Updated Eeen203 Second Part
Updated Eeen203 Second Part
Electrical Power
1.1. Electric power generation, transmission and distribution
1.2. Brief treatment of types of power station
1.3. Power generation and transmission problem (flow diagram representation from generator
to consumer terminals)
1.4. Types of power generation
1.5. Distribution of Electrical power using overhead lines and underground cables.
1.6. The distribution transformer in estates.
1.7. The use of AC.in preference to DC. Single and three-phase supplies: delta and star
connections.
1.8. The meaning of impedance, voltage, power and power-factor in AC supply systems.
2. Installations
2.1. Electrical Building services: supply, control and distribution in buildings including:
intakes, diversity.
2.2. Wiring circuits for lighting using loop-in methods. Number of points on one circuit.
Wiring socket outlets
2.3. Conductors and cables including: main parts of cables, types, insulators and the choice of
cable sizes in various types of installation.
2.4. Wiring systems including conduct systems, rubber and PVC sheathed systems. ceiling
roses, lamp holders, switches etc.
2.5. Safety precautions including the need for safety.
2.6. The use of circuit breakers and fuses and the importance of Earthing.
2.7. Illumination: Principle of illumination.
2.8. Definition of terms and the inverse square law.
2.9. Glare and its effects. Types of lamp and lamp fittings.
2.10. Principle of lighting design and illumination requirement for various types of
usual tasks.
Electric power systems are real-time energy delivery systems. Real time means that power is
generated, transported, and supplied the moment you turn on the light switch. Electric power
systems are not storage systems like water systems and gas systems. Instead, generators produce
the energy as the demand calls for it.
The system starts with generation, by which electrical energy is produced in the power plant and
then transformed in the power station to high-voltage electrical energy that is more suitable for
efficient long-distance transportation. The power plants transform other sources of energy in the
process of producing electrical energy. For example, heat, mechanical, hydraulic, chemical, solar,
wind, geothermal, nuclear, and other energy sources are used in the production of electrical energy.
High-voltage (HV) power lines in the transmission section of the electric power system efficiently
transport electrical energy over long distances to the consumption locations. Finally, substations
transform this HV electrical energy into lower-voltage energy that is transmitted over distribution
power lines that are more suitable for the distribution of electrical energy to its destination, where
it is again transformed for residential, commercial, and industrial consumption.
Figure 1 shows a single line diagram of a typical power system. Power is generated at a voltage
of 16kV. This voltage is then stepped up to 330kV using a step-up transformer. This voltage is
then further stepped down at intervals until a voltage of 415V is achieved. 415V represents a three-
phase system while a single-phase system is associated with a voltage level of 220V.
b) Load catered for: Peak load, intermediary load and base loads
1.3 Power generation and transmission problem (flow diagram representation from
generator to consumer terminals)
The huge amount of power generated in a power station (hundreds of MW) is to be transported
over a long distance (hundreds of kilometers) to load centers to cater power to consumers with the
help of transmission line and transmission towers.
To give an idea, let us consider a generating station producing 120 MW power and we want to
transmit it over a long distance. Let the voltage generated (line to line) at the alternator be 16kV.
Then to transmit 120 MW of power at 16 kV, current in the transmission line can be easily
calculated by using power formula circuit for 3-phases as follows:
𝑃
𝐼= 𝑤ℎ𝑒𝑟𝑒 cos 𝜃 𝑖𝑠 𝑡ℎ𝑒 𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟
√3𝑉𝐿 cos 𝜃
120000000
𝐼= = 5412𝐴
√3×16000×0.8
Instead of choosing 16 kV transmission voltage, if transmission voltage were chosen to be 330 kV,
current value in the line would have been only 262A. So sectional area of the transmission line
(copper conductor) will now be much smaller compared to 16 kV transmission voltage. In other
words, the cost of conductor will be greatly reduced if power is transmitted at higher and higher
transmission voltage. The use of higher voltage (hence lower current in the line) reduces voltage
drop in the line resistance and reactance. Also, transmission losses are reduced. Standard
transmission voltages used are 132 kV or 330 kV in Nigeria depending upon how long the
transmission lines are.
Therefore, after the generator we must have a step-up transformer to change the generated voltage
(say 16 kV) to desired transmission voltage (say 330 kV) before transmitting it over a long distance
with the help of transmission lines supported at regular intervals by transmission towers. It should
be noted that while magnitude of current decides the cost of copper, level of voltage decides the
cost of insulators. The idea is, in a spree to reduce the cost of copper one cannot indefinitely
increase the level of transmission voltage as cost of insulators will offset the reduction copper cost.
