt.
PRESS ∗TO SKIP
The system enters a confirmation mode so that the operation of the actual programmed input can be
confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you
may press the [∗] key on the keypad to save the serial and loop number combination without confirming.
Entd A022-4063 1 If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it also is displayed.
Rcvd A022-4064
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display for the next zone does not appear), press the [#] key twice and then enter or transmit the correct
serial number.
Activate the button on the wireless key again after re-entering the serial number.
Zn ZT P RC In L If the serial number transmitted matches the serial number entered, the system beeps 3 times and
advances to the summary display for the next zone's programming.
011 00 1 10 00 1
After all the zones have been programmed, enter 000 for the zone number to quit.
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information
(zone number, zone type, etc.) relevant to that device.
– 22 –
Report Code Programming
All report codes are entered using #93 Menu Mode Programming, either through Report Code Programming, or through Zone
Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. These
categories represent the main menu options in Report Code Programming. Reports and the categories in which they are
found are as follows:
ALARM CODES RESTR, SUPV. CODES SYSTEM GROUP #1
(for groups of 16 zones)
Zone Alarm Reports Alarm Restore Closing (arm AWAY)
Trouble Opening (disarm)
Trouble Restore System Low Battery
Bypass Low Battery Restore
Bypass Restore AC Loss
AC Restore
Periodic Test
Power
Cancel
Program Tamper
ALARM, ID DIGIT? Press [1] (Y) to enter Alarm Report Codes for zones. Press [0] (N) to skip to the next main menu option.
1 = YES 0 = NO 0
ENTER ZONE NO. Enter the zone number for which you are entering the report code.
000 = QUIT 001 Press [∗] to continue.
001 REPORT CODE Enter the first digit of the Alarm report code (double-digit entry) and press [∗]. Enter the 2nd digit of the
Alarm Report code.
1st 00 2nd 00 00
Press [∗] to continue.
ENTER ZONE NO. Enter the zone number for which you are entering the report code. When all zone Alarm Codes have been
programmed, enter 000 to Quit.
000 = QUIT 001
Press [∗] to continue.
QUIT REPORT MENU If you have completely finished entering report codes, press [1] (Y) to quit Report Code Programming. If you
wish to enter other system report codes, enter 0 (N).
1 = YES 0 = NO 0
Press [∗] to continue.
– 23 –
Restore/Supervisory Codes
PROMPT EXPLANATION
RESTR, SUPV. CODE Press [1] (Y) to enter Restore and Supervisory Codes for zones.
1 = YES 0 = NO 0
ENTER ZN FOR GRP Enter one zone for each group of 16 zones (001-016, 017-032, etc.).
000 = QUIT 001
ALARM RESTORE Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry). The
second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code
GRP 001-016 00
for each zone (if programmed).
Press [∗] to continue.
TROUBLE Enter the first digit of the Trouble Report Code for this group of zones (double-digit entry). The second digit
(for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone
GRP 001-016 00
(if programmed).
Press [∗] to continue.
TROUBLE RESTORE Enter the first digit of the trouble restore code (single-digit entry) and press [∗]. The second digit (for two-
digit reporting formats) is automatically the ID (second) digit of the alarm report code for each zone (if
GRP 001-016 00
programmed).
Press [∗] to continue.
BYPASS Enter the first digit of the Bypass Report Code (double-digit entry) and press [∗]. The second digit (for two-
digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone (if
GRP 001-016 00
programmed).
Press [∗] to continue.
BYPASS RESTORE Enter the first digit of the Bypass Restore Report Code (double-digit entry) and press [∗]. The second digit
(for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone
GRP 001-016 00
(if programmed).
Press [∗] to continue.
ENTER ZN FOR GRP Enter one zone for each group of 16 zones. When you are finished entering Restore and Supervisory Codes
for all zone groups, enter 000.
000 = QUIT 017
Press [∗] to continue.
QUIT REPORT MENU If you have completely finished entering report codes, press [1] (Y) to quit Report Code Programming. If
you wish to enter other system report codes, enter 0 (N).
1 = YES 0 = NO 0
Press [∗] to continue.
PROMPT EXPLANATION
CLOSE Enter the first digit of the Closing (Arm-AWAY) report. Press [∗]. Enter the second digit of the report. If the
user number is desired as the second digit, enter 01 (not necessary for Contact ID or High Speed formats).
1st 00 2nd 00
Press [∗] to continue.
– 24 –
PROMPT EXPLANATION
Enter the rest of the codes in the same manner. Other report codes in System Group #1 are:
• Opening (Disarm) Also, enable this if you desire Callback Requested reports (the panel answers a
phone call from the downloader).
• System Low Battery
• Low Battery Restore
• AC Loss
• AC Restore
• Periodic Test
• Power
• Cancel
• Program Tamper
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT REPORT MENU If you have completely finished entering report codes, press 1 (Y) to quit Report Code Programming. If you
wish to enter other system report codes, enter 0 (N).
1 = YES 0 = NO 0
Press [∗] to continue.
PROMPT EXPLANATION
STAY Enter the first digit of the Arm-STAY report. Press [∗]. Enter the second digit of the report. If the user
number is desired as the second digit, enter 01 (not necessary for Contact ID or High Speed formats).
1st 00 2nd 00
Press [∗] to continue.
Enter the rest of the codes in the same manner. Other codes in System Group #2 are:
• Time Set, Log Reset
• Dialer Queue Overflow
• Exit Error by Zone
• Exit Error by User
• Recent Close
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT REPORT MENU If you have completely finished entering report codes, press [1] (Y) to quit Report Code Programming. If you
wish to enter other system report codes, enter 0 (N).
1 = YES 0 = NO 0
Press [∗] to continue.
PROMPT EXPLANATION
EARLY OPEN Enter the first digit of the Early Opening Report Code. Press [∗]. Enter the second digit of the report code. If
the user number is desired as the second digit, enter 01 (not necessary for Contact ID or High Speed
1st 00 2nd 00
formats).
Press [∗] to continue.
– 25 –
PROMPT EXPLANATION
Enter the rest of the codes in the same manner. Other codes in System Group #3 are:
• Early Close
• Late Open
• Late Close
• Failed to Open
• Failed to Close
• Auto-Arm Failed
• Schedule Change
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT REPORT MENU If you have completely finished entering report codes, press [1] (Y) to quit Report Code Programming. If you
wish to enter other system report codes, enter 0 (N)
1 = YES 0 = NO 0
Press [∗] to continue.
PROMPT EXPLANATION
WALK TEST START Enter the first digit of the Fire Walk Test Start Report Code. Press [∗]. Enter the second digit of the report
code.
1st 00 2nd 00
Press [∗] to continue.
Enter the rest of the codes in the same manner. Other codes in System Group #4 are:
• Fire Walk-Test End.
• Off-Normal.
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT MENU MODE? Enter 1 to exit back to normal Programming mode. Enter 0 to stay in Menu mode.
1 = YES 0 = NO 0
– 26 –
Alpha Descriptors Programming
You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling
loop short, and RF receiver supervision troubles.
Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words
stored in memory, and any word can have an "s" or " 's " added to it.
NOTE: Due to the use of 3-digit zone numbers, the first word of the descriptor is limited to 6 characters if you want it to fit on
the top line of the display.
In addition, up to 60 installer-defined words can be added to those already in memory. Thus, when an alarm or trouble occurs
in a zone, an appropriate description for the location of that zone will be displayed at the keypad.
A custom installer's message can be programmed for each partition which is displayed when the system is "Ready" (e.g., THE
PETERSONS’).
1. To program alpha descriptors, enter Programming mode, then press #93 to display "ZONE PROG?"
2. Press [0] (NO) twice to display "ALPHA PROG?".
3. Press [1] to enter Alpha Programming.
There are 6 submenu selections that will be displayed one at a time.
Press [1] to select the mode desired.
Press [0] to display the next mode available. The alpha menu selections are:
ZONE DESCRIP? For entering zone descriptors.
DEFAULT SCREEN? For creating custom message; displayed when system is ready.
EXIT EDIT MODE? Press [1] to exit back to #93 Menu Mode.
4. Refer to the sections that follow for procedures for adding alpha descriptors.
Zone Descriptors
1. Select ZONE DESCRIPTOR mode.
The keypad keys perform the following functions:
[3] Scrolls both alphabet and actual words in ascending alphabetical order.
[1] Scrolls both alphabet and actual words in descending alphabetical order.
[2] Adds or removes an "s" or " 's " to a vocabulary word.
[6] Switches between alphabet and actual word list; used to accept entries.
[8] Saves the zone description in the system's memory.
