Tender Specifications_DBC (1)
Tender Specifications_DBC (1)
Page 1 of 26
provided that the design meets the following criteria.
A) The room is 1 h fire resistance rated, including a 1 h fire door and fire resistance
rated opening protective.
B) The room is no more than one level below ground level.
C) The room is provided with a dedicated mechanical ventilation system direct to
outside to achieve 10 air changes/h, in accordance with Section 2.17, Ch. 10 of
UAE FLSC. [Ref. B.1].
Page 2 of 26
1. it shall not impede access points to and from a building
2. it shall not be located less than 2.5 m horizontally and 5m vertically from any
operable windows of a living space such as a bedroom or living room.
3. It shall be located where interference with pedestrian traffic and other vehicle
access is minimal.
4. It shall be roofed and have a concrete pad designed to handle a load of the bins.
Note: Separate onsite storage areas are generally only permitted when the GA of the
largest storey of the building is less than 250m2, regardless of the height of the
building.
Page 4 of 26
B.10.6 Sustainable materials
B.10.6.1 Recycled materials
Based on cost, recycled content (as defined in ISO 14021) shall constitute at least
10% of the total value of the materials in the project. This shall be calculated as
follows:
Value of recycled content= (value of post-consumer recycles content) + half (value
of pre-consumer recycled content)
If only a fraction of a product or materials is recycled, then only that percentage (by
weight) can contribute to the recycled content value.
Mechanical, electrical and plumbing components, as well as furniture and specialty
items such an elevator, shall not be included in this calculation. Only materials
permanently installed in the building shall be included.
Also, the contractor shall arrange recycled content information for steel or any other
materials from the supplier/manufacturer as per below format:
To,
Ref. No:
Client`s Name
Dear Sir,
Subject: Recycled content in……….
Project Name:
Plot No:
We hereby certify that the above Steel product has the recycle content of ________% of postindustrial
and _________% of post-consumer recycle content.
Thanking you,
Company Representative Seal & Signature
Page 5 of 26
Recycled Steel Manufacturer Total weight of Weight of structural steel Recycled
/Supplier Structural Steel, kg with a minimum of 25% , Content
post-consumer recycled
content, kg
Steel Framed
Ref. No:
Client`s Name
Dear Sir,
Project Name:
Plot No:
Page 6 of 26
The material is manufactured at our factory in .............. which is .........km away from the
project site. The raw materials used in making the product are all extracted/ harvested/
recovered at ............place which is............... km away from project site.
Thanking you,
Page 7 of 26
building is equal to or lower than the annual energy consumption of the reference
building.
Page 8 of 26
E.5.2.3 Building envelope performance
E.5.2.3.1 Non-glazed elements
As per the project design, below are average U-value (thermal transmittance)
building envelope elements considered in cooling calculations for all conditioned
space of the project:
U-Value
Materials U-Value Requirements Complying?
Design
With the exception of non-conditioned enclosed parking areas, the average thermal
transmittance for external walls, roofs and exposed floors (the underside of the floor is
exposed to ambient conditions) shall not exceed the values in Table E.4 and figure E.3.
While the U-value for external walls can be achieved using aerated concrete blocks, the
use of insulation for the entire building envelope is recommended. Insulation material
Page 9 of 26
shall conform to Section 4 to 7, Ch. Of the UAE FLSC [Ref. E1]
For the floor area that is in contact with the ground, the thermal transmittance
requirement shall be achieved by installing 1 m of perimeter insulation as shown on
figure E.3.
For shopfronts and showrooms, other than those at ground floor level, glazed elements
shall meet the performance criteria in Table E.6.
Page 10 of 26
For Skylight, the performance criteria in Table E.7 shall be met depending on the area of
glazing over the total roof area.
Thermal transmittance values are overall U-values for the glazed elements. Overall U-
values shall be calculated as the area-weighted averages of the centre of pane U-value
(Glazing and panel) and frame U-value, including all edge effects (spacer and frame) and
thermal bridges. Glazed elements having back-insulated panels shall also meet the
thermal transmittance requirement, including framing, edges effects and thermal
bridges.