At the load centers, voltage level should be brought down at suitable values for supplying different
types of consumers. Consumers may be big industries (such as steel plants), medium and small
industries and offices and domestic consumers. Electricity is purchased by different consumers at
different voltage level. For example, big industries may purchase power at 132 kV, medium and
big industries purchase power at 33 kV or 11 kV and domestic consumers at rather low voltage of
220V, single phase. Thus, we see that 330kV transmission voltage is to be brought down to
different voltage levels before finally delivering power to different consumers. To do this we
require obviously step-down transformers.
Flow diagram representation from generator to consumer terminals is shown in Figure 2
Coal is heated at a very high temperature in the burner to produce heat energy. This heat is passed
through to the boiler where it converts water into steam. The condenser deals with steam coming
out of the turbine. At this stage, maximum heat is extracted from steam, and the steam left which
is now in the form of water is recycled to the burner.
The turbine receives steam from the boiler and converts its energy into mechanical energy which
drives the generator. the generator gives electrical energy.
P=9.8qH
P= 9.8×01370×324
P=4350000KW=4350MW
b. The output power.
P=9.8ηgηtqh
P= 9.8×01370×324×0.9×0.85
P=3327.7MW
Exercise
The Zaire River, in Africa, discharges at a constant rate of 1300km3 per year. It has been
proposed to build a dam in the region where the river drops by 100m. Calculate:
a. The water flow (m3/s)
b. The power that could be harnessed (MW)
1.5 Distribution of Electrical power using overhead lines and underground cables.
Electrical energy is carried by conductors such as overhead lines and underground cables.
Although these conductors appear very ordinary, they possess important electrical properties that
greatly affect the transmission of electricity.
In order to provide electricity to consumers in usable form, a transmission and distribution system
must satisfy some basic requirements. Thus, the system must:
1. Provide the power that consumers need at all times.
2. Maintain a stable nominal voltage that does not vary by more than 10 percent.
3. Maintain a stable frequency that does not vary by more than 0.1Hz.
4. Meet standards of safety.
5. Respects environmental standard.
The energy is carried over lines designated extra-high voltage (EHV), high voltage (HV), medium
voltage (MV) and low voltage (LV).
The design of a power line depends upon the following criteria:
1. The amount of active power it has to transmit.
2. The distance over which the power must be carried.
3. The cost of the power line.
Underground Cable
Electric power can also be transmitted or distributed using underground cables. The advantages of
underground cables are:
1. Less liable to fault.
2. Low maintenance cost.
3. Less chances of fault.
4. Better appearance.
The disadvantages include:
1. Greater installation cost.
2. Insulation problems.
Comparison Between Overhead System and Underground System
1. Public Safety: The underground system is safer than overhead system because all its distribution
wiring is placed underground and there are little chances of any hazard.
2. Initial Cost: The underground system is more expensive due to the high cost of cable insulation
and special components.
3. Faults: The chances of faults in underground system are very rare.
4. Appearance: The general appearance of underground cabling is better.
5. Fault Location and Repairs: If a fault occurs in an underground system, it is difficult to locate
and repair.
6. Maintenance Cost: Underground system has a very low maintenance cost due to less chances
of faults and service interruption from wind and lightening.
Distribution transformers normally have ratings less than 200 kVA, although some national
standards can allow for units up to 5000 kVA to be described as distribution transformers. Since
distribution transformers are energized for 24 hours a day (even when they don't carry any load),
reducing iron losses has an important role in their design. As they usually don't operate at full load,
they are designed to have maximum efficiency at lower loads. To have a better efficiency, voltage
regulation in these transformers should be kept to a minimum.
Distribution transformers are normally located at a service drop, where wires run from a utility
pole or underground power lines to a customer's premises. They are often used for the power
supply of facilities outside settlements, such as isolated houses, farmyards or pumping stations at
voltages below 30 kV. Another application is the power supply of the overhead wire of railways
electrified with AC. In this case single phase distribution transformers are used.
The number of customers fed by a single distribution transformer varies depending on the number
of customers in an area. Several homes may be fed from a single transformer in urban areas. Rural
distribution may require one transformer per customer, depending on mains voltage. A large
commercial or industrial complex will have multiple distribution transformers. In urban areas and
neighborhoods where the primary distribution lines run underground, pad mount transformers,
transformers in locked metal enclosures mounted on a concreted pad, are used.