[#] [#] plus zone number displays the description for that zone.
2. Enter the zone number to which you want to assign a descriptor.
For example, key [∗] 001 to begin entering the description for Zone 1, (key [∗] 002 for Zone 2, [∗] 003 for Zone 3, etc.).
The following is displayed: ∗ ZN 001 A.
Note that the first letter of the alphabet appears after the zone number, and that the zone number is automatically
included with the description.
3. Enter the descriptor for that zone.
Use one of two methods as follows:
(Assume, for example, that the desired description for Zone 1 is BACK DOOR.)
a) Press [#] followed by the 3-digit number of the first word from the fixed dictionary shown later in this section (e.g.,
[0][1][5] for BACK).
Press [6] in order to accept the word and proceed, or press [8] to store the complete descriptor and exit;
or
b) Select the first letter of the desired description (note that "A" is already displayed). Use the [3] key to advance
through the alphabet and the [1] key to go backward.
Press [3] key repeatedly until "B" appears (press [1] to go backwards if you happen to pass it), then press [6] to
display the first available word beginning with “B”.
Press [3] repeatedly to advance through the available words until the word “BACK” is displayed.
To add an "s" or " 's," if you need to, press 2. The first depression adds an "s," the second depression adds
an " 's, " the third depression displays no character (to erase the character), the fourth depression adds an
"s," etc.
– 27 –
4. Accept the word.
To accept the word, press [6], which switches back to the alphabet list for the next word, or press [8] to store the
complete descriptor and then exit.
5. Select the next word.
For selection of the next word (DOOR), repeat step 3a (word #063) or 3b, but selecting the word "DOOR.”
To accept the word, press [6], which again switches back to alphabet list.
6. Store the descriptor.
When all desired words have been entered, press [8] to store the description in memory.
To review the zone descriptors, key [#] plus zone number (e.g., #001).
To edit zone descriptors, key [∗] plus zone number (e.g., ∗001)
7. Exit Zone Description Mode: enter 000.
Default Screen (Custom Message Display)
Normally, when the system is in the disarmed state, the following display is present on the keypad.
****DISARMED****
READY TO ARM
Part or the entire above message can be modified to create a custom installer message for each partition. For example,
“****DISARMED****” on the first line or “READY TO ARM” on the second line could be replaced by the installation company
name or phone number for service.
NOTE: There are only 16 character spaces on each of the two lines.
To create a custom display message, proceed as follows:
1. Select Default Screen mode.
The keypad asks for the partition number for this message.
Enter the partition number. Press [∗] to accept entry.
The following display appears:
****DISARMED****
READY TO ARM
A cursor is present at the extreme left of the first line (over the first "star"). Press [6] to move the cursor to the right and [4]
to move the cursor to the left. Press [7] to insert spaces or erase existing characters.
2. Create the message.
For example, to replace “READY TO ARM” with the message “SERVICE 424-0177,” proceed as follows:
Press [6] to move the cursor to the right, and continue until the cursor is positioned over the first location on the second
line.
Press [3] to advance through the alphabet to the first desired character (in this case, "S"). Press [1] to go backward, when
necessary. When the desired character is reached, press [6].
The cursor then moves to the next position, ready for entry of the next character (in this example, "E"). When the cursor
reaches a position over an existing character, press [3] or [1] to advance or back up from that character in the alphabet.
Proceed in this manner until all characters in the message have been entered.
3. Save the message.
Store the new display message in memory by pressing [8].
4. The system asks for a new partition number.
Enter 0 to quit or 1-2 for a new partition number.
Custom Words
Up to 60 installer-defined words can be added to the built-in vocabulary. Each of the 60 "words" can actually consist of several
words, but bear in mind that a maximum of 10 characters can be used for each word string.
1. Select CUSTOM WORD Mode.
The keys perform the following functions:
[3] Advances through alphabet in ascending order.
[1] Advances through alphabet in descending order.
[6] Selects desired letter; moves the cursor 1 space to the right.
[4] Moves the cursor one space to the left.
[7] Inserts a space at the cursor location, erasing any character at that location.
[8] Saves the new word in the system's memory.
[∗] Returns to Description Entry Mode.
2. Enter the custom word number (01-60) you want to create.
For example, if you are creating the first word (or word string), enter 01; when creating the second word, enter 02, and so
on. A cursor now appears at the beginning of the second line.
– 28 –
3. Type the word using one of two methods as follows:
a) Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A").
When the desired character appears, press [6] to select it. The cursor will then move to the right, in position for the
next character. Press [#] plus the 2-digit entry for the next letter of the word.
or
b) Press 3 to advance through the list of symbols, numbers, and letters.
Press 1 to move back through the list.
When you have reached the desired character, press [6] to select it. The cursor then moves to the right, in position
for the next character.
4. Repeat step 3 to create the desired custom word (or words).
Press [4] to move the cursor to the left if necessary.
Press [7] to enter a blank (or to erase an existing character).
Each word or word string cannot exceed 10 characters.
5. Save the word by pressing [8].
This returns you to the “CUSTOM WORD?” display. The custom word (or string of words) is automatically added to the
built-in vocabulary at the end of the group of words beginning with the same letter.
Custom words are retrieved as word numbers 255 to 314 for words 1 to 60, respectively, when using method 3a to enter
alpha descriptors.
When using method 3b to enter alpha descriptors, each word appears at the end of the group of words that begin with the
same letter as it does.
6. Repeat steps 2 through 6 to create up to a maximum of 60 custom words (or word strings).
7. Exit Custom Word Mode by entering 00 at the “CUSTOM WORD” prompt.
Partition Descriptors
1. Select "Part DESCRIPT." Mode.
The system asks for the partition number desired. Enter the number as a single-key entry 1-2.
2. Follow the same procedure as for custom words.
NOTE: The partition descriptors are limited to 4 characters (e.g., WHSE for warehouse).
– 29 –
Alpha Descriptor Vocabulary
(For entering alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.)
NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when
programming relay voice descriptors.
000 (Word Space) • 052 DAUGHTERS • 103 HALL 152 PAINTING 204 TAMPER
• 001 AIR 053 DELAYED • 104 HEAT • 153 PANIC 205 TAPE
• 002 ALARM • 054 DEN 105 HIGH 154 PASSIVE 206 TELCO
003 ALCOVE 055 DESK 106 HOLDUP • 155 PATIO 207 TELEPHONE
004 ALLEY • 056 DETECTOR 107 HOUSE 156 PERIMETER 208 TELLER
005 AMBUSH 057 DIALER 1 • 157 PHONE • 209 TEMPERATURE
006 ANTENNA 108 INFRARED 210 THERMOSTAT
058 DIALER 2 158 PHOTO
• 109 INSIDE • 211 TOOL
• 007 AREA • 059 DINING 159 POINT
110 INTERIOR 160 POLICE 212 TRANSMITTER
• 008 APARTMENT 060 DISCRIMINATOR
111 INTRUSION 161 POOL 213 TRAP
009 ART 061 DISPLAY
• 010 ATTIC 062 DOCK 112 JEWELRY • 162 POWER 214 TRIGGERS
011 AUDIO • 063 DOOR • 113 KITCHEN
163 QUAD 215 ULTRA
012 AUX 064 DORMER
• 114 LAUNDRY • 216 UP
013 AUXILIARY • 065 DOWN 164 COMMUNICATOR
• 115 LEFT • 217 UPPER
• 066 DOWNSTAIRS • 165 REAR
• 014 BABY 116 LEVEL • 218 UPSTAIRS
067 DRAWER 166 RECREATION
• 015 BACK • 117 LIBRARY • 219 UTILITY
• 068 DRIVEWAY 167 REFRIG
• 016 BAR • 118 LIGHT 220 VALVE
069 DRUG 168 REFRIGERATION
017 BARN 119 LINE 221 VAULT
• 070 DUCT 169 RELAY 1
• 018 BASEMENT 120 LIQUOR 222 VIBRATION
170 RF
• 019 BATHROOM • 071 EARTH • 121 LIVING 223 VOLTAGE