1.7 The use of AC in preference to DC, Single and three-phase supplies: delta and star
connections.
The reasons for preferring AC system over DC are:
1. It is easy to maintain and change the voltage of AC electricity for transmission and
distribution.
2. Plant cost for AC transmission (circuit breakers, transformers etc.) is much lower than the
equivalent DC transmission
it.
4. When a large fault occurs in a network, it is easier to interrupt in an AC system, as the sine
wave current will naturally tend to zero at some point making the current easier to interrupt.
6. AC can be stepped up and back down with transformers quite easily whereas DC cannot
7. If the DC was left at the supply voltage over a very large distance the volt drop would be
too great and the wires would have to be enormously thick (and expensive) in order to carry
circuitry and is becoming a possibility for the future, but it is still expensive and not quite
For the star connection, it is obvious that the voltages (known as phase-to-ground voltages) and
currents for each load will be spaced 120 degrees apart. The same is true for the delta connection,
but it is less obvious. The choice of delta or star connection has some ramifications for reliability,
in case there should be a short circuit. The delta configuration as a whole is ungrounded or floating,
meaning that no point on the circuit is connected to ground or to any point that has a particular,
known potential. Consequently, if any part of the circuit accidentally gets grounded, the delta
circuit can continue to operate on an emergency basis. Because of this property, the delta
configuration is used where reliability is most important, such as auxiliary equipment in power
plants, or on smaller transformers.
The star configuration, by contrast, is normally grounded at the center or neutral point. The star
connection is typically used on generators, main transformer banks, and transmission lines. It is
also possible to switch between delta and star connections, which is frequently done by
transformers that are wired in a delta configuration on one side and star on the other.
Comparison between star connection and delta connection
1. Star connection is either a three or a four-wire connection while delta connection is always a
three-wire connection.
2. There is a neutral wire in star connection while there is no neutral wire in delta connection.
3. In star connection, the line voltage and phase voltage are same while in delta connection, the
line voltage and phase voltage are same.
4. In star connection, the line current and phase current is same while in delta connection, the line
current and phase current are different.
Example
Three loads each of resistance 20 ohms are connected in star. If the effective voltage induced in
each phase is 120V, calculate:
a. The phase current
Each resistor behaves as a single-phase load connected to an effective voltage of 120V. The phase
current is given by:
𝑉𝑝ℎ = 𝐼𝑝ℎ × 𝑅
𝑉𝑝ℎ 120
𝐼𝑝ℎ = = = 6𝐴
𝑅 20
Exercise
Three identical impedances are connected in delta across a 3-phase 550V line as shown in Figure
10. If the line current is 10A, calculate the following:
a. The current in each impedance
b. The value of each impedance (ohms)
Figure 10
1.8 The meaning of impedance, voltage, power and power-factor in AC supply systems.
Impedance in AC circuit
Impedance Z is the ratio of the voltage to the current, measured in Ohms. Impedance is the
opposition to the flow of sinusoidal current.
In complex form, S=P+jQ for inductive circuit and S=P-jQ for capacitive circuit.
Power Factor
The ratio of active power to the apparent power in an AC circuit is called power factor.
𝑟𝑒𝑎𝑙 𝑝𝑜𝑤𝑒𝑟
𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟 = = 𝑐𝑜𝑠𝜃
𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡 𝑝𝑜𝑤𝑒𝑟
The power factor is also equal to the cosine of the phase angle between the applied voltage and the
circuit current.
A circuit in which the current lags the voltage i.e. inductive circuit is said to have a lagging power
factor. Similarly, a circuit in which the current leads the voltage i.e. capacitive circuit is said to
have a leading power factor.
Example
1. Given that V(t) = 120cos (377t + 45º) V and I(t) = 10cos(377t − 10º)A, Find the average power
absorbed by the circuit.
Solution
𝑃𝑎𝑣𝑒 = 𝑉𝑟𝑚𝑠 𝐼𝑟𝑚𝑠 𝑐𝑜𝑠𝜃
120 10
𝑃𝑎𝑣𝑒 = cos 55
√2 √2
Pave = 344.2W
120 1.576
𝑃𝑎𝑣𝑒 = 𝑐𝑜𝑠 − 66.8
√2 √2
Pave = 37.24W
Exercise
1. A 3-phase motor, connected to a 400V line, draws a line current of 5A. If the power
factor of the motor is 80 percent, calculate the following:
a. The total apparent power
b. The total active power
c. The total reactive power absorbed by the machine
2. A manufacturing plant draws a total of 415 kVA from a 2400V (line to line) 3-phase line.
If the plant power factor is 87.6% lagging, calculate the impedance of the plant.
2.1 Electrical Building Services: supply, control and distribution in buildings including:
intakes, diversity.
Supply to adequate electric service to both present and future probable load has to be cost effective
and safety for convenient purpose. The function of electric power distribution of an installation is
to receive at one or more points and to deliver it to individual appliances such as lamps, motors.
The distribution system to the building is to make it almost suitable for best designed and
installation of equipment in the best position. For best distribution system the Engineer must have
details concerning the loads and knowledge of the various type of systems that are applicable to
that particular building as certain categories of building have different designing requirements and
challenges, but basic principles are common in most situation.
The basic principles requiring considerations during design of power distribution and control
system includes but not limited to the following: functions of structure for present and future, life
and flexibility of the structure, location of service entrance and the distribution equipment,
locations and characteristics of the loads, location of unit substations, demand and diversity factors
of the loads, source of power including normal, standby and emergency, distribution equipment
and motor control, type of lighting systems, installation methods, power monitoring, efficiency
and management, and finally electric utility requirements.
With emergence of communication and information technology in modern electric power and
home automation, the designer of building installation must take into consideration the operations
of smart devices both in energy data and system operation information. In general designing of an
electrical system for a given facility safety and cost are the overall goals with maximum power
quality and efficiency.
Service main
An electrical circuit is the whole path along which an electric current may flow. This path may
be divided into three parts:
1- The source of electricity (e.g. generator, transformer or battery), which supplies energy to the
supply terminals of the circuit.
2- The consuming devices, which convert the electrical energy into the desired form, such as
heat or light.
3- The wires and control gear, which convey the electricity from the supply terminals on the
premises to the consuming devices.
Power supplies to towns and villages are provided from the power stations all over the country,
via a system of overhead and underground mains and transformers which reduce the voltage in
steps from the transmission voltage to the normal mains voltage at the consumers. The National
Grid Company is responsible for the transmission of power in bulk, at 400 kV, on the Super Grid
System. The local Electricity Boards are responsible for the distribution of power from the grid
stations to domestic and industrial consumers. This is done by using a network of overhead lines
and underground cables (usually at 132 kV and 33 kV) to take the power to the main load centres,
and 11 kV overhead lines and underground cables to distribute the power to individual load centres,
where secondary sub-stations reduce the voltage to mains potential. From these sub-stations
(which can consist of pole-mounted transformers and isolating gear or ground-mounted
transformers and switch-gear), low voltage overhead and underground mains are taken to the
consumer's supply terminals (Figure 11).
A.C. power is distributed mainly on three-phase networks, although in some rural areas single-
phase supplies only are available. Thus, on the low voltage side of most local transformers we
have four terminals: red, yellow and blue phases and neutral. Between each phase and the neutral
there is a voltage of 240 V (the standard voltage in Britain); between the phases the voltage is 415
V. For this reason, the secondary output voltage of transformers is given as 415/240 V. The supply
authorities are required to maintain the voltage at the consumer's supply terminals within plus or
minus 6 per cent of the nominal voltage, i.e. a 240 V single-phase supply must be kept between
224 and 256 V.
Armoured Cable: for the armoured cable which is normally for distribution network, the insulation
immediately surrounding a cable conductor is designed to withstand the cable’s working voltage
in order to prevent danger. The additional sheathing and/ or armouring is added to protect the
insulated conductors from mechanical damage. The inner sheathing works as a binder for insulated
conductors together in mult-core power cables and provides bedding to armour. Some
environments are more hazardous than others, and cables must be chosen carefully to suit those
environments; for example, a PVC-sheathed steel wire armoured cable would be used for running
underground for house services, the figure below depicting armoured cable with main part level.
Flexible cables and cords: Flexible wire varying in size from 0.5mm² (16/0.20) to 4mm² (56/0.30)
are called flexible cords. Flexible wires of larger sizes from 6mm² (84/0.30) to 630mm²
(2257/0.60) are called flexible cables. Flexible cords and cables are so made of fine gauge of wire
as to be much more flexible than ordinary wiring cables and are used for such purpose as from
ceiling rose to lamp holder, butyl rubber for supply to water heaters or from socket outlets to
portable apparatus.