• 171 RIGHT
• 020 BED 072 EAST • 122 LOADING • 172 ROOM 224 WALL
• 021 BEDROOM 073 ELECTRIC 123 LOCK 225 WAREHOUSE
173 ROOF
022 BELL 074 EMERGENCY 124 LOOP 226 WASH
023 BELL 1 075 ENTRY 125 LORRA 174 SAFE
• 227 WEST
024 BELL 2 • 076 EQUIPMENT 126 LOW 175 SCREEN
• 228 WINDOW
• 025 BLOWER 077 EXECUTIVE • 127 LOWER 176 SENSOR
229 WINE
• 026 BOILER • 078 EXIT • 177 SERVICE
• 128 MACHINE • 230 WING
027 BOTTOM 079 EXTERIOR • 178 SHED 231 WORK
028 BOX 129 MAGNETIC 179 SHOCK
029 BREAK • 080 FACTORY 130 MAIDS • 180 SHOP 232 XMITTER
• 030 BUILDING 081 FAILURE 131 MAIN 181 SHORT
082 FAMILY • 132 MASTER 233 YARD
031 BURNER 182 SHOW
• 083 FATHERS 133 MAT • 183 SIDE 234 ZN-1
032 CABINET • 084 FENCE • 134 MEDICAL 184 SKYLIGHT • 235 ZONE
• 033 CALL 085 FILE 135 MEDICINE 185 SLIDING
034 CAMERA • 086 FIRE 136 MICROWAVE • 236 0
• 186 SMOKE
035 CAR • 087 FLOOR 137 MONEY • 237 1
187 SONIC
036 CASE 088 FLOW 138 MONITOR • 238 1ST
• 188 SONS
037 CASH 089 FOIL • 139 MOTHERS • 239 2
• 189 SOUTH
038 CCTV • 090 FOYER • 140 MOTION • 240 2ND
190 SPRINKLER
039 CEILING 091 FREEZER 141 MOTOR • 241 3
191 STAMP
040 CELLAR • 092 FRONT 142 MUD • 242 3RD
• 192 STATION
• 041 CENTRAL 093 FUR • 243 4
• 143 NORTH 193 STEREO
042 CIRCUIT 094 FURNACE • 244 4TH
144 NURSERY 194 STORE
043 CLIP • 245 5
095 GALLERY • 195 STORAGE
• 044 CLOSED • 145 OFFICE • 246 5TH
• 096 GARAGE 196 STORY
045 COIN 146 OIL • 247 6
• 097 GAS 197 STRESS
046 COLD • 147 OPEN
098 GATE 198 STRIKE • 248 6TH
047 COATROOM 148 OPENING
• 099 GLASS 199 SUMP • 249 7
048 COLLECTION • 149 OUTSIDE
100 GROUND 200 SUPERVISED • 250 7TH
049 COMBUSTION 150 OVERFLOW
101 GUEST 201 SUPERVISION • 251 8
• 050 COMPUTER 151 OVERHEAD
102 GUN 202 SWIMMING • 252 8TH
051 CONTACT
203 SWITCH • 253 9
• 254 9TH
255 Custom Word 1
to
314 Custom Word 60
CHARACTER (ASCII) CHART
(For Adding Custom Words)
32 (space) 42 * 52 4 62 > 72 H 82 R
33 ! 43 + 53 5 63 ? 73 I 83 S
34 " 44 , 54 6 64 @ 74 J 84 T
35 # 45 - 55 7 65 A 75 K 85 U
36 $ 46 . 56 8 66 B 76 L 86 V
37 % 47 / 57 9 67 C 77 M 87 W
38 & 48 0 58 : 68 D 78 N 88 X
39 ' 49 1 59 ; 69 E 79 O 89 Y
40 ( 50 2 60 < 70 F 80 P 90 Z
41 ) 51 3 61 = 71 G 81 Q
NOTE: This factory-provided vocabulary of words is subject to change.
– 30 –
Device Programming
This menu is used to program keypads, receivers, and relay modules, etc.
Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression
options, and these settings cannot be changed.
From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?"
PROMPT EXPLANATION
DEVICE ADDRESS The device address identifies the device to the control. Enter the 2-digit device address number to match
the device's physical address setting (01-30).
01-30, 00=QUIT 01
Press [∗] to accept entry.
Alpha Keypad
PROMPT EXPLANATION
01 CONSOLE PART. If you selected device type 01 (alpha keypad), this prompt appears. Enter the addressable device's default
partition number (1 to maximum number of partitions programmed for system in field 2∗00). This is the
1
primary partition for the device. Enter 3 to make this keypad a "Master" keypad for the system.
Press [∗] to accept entry.
01 SOUND OPTION If you entered device type 01 (alpha keypad), this prompt appears. Keypads can be individually
programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode beeps. This helps prevent
00
unwanted sounds from disturbing users in other areas of the premises.
Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows:
00 = no suppression
01 = suppress arm/disarm & entry/exit beeps
02 = suppress chime mode beeps only
03 = suppress arm/disarm, entry/exit and chime mode beeps
Press [∗] to accept entry.
01 KEYPAD GLBL? If you entered device type 01 (alpha keypad), this prompt appears. Each keypad can give users with access
to multiple partitions the ability to arm and disarm those partitions from it. To enable this keypad for global
0
arming/disarming, enter 1. To prevent the ability to use this keypad for global arming/disarming, enter 0.
Press [∗] to accept entry.
RF Expander
PROMPT EXPLANATION
01 RF EXPANDER If you selected device type 03 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31).
HOUSE ID 00 Press [∗] to accept entry.
– 31 –
Output Relay Module
PROMPT EXPLANATION
01 SUPERVISED CF? If you selected device type 04 (relay module), this prompt appears. Enter 1 if the unit is a 4204CF. If not,
enter 0. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed
0
for functions.
NOTE: For Commercial Fire installations, only one notification appliance module may be used, and only one
notification appliance output (A or B) may be used on that module.
Press [∗] to accept entry.
Communicator
If you selected device type 6, the 6160 and 6160CR-2 Keypad functions similarly to the 7720P Programming Tool. See Figure
1 for the functions of the keys on the 6160CR-2.
A B C
ARMED (A) BS/ESC 1 OFF 2 AWAY 3 STAY
READY D E F
FUNCTION ALARM S T X
WHEN LIT SILENCED (C) N/Y 7 INSTANT 8 CODE 9 CHIME
SUPV SPACE ENTER
TROUBLE (D) SHIFT READY
0 #
6160CR2-001-V1
6160CR-2
6160
NOTE: The 6160CR-2 must be used in Commercial
Fire installations
Figure 1: 6160CR-2 Key Functions for Programming the Communicator
Each key has two possible functions: a normal function and a SHIFT function. To perform a normal key function, simply press
the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.
Normal and SHIFT key Functions:
Key Normal Key Function SHIFT Key Function
BS/ESC [BS]: Press to delete entry [ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults *
↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming
N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
SHIF Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is
T pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number
2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number
3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number
4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number
5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number
6/F [6]: For entering the number 6 [F]: Used for C.S. ID & FAST Mode
7/S [7]: For entering the number 7 [S]: Press to display diagnostic status
8/T [8]: For entering the number 8 [T]: Press to send TEST messages
9/X [9]: For entering the number 9 [X]: Press to reset the 7845i-ent
∗/SPACE [∗]: Not used with 7845i-ent [SPACE]: Not used with 7845i-ent
0 [0]: For entering the number 0 No SHIFT function
#/ENTER [#/ENTER]: Press to accept entries No SHIFT function
* Active only when the "REVIEW?" prompt is displayed.
– 32 –
The 6160/6160CR-2 Keypad displays the following prompts, which are sent by the Communicator to the control.
NOTE: These prompts are for the 7845i-ent Communicator only. If you are using a different communicator, refer to
the communicator’s instructions for the correct prompts.
PROMPT EXPLANATION
DEVICE ADDRESS Enter the device address of the Communicator. The default address is 3.
ID # Enter the 4-digit customer account number, 0001-9999. This ID number will appear in the messages
generated by the Communicator. Messages generated by the panel and transmitted by the Communicator
(1234)
will contain the ID number programmed into the panel. The Communicator and the panel should have the
same ID number, if possible.
If a different 4-digit customer account number is used in the Communicator that is programmed into the alarm
control, the Communicator will transmit Communicator-specific messages (power-on reset, AC fail, etc.) using the
Communicator customer number, and alarm messages using the control panel’s customer number. If these
numbers are different, you will be billed for two AlarmNet Communicator accounts.
PROMPT EXPLANATION
ODD [Y/N] Enter Y for odd system flag; N for even system flag.
(N)
Alarmnet (Y/N) Enter Y if this is an AlarmNet installation. Enter N if this is a private system and skip to Question 7.
(Y)
CS ID Enter the primary central station’s system ID number 1-7F (will not be displayed for private system users).
(11)
BAT PRESENT [Y/N] Enter Y if optional battery will be used. Must be Y for UL installations (a battery must be installed).
(N)
USE RADIO # [Y/N] If you selected Y, the Communicator ID number replaces the panel Subscriber ID in panel-generated
messages.