• Cable design Procedure: The following are basic cable designs procedure:
1. Assessment of general characteristics
2. Determination of design current Ib
3. Selection of protective device having nominal rating or setting In
4. Selection of relevant rating factors
5. Divide In by the relevant rating factors (CFs) to give tabulated cable current carrying capacity
It. In cases where overloads are not likely In = Ib
6. Selection of suitable conductor size to suit It
7. Check voltage drop
8. Evaluation of shock risk
9. Evaluation of thermal risks to conductors.
Tests and inspections: Before any completed installations, or addition / alteration to an existing
installation may be connected to the supply, all such installation work must be inspected and tested
in order to comply with part 6 of the IEE wiring regulations. Prior to such test, full knowledge of
the installation must be established through charts, tables, etc. in order to know which tests are
required. It is then necessary to determine that:
o All electrical equipment installed complies with the applicable standard.
o Each item of equipment, every appliance and all the installation have been correctly
selected (designer’s responsibility) and erected / installed in order to comply IEE
Regulations.
o All installed equipment and parts of the installation are not visibly damaged.
Laws of illumination
1. Luminous Flux Emitted by Point Source
This can be found by considering the result of enclosing the source of luminous intensity I cd in
a sphere one 1m radius as shown in Figure 15
A = 4m
E = I lux
1m
Since each part of the surface of the sphere is 1m from the source, it receives an illuminance = I
lux. Now total surface area of sphere = 4π m2
F= E x A
= I x 4π = 4πI lumen.
Therefore, for a uniform point source, the total luminous flux emitted is 4πI lumens.
2. Inverse Square Law
If a point source of light having a luminous intensity of I cd is placed at the center of a sphere of
radius d meters as shown Figure 16.
If this surface were removed, the same luminous flux would then fall on surface B.
Since the parallel rays of light falling on the inclined surface B are spread over a larger surface
area, the illuminance will be reduced by a factor θ, and therefore, of the cosine rules this
equation is known as the cosine law known Lambert’s cosine rule.
𝐼 cos 𝜃
𝐸=
𝑑2
Example 1.
A lamp of luminous intensity 1000 cd is suspended 2 m above a laboratory bench. Calculate
the illuminance directly below the lamp:
solution
using inverse square law
I= 1000 cd
d= 2m
𝐼 1000𝑐𝑑
𝐸= 2
= = 250𝑙𝑢𝑥
𝑑 (4𝑚2 )
Example 2
A street lantern suspends a 2000 cd light source 4 m above the ground. Determine the
illuminance directly below the lamp and 3 m to one side of the lamp base.
Solution
Now
𝐼 cos 𝜃
𝐸= 𝑙𝑢𝑥
𝑑2
4
cos 𝜃 =
5
2000 4
𝐸= × 𝑙𝑢𝑥 = 64𝑙𝑢𝑥
(5𝑚)2 5
𝐹(𝑙𝑚)
𝐸= 𝑖𝑛 𝑙𝑢𝑥
𝐴(𝑚2 )
b. Lumen method
Coefficient of utilization (CU): In practice, not all the light emitted by the light sources will fall
on to the working plane. The coefficient of utilization of a lighting system is defined as:
Therefore, allowing for the coefficient of utilization, the average illuminance E, over the working
plane is given by:
F (total flux in lm) x coefficient of utilization)
A (area of working plane in cm²)
The coefficient of utilization depends on the colour and the nature of the surface of walls and
ceilings, and type of lights fittings used. Even the shape of the room and arrangement of light
sources affects its value.
Maintenance factor (Light loss factor): The lumen method of calculation can be used to calculate
the total lamp power required to illuminate a green area. However, as the output of a light source
gradually falls, due to aging of the lamps and dirt collection on the lamps and fittings, it is usual
to allow for a maintenance factor or depreciation factor when estimating the number of lamps
required.