(N)
If you selected N, the Communicator sends panel-generated messages with the panel Subscriber ID
number.
2ND CS ID This must be programmed with a value, even if it is the same as the primary central station. The
alarm panel has the option of sending a selected message to the second central station.
(12)
REVIEW (Y/N) Enter Y to review the programming options and to ensure that the correct responses have been made.
Parameters can be changed during review.
(N)
Enter N to end programming session.
– 33 –
Output Programming
The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output
must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a
designated STOP event. The options used to start and stop these devices are described below, followed by the actual screen
prompts and available entries.
NOTE: If you are using outputs on the polling loop (e.g., 4101SN) no more than 20 of the polling loop outputs may be
programmed for the same START or STOP condition. Also, if you are using ZONE # for the START of a polling loop
output and want that output to stop when the same zone restores, the STOP programming MUST BE BLANK.
If you are using Zone Type 17 (Waterflow) or 18 (Fire Supervisory) to trigger an output, you must program an Event
for the START (alarm, trouble, etc.). All other Zone Type/System Operations do not require an Event.
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the
various summary displays of programmed data during programming.
ACTION (A) The "ACTION" of the device is how the device will respond when it is activated by the "START"
programming. You may want the device to activate momentarily, to pulse on and off continuously, or to
remain activated until some other event occurs to stop it. There are five different action choices:
• ACTIVATE for 2 SECONDS and then reset. If selected, it is not necessary to program a stop
parameter.
• ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
• PULSE ON and OFF until stopped by some other event.
• NO RESPONSE when the device is not used.
• TOGGLE on and off alternately with each activation of event. Do not program a stop parameter as
this may cause unpredictable results.
START (STT) The "START" programming determines when and under what conditions the device is activated. The
following START options are available:
1) EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone
list) in order to activate the device. These conditions apply only when a zone list is used. The different
choices for "EVENT" are listed below and in “Programming Relays” later in this section.
• ALARM Action begins upon any alarm in an assigned zone in the zone list.
• FAULT Action begins upon any opening of an assigned zone in the zone list.
• TROUBLE Action begins upon any trouble condition in an assigned zone in the zone list.
• NOT USED Action is not dependent upon one of the above events.
ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular
device. Note that there are a total of 15 zone lists that can be programmed; when the selected EVENT
(alarm, fault or trouble) occurs in any zone in the selected “Start” ZONE LIST (01-15), activation of the
selected device will START.
2) ZONE # A specific zone going into alarm, fault, trouble, or restore (Event programming) can be used to
start the relay action. Enter the 3-digit zone number (000-032).
3) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same
response type, and there are no other zones of this type that are not to activate this device, then
“ZONE TYPE” may be used instead of a "ZONE LIST" and "EVENT” to activate the device.
If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate the device, enter
the appropriate choice under the “ZONE TYPE” option.
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “EVENT/ZONE
LIST” combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault
will cause the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen for
the STOP programming, any zone of that type that restores will de-activate the device.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate as selected in
"ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in
“Programming Relays” later in this section, and on the Programming Form.
4) PARTITION NO. (P). The device's "Start" ZONE TYPE/SYSTEM OPERATION may be limited to an
occurrence on one partition (1-2), or any partition (0).
– 34 –
STOP (STP): The "STOP" programming determines when and under what conditions the device is de-activated. The
following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the device de-activates
when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs
regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" is
normally only used when a "ZONE LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," you can select
a specific zone (response) type or system operation action to de-activate the device.
If you choose a specific "ZONE TYPE," any zone of that response type that restores from a previous
alarm, trouble, or fault condition will cause the device to de-activate.
If you choose a "SYSTEM OPERATION," that operation causes the device to de-activate. The
different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Programming Relays”
later in this section, and in the Programming Form.
3) PARTITION NO. (P). The device's "Stop" Zone Type/System Operation may be limited to an
occurrence on one partition (1-2), or on any partition (0).
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the
“RESTORE/ZONE LIST” combination.
Output Devices Programming
From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option
until the "OUTPUT PGM?" prompt appears. Press [1] (YES).
While in this mode, press [∗] to advance to next screen. Press [#] to back up to the previous screen.
PROMPT EXPLANATION
ENTER RELAY # Enter the relay (output device) identification number 01-96. This is a reference number only, used for
identification purposes. The actual module address and relay number on the module are programmed in the
(00=QUIT) 01
last two prompts.
Press [∗] to continue.
02 RELAY ACTION The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the
desired action for this relay as follows:
NO RESPONSE 0
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off; 4= toggle on and off alternately
NOTE: For options 1 and 4, do not program a “Stop” parameter.
02 START EVENT An output may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation.
For an Event/Zone List combination, enter the event code as follows:
NOT USED 0
0=not used; 1=alarm; 2=fault; 3=trouble
NOTE: An Event is required for Zone List, Zone Number and Zone Types 17 and 18.
If you are not using a Zone List, Zone Number, or Zone Types 17 or 18 to activate the relay, enter 0.
Press [∗] to continue.
02 START: ZN LIST A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being
used to start this relay action, enter the zone list number, 1-15. If a zone list is not being used, enter 0.
00
Press [∗] to continue.
02 START: ZONE # A specific zone can be used instead of or in addition to an Event/Zone List or Zone Type/System Operation
combination to start the relay action. Enter the 3-digit zone number.
000
Press [∗] to continue.
02 START: ZN TYPE A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or
a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit
NO RESPONSE 00
code as listed in the table that follows.
Press [∗] to continue.
– 35 –
Choices for Start/Stop Zone Types and System Operations:
00 = No Response (Not Used) 22 = Disarming (Code + Off) 43 = Communication failure
01 = Entry/Exit #1 23 = No Alarm Response 44 = RF Low Battery
02 = Entry/exit #2 27 = Access Point (allows more than one 45 = Polling Loop Failure
03 = Perimeter relay to be controlled by activation if access 47 = Console Failure
04 = Interior Follower point request) - Not Used 51 = RF Receiver Failure
05 = Trouble Day/Alarm Night 28 = MLB Supervision - Not Used 52 = Kissoff
06 = 24-Hr. Silent 29 = Momentary Exit - Not Used 54 = Smoke Detector Reset
07 = 24-Hr. Audible 30 = On Second Code + Off 55 = Disarm + 1 Minute
08 = 24-Hr. Auxiliary 31 = End of Exit Time 56 = XX Minutes (enter XX in field 1∗74) *
09 = Fire Alarm or Trouble 32 = Start of Entry Time 57 = YY Seconds (enter YY in field 1∗75) *
10 = Interior W/Delay 33 = Any Burglary Alarm 58 = Duress
12 = PLM Supervision - Not Used 34 = Code + [#] + 71 Key Entry
13 = Remote P/S 35 = Code + [#] + 72 Key Entry
14 = CO Detector Alarm 36 = At Bell 1 Timeout ** 60 = Audio Alarm Verification (must be
16 = Fire With Verification 37 = 2x Bell 1 Timeout ** selected for both START and STOP
17 = Waterflow***** 38 = Chime operation)
18 = Fire Supervisory 39 = Fire Alarm 61 = Code + [#] + 67
19 = 24-Hour Trouble 40 = Bypassing 62 = Bell 2 Timeout
20 = Arming-STAY*** 41 = AC Power Fail 63 = Auxiliary Relay Timeout
21 = Arming-AWAY**** 42 = System Battery Low
* Stop condition only
** Or at disarming, whichever occurs earlier
*** The output also activates when the partition is armed in the INSTANT mode
**** The output also activates when the partition is armed in the MAXIMUM mode
***** Use an event of fault or alarm as the START option
If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1∗74
and 1∗75 for the respective relay timeouts for minutes and seconds.
Do not use a zone programmed with an RF Button (Input Type BR) to STOP a relay. The system will not de-
activate the relay.
PROMPT EXPLANATION
02 STOP: ZN LIST If a zone list is being used to stop this relay action, enter the zone list number, 1-15. The restore of a zone
on the zone list stops the relay. If a zone list is not being used, enter 0.
00
Press [∗] to continue.
02 STOP: ZN TYPE If a Zone Type/System Operation is being used to stop the relay action, enter the 2-digit code listed in the
Choices for Start/Stop System Operation chart.
NO RESPONSE 00
NOTE: If a 4204CF is being used, the stop action for a NAC must be programmed as zone type 62, Bell 2
Timeout. Only one relay of the 4204CF may be used for this function.
Press [∗] to continue.
02 STOP: PARTN This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter 1-2 for specific
partition number.
ANY PARTITION 0
Press [∗] to continue.
02 RELAY GROUP Relays may be grouped for common activation by time-driven events (commands 06-10). Enter 00 (no
group) or 01-15 for a specific group number.
00
Press [∗] to continue.
02 FIRE BELL Enter 1 only if this output is to be used to activate a fire alarm sounder.
1=YES 0=NO 0 Press [∗] to continue.
02 RESTRICTION The system may have some devices that are not intended to be under end user control, such as relays
activating fire doors or machinery.
1=YES 0=NO 0
NOTE: #70 must be set to yes for Commercial Fire installations.
Enter 1 if the end user will be restricted from accessing this relay group.
Press [∗] to continue.
– 36 –
PROMPT EXPLANATION
02 RELAY TYPE Enter 0 for V-Plex (polling loop) devices. Enter 1 for (ECP) relay modules (4204/4204CF).
V-PLEX 0 Press [∗] to continue.
02 V-PLEX ZONE # For polling loop trigger outputs (4101SN), enter the protection zone number (001-032) linked to each output,
if used. Be sure to enroll the module’s serial number (see Zone Programming).
000
Press [∗] to continue.
02 ECP ADDRESS If you selected 1 (4204/4204CF), enter the actual module's address (01-15) as set by its DIP switches. Up
to 8 4204/4204CF modules can be installed in a system.
00
Press [∗] to continue.
02 MODULE RELAY# For 4204 Relay Outputs, enter the specific relay number on that module (1-4). For 4204CF outputs, enter
only module relay number 1 (Output A) or relay number 3 (Output B). These are the only two
0
programmable relays on the 4204CF Module.
Press [∗] to continue.
The keypad will display the Start and Stop summary screens again.
Press [∗] to continue.
When all relays have been programmed, enter 00 at the "ENTER RELAY NO." prompt.
If you are defining a zone list, continue to the next section. If not, enter 00 + [∗] at the next two prompts. You will then be
asked "Quit Menu Mode?" Enter 1 for "Yes," 0 for "No." Then enter ∗99 to exit programming completely.
If supervision of the 4204CF Relay Output is desired, enter a response type for that output's corresponding supervisory zone.
This is equal to 600 + [Relay ID No.]. For example, if you are programming Relay ID No. 1, the relay's supervisory zone 601.
Program this zone with response type 05 (Day/Night) in Zone Programming.
Zone List Programming
After all relays have been programmed, upon entering 00 at the "ENTER RELAY NO." prompt, you are asked to enter a zone
list. If a zone list number was used to start or stop a relay, you must define the zones belonging to that list as follows:
PROMPT EXPLANATION
ENTER Zn LIST ? Enter the zone list number 01-15. Enter 00 to quit.
00=QUIT 00
01 ADD ZONE # Using 3-digit entries enter each zone to be included in this zone list. Press [∗] after you enter each zone
number.
00=QUIT 00
When you have entered all zones, enter 000.
Press [∗] to continue.
01 Del Zn LIST ? Enter 0 to save this zone list. Enter 1 to delete it.
1=YES 0=NO 0
01 DEL ZONES ? Enter 1 to delete one or more zones in that zone list. Enter 0 if no changes are necessary. If you enter 1,
the following screen appears; otherwise, the "Enter Zone LIST" prompt reappears.
1=YES 0=NO 0
01 Zn to DELETE ? Enter each zone number to be deleted from the zone list, pressing [∗] after each number.
00=QUIT 01
VIEW Zn LIST ? This display appears if you pressed 00 at the “Enter Zone LIST” prompt. Enter the zone list number that you
wish to view.
00=QUIT 00
Press [∗] to continue.
01 ASSIGNED ZONE Press [∗] to scroll through all zones in that list. Enter 000 + [∗] to quit.
00=QUIT 00 Press [1] to exit Menu Mode.
Press ∗99 to exit Program Mode.
– 37 –
Relay Voice Descriptors
Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes
Vocabulary list (later in this section).
The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal
system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary
list in the Alpha Programming part of this guide.
PROMPT EXPLANATION
RLY VOICE DESCR? Press [1] to program voice descriptors for relays.
1=YES 0=NO 0
ENTER RELAY NO. Enter the 2-digit relay number (01-32) for the relay desired, or enter 00 to quit Relay Voice Descriptor
Programming Mode.
00=QUIT 01
Press [∗]
01 ENTER DESC d1 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the first word of the relay descriptor phrase.
Press [∗] to accept entry.
01 ENTER DESC d2 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the second word of the relay descriptor phrase. If second word is not desired, press [000].
Press [∗] to accept entry.
01 ENTER DESC d3 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the third word of the relay descriptor phrase. If third word is not desired, press [000].
Press [∗] to accept entry. The “ENTER RELAY NO.” prompt appears. Enter the next relay number to be
programmed. When you have programmed all output devices, enter 00 to quit.
Enter ∗99 to exit Program Mode.
– 38 –
Relay Voice Descriptors and Custom Word Substitutes Vocabulary
Word Index Word Index Word Index Word Index Word Index
Air.............................116 Device...................... 060 Gas...........................138 Off ............................ 011 Smoke .....................024
Alarm........................255 Dim .......................... 163 Glass ........................139 Office........................ 147 South .......................155
And...........................067 Dining....................... 031 On ............................ 058 Stairs .......................006
Apartment.................117 Door ......................... 016 Hall ...........................050 One .......................... 070 Station .....................156
Appliances................161 Down........................ 008 Heat..........................010 Open ........................ 148 Storage ....................157
Area .........................118 Downstairs ............... 184 Outside..................... 210 Sun ..........................154
Attic ..........................119 Driveway .................. 130 Inside........................209 System.....................062
Duct ......................... 131 Panic ........................ 013
Back .........................121 Kitchen .....................022 Partition.................... 090 Temperature ............158
Bar ...........................122 East ......................... 132 Patio......................... 149 Third ........................159
Basement .................021 Eight ........................ 077 Laundry ....................140 Phone....................... 061 Three .......................072
Bathroom..................051 Eighth....................... 221 Left ...........................027 Power....................... 063 Tool..........................213
Battery......................053 Equipment................ 133 Library ......................141 Pump........................ 166 Two..........................071
Bedroom...................015 Exit........................... 004 Light .........................019
Blower ......................123 Living ........................030 Rear ........................ 088 Up ............................025
Boiler........................124 Factory..................... 134 Loading.....................142 Right......................... 028 Upper.......................187
Bright........................162 Fence....................... 135 Lower........................094 Room ....................... 018 Upstairs....................183
Building ....................125 Fifth.......................... 218 Utility........................185
Burglary....................039 Fire .......................... 040 Machine....................143 's .............................. 007
First ......................... 136 Master ......................144 Second..................... 056 West ........................215
Central......................089 Five.......................... 074 Medical .....................014 Service ..................... 150 Window....................017
Chime.......................054 Floor ........................ 029 Motion.......................145 Seven....................... 076 Wing ........................216
Closed ......................126 Four ......................... 073 Seventh.................... 220
Computer .................127 Fourth ...................... 217 Nine ..........................078 Shed......................... 151 Zero .........................069
Console ....................066 Foyer........................ 137 Ninth .........................222 Shop......................... 152 Zone ........................002
Front ........................ 087 No.............................165 Side......................... 153
Den ..........................052 North.........................146 Six........................... 075
Detector....................128 Garage..................... 023 Not............................012 Sixth ........................ 219
– 39 –
System Layout Worksheets
Before programming any security system, you should first define the installation. To help you lay out a partitioned
system, use the following worksheets. This will further simplify the programming process.
PARTITIONS
Partition # Descriptor (4-char max) Prim. Sub. # Sec. Sub. # Alpha Default Message (32-character maximum)
Partition 1
Partition 2
Keyswitch Arming Partition Assignment (1-2 ):
Wireless Keypad Partition Assignment (1-2):
Use Partition Descriptor (yes/no)?
Common Lobby Partition Assignment (1-2):
COMMUNICATION OPTIONS BY PARTITION
Option Part. 1 Part. 2
Swinger Suppression Count 00-15; 00=no suppression
Cancel Report After Disarm
Dialer Reports for Panic (∗ + 1)
Dialer Reports for Panic (# + 3)
Dialer Reports for Panic (∗ + #)
Dialer Reports for Duress
Burglary Alarm Communications Delay (16 sec.)
SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no)
Option Part. 1 Part. 2
Entry Delay #1 (00, 30-225 seconds):
Exit Delay #1 (00, 45-225 seconds):
Entry Delay #2 (00, 30-225 seconds):
Exit Delay #2 (00, 45-225 seconds):
Quick Arming
Multiple Alarms per Arming
Console Panic for Zone 995 (∗ + 1)
Console Panic for Zone 996 (# + 3)
Console Panic for Zone 999 (∗ + #)
Allow Sign-on (GOTO function)
Non-Bypassable Zone (001-032)
Bell 1 Sounder Duration (2 min. increments)
Bell 2 & Aux Relay Sounder Duration for (2 min. incr.)
Console Annunciation During Entry (3 beeps or continuous)
Console Annunciation During Exit
Bell 1 Confirmation of Arming Ding
Bell 2 & Aux Relay 1 Confirmation of Arming Ding
Chime on Bell 1
Chime on Bell 2 & Aux Relay
Access Control Relay (field 1∗76)
Affects Lobby (check partitions that apply)
Arms Lobby (check partitions that apply)
Display Fire Alarms of Other Partitions
Display Burg & Panic Alarms of Other Partitions
Display Troubles of Other Partitions
PRINTER OPTIONS
12- or 24-hour Time format EVENT LOG TYPES
Printer On-Line (yes/no) Option No Yes
1200 or 300 baud Printer Baud Rate Alarm
Trouble
Bypass
Open/Close
System
Test
– 40 –
DEVICES (keypads, 4204, rf receivers, communicator)
Sound Supv House Kypd Panel
Addr Type Part
Opt CF? ID Glbal ID
00. Device Types:
01. 00 = Device Not Used
02. 01 = Alpha Console
03 = RF Receiver
03.
04 = Output Relay Module
04.
05 = Not Used
05. 06 = Communicator
06. 09 = Not Used
07. 10 = Not Used
08.
09. Console Sounder Options:
0 = No Suppression
10.
1 = Suppress Arm/Disarm and Entry/Exit Beeps
11. 2 = Suppress Chime Mode Beeps Only
12. 3 = Suppress Arm/Disarm, Entry/Exit and Chime
13. Mode Beeps
14.
15. Defaults:
Addresses 00 = Alpha Keypad; No Suppression
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
Authority Levels: 1=Master (arm, disarm, bypass, and/or modify lower level users) 6=Duress code (arm, disarm, triggers silent
2=Manager (arm, disarm, bypass, and/or modify lower level users) panic alarm)
3=Operator A (arm, disarm, bypass) Defaults:
4=Operator B (arm, disarm) User 4-Digits Alpha
5=Operator C (arm, disarm only if system was armed with this code) User 1 (Installer) 5140 INSTLR
– 41 –
ZONE DEFINTION FOR ZONES 01-25
Zone Zone Part Input Arm Vent STAY Auto- Silent Bypass Access Panel Tamper Serial # / Loop Bell/Relay Rpt. Zone Information & Alpha
No. Type 1-2 Type w/Fault Zone Mode STAY Group Point ID # Activation Code Descriptor (3 words max.)
10
11
12
— 42 —
13
14
15
16
17
18
19
20
21
22
23
24
25
ZONE DEFINTION FOR ZONES 26-32
Zone Zone Part Input Arm Vent STAY Auto- Silent Bypass Access Panel Tamper Serial # / Loop Bell/Relay Rpt. Zone Information & Alpha
No. Type 1-2 Type w/Fault Zone Mode STAY Group Point ID # Activation Code Descriptor (3 words max.)
26
27
28
29
30
31
32
— 43 —
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, and 999
Enter yes/no for each partition-field ∗22
Zone Zone Bell/Relay Report Zone Information and
No. Type 1 2 Activation Code Alpha Descriptor (3 words max.)
995
(see
note
below)
996
999
ZONE DEFINITIONS FOR SYSTEM ZONES; 970 − 975, 988, 990 and 997
Zone Information
Zone Zone Bell/Relay Report
and
No. Type Activation Code
Alpha Descriptor (three words max.)
970
971
972
973
974
975
988
990
997
— 44 —
ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-632
Zone Information Zone Information
Zone Zone Report Zone Zone Report
and and
No. Type Code No. Type Code
Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.)
601 617
602 618
603 619
604 620
605 621
606 622
607 623
608 624
609 625
610 626
611 627
612 628
613 629
614 630
615 631
616 632
NOTE: Only the relays on 4204CF modules may be supervised. If supervision is programmed for other
types of Output Devices, unpredictable results may occur.
— 45 —
ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-830
Zone Information Zone Information
Zone Zone Report Zone Zone Report
and and
No. Type Code No. Type Code
Alpha Descriptor (3 words max.) Alpha Descriptor (3 words max.)
800 816
801 817
802 818
803 819
804 820
805 821
806 822
807 823
808 824
809 825
810 826
811 827
812 828
813 829
814 830
815
Zone Types
00=zone not used 07=24-hour audible 16=fire w/verification 22=disarm
01=entry/exit 1 08=24-hour auxiliary 17=waterflow 23=no alarm response
02=entry/exit 2 09=supervised fire 18=supervisory 27=Not Used
03=perimeter 10=interior (delay) 19=24-hour trouble 28=Not Used
04=interior (follower) 12=Not Used 20=arm stay 29=Not Used
05=day/night burglary 13=remote P/S 21=arm away
06=24-hour silent 14=CO detector alarm
— 46 —
Output Devices Worksheets
Applicable only if relays (4204/4204CF) or V-Plex are used.
Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on
the worksheet below and follow the procedure in the installation and setup guide as you enter the data during the
displays and prompts that appear in sequence.
NOTES: 1. For 4204/4204CF, the Device Programming section must be programmed for the device address. Set the
DIP switches on the device for that address.
2. For V-Plex, devices must be programmed in the Zone Programming section
3. If you are using outputs on V-Plex (e.g., 4101SN) no more than 20 of the V-Plex outputs may be
programmed for the same START or STOP condition. Also, if you are using ZONE # for the START of a
V-Plex output and want that output to stop when the same zone restores, the STOP programming MUST
BE BLANK.
S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for
OUTPUT Relay 1=4204/ or 4204/
A Restrict
DEV # EV/ZL Zone ZT / P ZL ZT / P Group 4204CF Dev Add 4204CF
4204/4204CF
10
11
12
13
14
15
16
17
18
19
20
— 47 —
OUTPUT DEVICES WORKSHEET (cont’d)
S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for
OUTPUT Relay 1=4204/ or 4204/
A Restrict
DEV # EV/ZL Zone ZT / P ZL ZT / P Group 4204CF Dev Add 4204CF
4204/4204CF
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
— 48 —
OUTPUT DEVICES WORKSHEET (cont’d)
S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for
OUTPUT Relay 1=4204/ or 4204/
A Restrict
DEV # EV/ZL Zone ZT / P ZL ZT / P Group 4204CF Dev Add 4204CF
4204/4204CF
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
— 49 —
OUTPUT DEVICES WORKSHEET (cont’d)
S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for
OUTPUT Relay 1=4204/ or 4204/
A Restrict
DEV # EV/ZL Zone ZT / P ZL ZT / P Group 4204CF Dev Add 4204CF
4204/4204CF
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
— 50 —
A = DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 =
Toggle alternately between START and STOP events
EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore
ZL = ZONE LIST 01-15, 00 = Not Used
"START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device
action will START.
"STOP" ZONE LIST: Upon restore of ALL zones on this list, device action will STOP. It
need not be same list as used for START.