Average light output obtained in practice
𝑀𝑎𝑖𝑛𝑡𝑒𝑛𝑎𝑛𝑐𝑒 𝑓𝑎𝑐𝑡𝑜𝑟 (𝑀𝐹) =
Light output of new lamp
1
Depreciation factor =
Maintenance factor
E×A
Total lumens required =
(Coefficient of utilization x maintenance factor)
Values between 0.7 to 0.8 are typical for CU and MF, Knowing the total lumens and the lumen
of one lamp (selected), the number of lamps can be calculated
Efficacy: The efficiency of a light source is often quoted in Lumens per watts. Thus:
0.85m
The working plane is often taken to be 0.85m above finished floor level. The spacing – height
ratio is taken as 1.5 if dispersive and diffusing type of fittings are used. It is taken as 1.25 for
concentrating or louvre types of fittings are used. The space between the center of a lamp and a
wall of a room is usually taken to be half the spacing between the lamps, but if a lot of work is
done near the wall, it is taken as one third of the spacing of the lamps.
Example 3
It is desired to illuminate a drawing hall with an average of 200 lux. The hall is 30m x 20m x
4m. The lamps are to be fitted from ground floor. Find the number of lamps and the wattage per
lamp for the lighting scheme. Given efficiency of the lamps as 25 lumens per watt, depreciation
factor 0.8 and coefficient of utilization 0.75, space-to height ration between 0.8 and 1.2. Draw a
suitable drawing of the arrangement.
Solution
The lamps near the walls are kept at half the calculated spacing to keep uniformity of light
If for example, this distance is kept equal, then the light between adjacent lamps will be more as
compared to the illumination at the walls, as shown in the Figure 18.
30m
2 m
4m
4m
4m
4m
2m
This scheme does not satisfy the requirements, then the process will start all over again
LAMP TECHNOLOGIES
Artificial luminous radiation can be produced from electrical energy according to two principles:
incandescence and electroluminescence.
Incandescence is the production of light via temperature elevation. The most common example is
a filament heated to white state by the circulation of an electrical current. The energy supplied is
transformed into heat by the Joule effect and into luminous flux.
• Discharge Lamps
When an electric current is passed through certain gases visible light is produced. The gas is
normally contained in a large tube fitted with an ‘electrode’ at each end. A fairly high voltage is
required to maintain the discharge although the current is small. For most discharge lamps; the
‘striking voltage’ required is higher than the ‘running’ voltage and so some means of limiting the
running current is required. An inductor is sometimes used this for purpose or a special
transformer which provides a high striking voltage at first, and then progressively lower voltage
as the tube current increases. The colour of the light emitted depends upon the type of gas used. If
the tube of a discharge lamp containing mercury vapour is coated internally with an even layer of
fluorescent material, a considerable proportion of the ultra – violet caused by the discharge lamp
is converted into visible light. In some type of lamps, the electrodes are not heated, and are
therefore known as “cold cathode” lamps. In other types, the electrodes are heated, as this reduces
the voltage required to strike and maintain the discharge. Lamps using heated electrodes are known
as ‘hot cathodes’ lamps, a typical example being the ordinary florescent lamp.
• Fluorescent Lamps
This lamp uses a phenomenon of fluorescence to emit visible light. It is known as that certain
materials emit visible light whenever they absorb ultra-violet light, and they may be used to
produce a very efficient lamp. When the supply is switched on with the starter switch (s) closed, a
current flow through inductor (L) also known as choke and through the lamp electrodes. This initial
current heats the lamp in readiness for striking the lamp. The starting switch is opened making a
sudden interruption in the current flowing through the inductor and so causing a high voltage to
be momentarily induced. This voltage starts a discharge between the two electrodes and the current
rapidly rises to a value determined mainly by the inductance of the inductor. The starter switch is
left open while the lamp is alight, the electrodes maintaining the operating temperature as long as
they continue to pass the discharge current. In practice, the starter switch is an automatic type,
switching on when the supply is first switch on, then switching off to strike the lamp and remaining
off all the time that the lamp is alight. There are 2 types in general use, the glow type and the
thermal type.
• Sodium Lamp
This type of lamp is also used for street lighting and similar purposes. To start this lamp, an auto
transformer is used to provide high voltage between the lamp electrodes; the transformer being
designed to have a high leakage reactance so that separate reactance is not required. The ‘U’ tube
contains a mixture of neon gas and sodium vapor and, when the lamp is cold, some of the sodium
vapor condenses to form globules of metallic sodium on the glass of the ‘U’ tube. When the lamp
is first switched on the high voltage applied causes a discharge through the neon gas. As the lamp
warms up the globules of metallic sodium vaporize, causing the pressure of the vapor to rise, and
the discharge transfers to the sodium vapor in preference to the neon gas, the light output increasing
as it warms up, until the full vapor pressure is attained. Mounting is very important to avoid
condensed sodium vapor falling on to the electrodes.