ZT = ZONE TYPE/SYSTEM OPERATION
Choices for Zone Type/System Operation are:
00 = No Response (Not Used) 21 = Arming-AWAY**** 41 = AC Power Fail
01 = Entry/Exit #1 22 = Disarming (Code + Off) 42 = System Battery Low
02 = Entry/exit #2 23 = No Alarm Response 43 = Communication Failure
03 = Perimeter 27 = Access Point (allows more than one 44 = RF Low Battery
04 = Interior Follower relay to be controlled by activation if 45 = Polling Loop Failure
05 = Trouble Day/Alarm Night access point request) - Not Used 47 = Console Failure
06 = 24-Hr. Silent 28 = MLB Supervision - Not Used 51 = RF Receiver Failure
07 = 24-Hr. Audible 29 = Momentary Exit - Not Used 52 = Kissoff
08 = 24-Hr. Auxiliary 30 = On Second Code + Off 54 = Fire Zone Reset
09 = Fire Alarm or Trouble 31 = End of Exit Time 55 = Disarm + 1 Minute
10 = Interior W/Delay 32 = Start of Entry Time 56 = XX Minutes (enter XX in field 1∗74) *
12 = PLM Supervision - Not 33 = Any Burglary Alarm 57 = YY Seconds (enter YY in field 1∗75)
Used *
13 = Remote P/S 34 = Code + [#] + 71 58 = Duress
14 = CO Detector Alarm 35 = Code + [#] + 72 60 = Audio Alarm Verification (must be
16 = Fire With Verification 36 = At Bell Timeout ** selected for both START and STOP
17 = Waterflow***** 37 = 2 Times Bell Timeout ** operation)
18 = Fire Supervisory 38 = Chime 61 = Code + [#] + 67
19 = 24-Hour Trouble 39 = Fire Alarm 62 = Bell 2 Timeout
20 = Arming-STAY*** 40 = Bypassing 63 = Auxiliary Relay Timeout
* Stop condition only
** Or at disarming, whichever occurs earlier
*** The output also activates when the partition is armed in the INSTANT mode
**** The output also activates when the partition is armed in the MAXIMUM mode
***** Use an event of fault or alarm as the START option
P = PARTITION No. 1-2, 0 = Any
ZONE LISTS FOR OUTPUT DEVICES – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the
required data on the worksheet below and follow the procedure shown earlier in this Programming Guide as you enter the
data during the displays and prompts that appear in sequence. Up to 15 zone lists may be created
NOTE:Record desired zone numbers below. More or fewer boxes than shown may be needed, as any list may include any or
all of system's zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 3: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 4: Started or stopped by zone numbers (enter 000 to end entries).
— 51 —
Zone List 5: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 6: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 7: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 8: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 9: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 10: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 11: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 12: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 13: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 14: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 15: Started or stopped by zone numbers (enter 000 to end entries).
— 52 —
Scheduling Menu Prompts
To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the
menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode.
Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
Menu selections are as follows:
PROMPT EXPLANATION
Time Window ? For defining up to 20 time windows each with a start and a stop time programmed by entering the hours and
minutes.
1 = YES 0 = NO 0
O/C Schedules ? For defining the daily open and close schedules for the 2 partitions. Each partition can be programmed with
an opening and closing window for each day of the week and holidays.
1 = YES 0 = NO 0
Timed Events ? For defining up to 20 time driven events with the following parameters:
1 = YES 0 = NO 0 • Time window
• Action desired
• Action specifier
• Activation time
• Days of the week
Access Sched. ? For defining the limitation of access schedules for the user codes. Each schedule can be programmed with
two windows for each day of the week and holidays
1 = YES 0 = NO 0
— 53 —
Scheduling Worksheets
Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times.
They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in
the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
Time Window Start Time Stop Time
Number (HH:MM) (HH:MM)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
(Keep this worksheet handy, as you will be asked for a given time window number later in this section.)
Because the time windows are shared among both partitions, it is important to make sure that
changing a time window does not adversely affect desired actions in the other partition.
Daily Open/Close Schedule Worksheet: Using the time windows previously defined, fill in the required data on the
worksheet below and follow the procedure in the installation and setup guide as you enter the data during the displays and
prompts that appear in sequence.
Part Mon Tues Wed Thur Fri Sat Sun Hol
Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl Op Cl
1
2
— 54 —
Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday
can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in
the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
HOL Partition
Month/Day 1 2
1 /
2 /
3 /
4 /
5 /
6 /
7 /
8 /
9 /
10 /
11 /
12 /
13 /
14 /
15 /
16 /
Time-Driven Event Worksheet: The system provides up to 20 time-driven events that can be programmed for the system.
Fill in the required data on the worksheet below and follow the procedure in the installation and setup guide as you enter the
data during the displays and prompts that appear in sequence.
— 55 —
Automatic Refresh: The system automatically updates the status of all Time-Driven Events upon any of the following
occurrences:
• Changing of the time or date via #63 mode
• Exiting #80 Scheduling Menu mode
• Exiting Program mode
• After a disconnect from the downloader
• On a power-up
• At Daylight Saving Time adjustment.
Below is a list of the "Action" codes (desired actions) used when programming time-driven events. Note that these codes are
independent of the "relay codes" programmed during the #93 Menu Mode–Output Programming mode. If using Time-
Driven Events, the following menu items must first be programmed using #93 Menu Mode - Output Programming:
Enter Relay No. (reference identification number) Zone No. (V-Plex)
Relay Group (if applicable) ECP Address (4204/4204CF)
Restriction Relay No. (4204/4204CF)
Relay Type (V-Plex or 4204/4204CF)
Relay commands:
Action Specifier for commands 01-05 is Relay No.; Action Specifier for commands 06-10 is Relay Group No.
01 = Relay On 02 = Relay Off
03 = Relay Close for 2 seconds 04 = Relay Close XX minutes (field 1∗74)
05 = Relay Close YY seconds (field 1∗75) 06 = Relay Group On
07 = Relay Group Off 08 = Relay Group Close for 2 seconds
09 = Relay Group Close XX minutes (field 1∗74) 10 = Relay Group Close YY seconds (field 1∗75)
Arm/Disarm commands:
Action Specifier for commands 20-24 is Partition(s). Activation times 1 (Beginning), 2 (End), 3 (During), 5 (Random Start), 6
(Random End), 7 (Random During) are the only valid choices for auto-arming and disarming functions.
20 = Arm-Stay 21 = Arm Away
22 = Disarm 23 = Force Arm Stay (Auto-bypass faulted zns)
24 = Force Arm Away (Auto-bypass faulted zns)
Bypass commands:
Action Specifier for commands 30-31 is Zone List #, Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid
choices for bypass commands.
30 = Auto bypass - Zone list 31 = Auto unbypass - Zone list
Open/Close Windows:
Action Specifier for commands 40-41 is Partition(s), for 42 is Access Group and for 50 no specifier is programmed.
Activation time 3 (During) is the only valid choices for these commands.
40 = Enable Opening Window 41 = Enable Closing Window 42 = Enable Access Window
50 = Off-Normal Reminder (Starts local keypad beeping if off-normal condition exists)
— 56 —
Activation time:
Refers to when the action is to take place relative to the time window.
1 = Beginning of time window
2 = End of time window
3 = During time window active period only (On at
beginning of window, off at end).
Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system.
Fill in the required data on the worksheet below and follow the procedure in the installation and set guide as you enter the data
during the displays and prompts that appear in sequence.
Temporary Schedule #81 Menu Mode. The system provides a Temporary Schedule for each partition. Enter the temporary
scheduling mode by pressing [Installer Code] + [#] + [81]. Fill in the required data on the worksheet below and follow the
procedure in the installation and setup guide as you enter the data during the displays and prompts that appear in sequence.
— 57 —
NOTES
— 58 —
NOTES
— 59 —
NOTES
— 60 —
NOTES
— 61 —
NOTES
— 62 —
COMMERCIAL PROTECTED PREMISE CONTROL UNIT
TEST BURGLARY SYSTEM WEEKLY
FOR DRY, INDOOR USE ONLY
WARNING: TYPES OF FIRE SIGNALING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm. UL Listed local control (non-coded).
This unit includes a Fire Alarm Verification feature that will result in a delay of UL Listed central station and remote station protected premises unit when used with 5140DLM back-up dialer module.
the System Alarm Signal from the indicated Fire Alarm circuits. The total delay Installation limits under jurisdiction of local authority.
J2 VOLTAGE TRIGGERS
(Control Unit plus Smoke Detectors) shall not exceed 60 seconds. No other See instructions for trigger use and programming
(default functions shown)
Attach 5140DLM module to main PCB shield using 1. OUT 4 (SILENT PANIC/DURESS)
Smoke Detector shall be connected to these circuits unless approved by the 4 standoffs (supplied) 2. OUT 7 (TROUBLE)
local authority having jurisdiction. The 5140DLM Dialer 3. OUT 3 (BURGLARY/AUDIBLE PANIC)
BACK-UP LINE SEIZE Complies with FCC Rules, Part 68 4. OUT 6 (SUPERVISORY)
LED (GREEN) FCC Reg. No.: AC398U-68628-MO-N 5. OUT 2 (FIRE)
Circuit (zone) Smoke Detector Ringer Equivalence: 0.7B
Control Unit Delay, Seconds 6. OUT 5 (REMOTE KEYPAD SOUNDER)
Model Delay, Seconds BACK-UP PHONE JACK 7. OUT 1 (OPEN/CLOSE)
SEE TELCO 8. GROUND
Zone 1 8 Seconds 9. IN 1 (N.O. LOOP)
JACK SHOCK
Zone 2 8 Seconds WARNING RJ31X RATINGS: OUT 1, 5, 7:
BELOW LOW: 2K TO GROUND
Aux Relay 8 Seconds Connect to main PCB HIGH: 10 - 14VDC, 20mA MAX
Polling Loop 8 Seconds (connect using supplied cable) OTHER OUTS: LOW: 1K TO GROUND
header J3 using ribbon Supervision is programmable
cable (supplied) HIGH: 10 - 14VDC THRU 5K
THE DELAY TIME MARKED ON THE INSTALLED DETECTOR(S) IS TO BE USED.
BACK-UP DIALER ON HOOK
BACK-UP DIALER EARTH VOLTAGE 1 2 3 4 5 6 7 8 9
This equipment should be installed in accordance with the National Fire Protection Association's Standard 72 VOLTAGE THRESHOLD (BLUE)
TRIGGERS J2
GROUND SCREW
(National Fire Protection Assoc., Batterymarch Park, Quincy, MA. 02169). Printed information describing INTACT: 25V (wire to main PCB (not supervised)
proper installation, operation, testing, maintenance and repair service is to be provided with this equipment. CUT: 13V terminal #30) Make connections
using 4142TR cable
OPTIONAL 5140DLM BACK-UP DIALER MODULE
NOTE: As shipped, Vista-32FB is suitable for UL Commercial Fire Installations. Cabinet supports up to 14AH NOTE: J2 Voltage triggers are for burglary use only.
Batteries. Use Vista-ULKT Cabinet Kit to house up to 34.4AH Batteries. Also use this kit along with MAIN PCB SHIELD Do not use for fire or combo fire/burg applications.
1451 Transformer for UL Listed Commercial Burglary Installations. NOTE: Trigger Wiring must be run in conduit within
20ft of the Control Panel.
Special Application Circuit
BATTERY TABS Connect Only Fire Keypads to J4 KEYPAD PORT #2 CONNECTION OF THE FIRE ALARM MAIN DIALER ON HOOK
BLK + RED BELL CIRCUIT SUPERVISION JUMPERS AUX PWR # 2. See instr. regarding port #2 use VOLTAGE THRESHOLD
INTACT: Supervised using 2k EOLR SIGNAL TO A FIRE ALARM HEAD- WARNING
1. GROUND (to keypad black wire) QUARTERS OR A CENTRAL STATION INTACT:25V TO PREVENT
CUT: Not supervised (no EOLR used) 4. DATA IN 2 (to keypad green wire) CUT: 13V
BELL 1 BELL 2 KEYPAD PORT #2 SHALL BE PERMITTED ONLY WITH RISK OF
5. AUX PWR #2 (to keypad red wire) THE APPROVAL OF THE LOCAL ELECTRICAL
1 2 3 4 5 6 7 8 9 J4 Rating: 10 - 14 VDC, W6
Connect to 12V, 7AH min/34.4AH max AUTHORITY HAVING JURISDICTION. (BLUE) SHOCK,
lead acid batteries using cables supplied. W1 W4 400mA max. See note 1 THE BURGLARY ALARM SIGNAL DISCONNECT
See instructions for required capacity. (WHITE) (WHITE) 7. DATA OUT 2 (to keypad yellow wire) SHALL NOT BE CONNECTED TO A INTERFACE TO 5140DLM TELCO JACK
Make connections using
Float charging voltage: 13.7VDC. Battery 4142TR cable (supplied) PINS 2, 3, 6, 8 & 9 NOT USED POLICE EMERGENCY NUMBER. BEFORE
normally need not be replaced for J3 SERVICING
at least 3 yrs. THIS PANEL
MAIN
TRNSFMR BELL OUTPUTS AUX. RELAY KEYPAD PORT #1 ZONE 1 ZONE 2 ZONE 3 ZONE 5 ZONE 6 ZONE 7 ZONE 8
OPTIONAL REMOVABLE
TERMINAL BLOCK KIT: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 RJ31X
ADEMCO NO. 4142BLK
— 63 —
TRANSFORMER
w/ENCLOSURE Connect
(lower left corner of cabinet) RJ31X
POWER #1
REPLACE COVER AFTER using
N.O.
POLE
N.C.
SPARE AUX
cable
supplied.
Supervision
Data in
Data out
OUTPUT: BELL 1 BELL 2 is
18VAC, 72VA Connect to POLLING
Earth Ground AUX RELAY Red Blk Grn Yel programmable
Not Power LOOP
Limited Maintain Terminal 30 (FORM C)
BL BL programmable REMOTE KEYPADS:
1/4" spacing GRN BELL BELL
2-WIRE SMOKE
DETECTOR LOOP
2-WIRE SMOKE
DETECTOR LOOP
PROGRAMMABLE
AS KEYSWITCH LOOP
PROGRAMMABLE
AS KEYSWITCH LOOP
Contact Rating:
28V, 2.8A See instructions
resistive loads for proper earth
HORN HORN SMOKE SMOKE GLASS 4209U ground
AUXILIARY POWER #1
NOTE: 1.0A MAX (STANDBY) BREAK connections.
Use wires that (650mA for ULC S559 applications) The impedance
2A Circuit have insulation
Breaker 1.7A MAX (ALARM) (See Note 1.) at which a
rated for 90% Max. Impedance: 0.6 Ohms N.C. N.C. N.C. N.C. N.C.
higher N.C. N.C. N.C. ground fault is
2k 2k Fire & Burglary Devices on the ECP Bus 5192SD annunciated is
must be isolated using an ECP Isolator. SMOKE 1000 Ohms.
BLK WH GRN ALARM POLARITY SHOWN Refer to Instructions for specific examples.
INPUT: 120VAC, N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O.
ECP Bus: Max. Line Impedance: 50 Ohms
60HZ, 1.0A max. Connect to Proper Special Application Circuit.
Connect to a Earth Ground. 4208U
dedicated circuit. See instructions.
2k (note 2) 2k 2k 2k 2k 2k 2k 2k
Each output may be selected for Style Y supervision
NOTES or no supervision (See main PCB jumpers W1, W4 ZONE 1-8 NOTES
and#93 Menu Mode.) • Ratings for zones 1,2: • All zones are Class B and provide Style B supervision TO OTHER DEVICES
1. The combined standby current drawn from aux • Zone resistance (excluding EOLR):
pwr #1, aux pwr #2 and polling loop cannot - 10 - 14VDC
- Zones 1, 2, 8: 100 ohms max Polling Loop: Class B, Style 3.
exceed 1.0A.The combined alarm current FIRE CKTS: Use only devices listed as Special - 2mA max for smoke all det. (up to 16
- Other zones: 300 ohms max Polling Loop Ratings:
drawn from aux pwr #1, aux pwr #2, polling Application NAC Devices in Installation and Setup detectors of the type specified in the
• Zone response: 350 - 500mS (all zones) • (supervised) 128mA max. See Note 1.
loop, bell 1 and bell 2 cannot exceed 2.3A. Guide.Supervise using 2k EOLR. Use polarized instructions can be used)
• Do not mix fire and burg. sensors on one loop. • 8 - 11 VDC
2. See instructions on setting addresses & for sounding devices. • UL compatibility ID: A
N.C. contacts for burg. usage only. • 20 Ohms Max. Impedence
max # of keypads and wire run length
restrictions. Keypad color subject to approval BURG CKTS: Supervision not req'd. EOLRs not req'd. • Maximum capacitance loading of the initiating circuit: 100 uf. See instructions for compatible
of local authority. May use non polarized devices. devices and for max wire run length.
Fire and Burglary devices on the
3. Use only 14-22 AWG wire. 1.7A max. polling loop must be isolated by use
4. No more than one (1) wire per terminal may See note 1, see instructions for compatible devices. of a 4297 or VSI module.
be connected. For commercial fire, bell timeout FOR INSTRUCTIONS Refer to instructions for specific examples.
must be a minimum of 6 minutes. SEE K3521V4 REV A,
DATED 7/09
ALL CIRCUITS ARE POWER LIMITED EXCEPT AND QUICK REFERENCE The Main Dialer Complies with
THE OUTPUT OF THE POWER TRANSFORMER K3521QR DATED 7/09 FCC Rules, Part 68
AND BACKUP BATTERIES FCC Reg. No.: AC398U-68192-AL-E
Ringer Equivalence: 0.7B
ALL POWER-LIMITED WIRING MUST BE ADEMCO VISTA-32FB
SEPARATED FROM NON-POWER LIMITED AND
HIGH VOLTAGE WIRING BY 1/4 INCH (6.4.MM). SUMMARY OF CONNECTIONS V32FB-SOC-V5
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2009 Honeywell International Inc.
www.honeywell.com/security
ÊK3840V5Š
K3840V5 10/09 Rev B