Page 11 of 26
E.5.8 Exterior light power, pollution and controls
As per the project, all External lights shall be shielded or aimed Downward
Wall washing lights shall spill no more than 10% lighting past the building façade.
Downward directed lighting shall be used for lighting of signage and;
All exterior lighting shall be control through automatic timer control.
The average lighting power density for the exterior connected lighting load for building
envelopes shall not exceed 2.2 W/m2 for each illuminated wall or surface area or 16.4
W/linear meter for each illuminated wall or surface length.
Permanently installed exterior lighting shall meet the following requirements.
a) All exterior light fixtures on the building site, other than architectural accent lighting
(see E.5.8b) and Civil Aviation safety lighting, shall be shielded, such that the full
Page 12 of 26
light emitted by the fixture, either directly or in directly by reflection or by
refraction from any part of the fixture, is projected below the horizontal plane
passing through the lowest part of the fixture (see figure E.7)
b) Architectural accent lighting shall be aimed or shielded to prevent the lighting of the
night sky. Wall washing lights shall spill no more than 10% of the lighting past the
building facade.
c) Downward directed lighting shall be used for lighting of signage.
d) All exterior lighting shall be fitted with automatic controls, so that the light can be
set not to operate during daylight hours.
For occupant comfort, normal occupied spaces shall have an average air velocity
between 0.2 m/s and 0.3 m/s
Page 13 of 26
a)Table 1: Split and packaged unit including cassette type unit;
b)Table 2: Water source heat pumps;
c)Table 4: multiple split unit.
Chillers shall meet the minimum efficiency requirements and test procedures given in
Table 6.8.1 to Table 6.8.3 of ASHRAE 90.1-2019.
The chiller equipment requirements shall be met for all chillers, including those where
the leaving fluid design temperature is <45 °C.
Page 14 of 26
exceeded Indoor air quality testing shall be carried out prior to occupancy. A test
report showing compliance with these requirements shall be submitted to the
Authority.
Contractor to demonstrate that a minimum of 95% (by weight) of all adhesives and
sealants used on the building interior must not exceed the prescribed VOC limits in
South Coast Air Quality Management District Rule 1168.
Page 15 of 26
Table A.1: Maximum Volatile Organic Compounds (VOC’s) Content Limit Values for Paints and
Coatings (from DMS 020)
Page 16 of 26
Table: 404.02(1) – Maximum VOC Limits of adhesives and Sealants
Other 750
All Paints & coatings used on the interior of the building (inside of the water
proofing system & applied on site) must not exceed the VOC content limits
established in Green Seal Standard GS-11, Paints, 1st edition. Anti-corrosive and
anti-rust paints applied to interior ferrous metal substances must not exceed VOC
Page 17 of 26
content limit of 250 g/l established in green seal standard GC-03, Anti Corrosive
Paints, 2nd edition.
Clear wood finishes, floor coatings, stains, primers and shellacs applied to interior
elements must not exceed the VOC content limits established in South Coast Air
Quality Management District (SCAQMD) Rule 1113, Architectural coatings.
Contractor to provide material data sheets/ cut sheets specifying the VOC content
of the materials.
H.4.12.1 General
The ventilation system design and selection shall be determined by the mechanical
design Engineer for the given application, taking into account all relevant issues
associated with the building design, usage, configuration and commissioning,
operation and maintenance of the system.
Mechanical ventilation shall be provided by a method of supply air and return or
exhaust air (see Figure H.3). The amount of supply air shall be approximately equal
to the amount of return and exhaust air. The system shall not be prohibited from
producing negative or positive pressure. Air handling units shall deliver filtered and
conditioned air within the building. Air handling units shall be American Heating
and Refrigeration Institute or Euro vent certified
Mechanical ventilation installations shall meet the requirements given in Ch. 16 of
the ASHRAE Fundamentals handbook [Ref. H.18]
As per the DBC Requirements, there are two compliance routes for water use:
a) Elemental method: All Buildings shall conform to H.5.2.2
b) Performance method: A calculation method may be employed for a building which
Page 19 of 26
might not meet the elemental requirements for water-efficient fixtures detailed in
H.5.2.2.
The performance method shall use supporting calculations to compare the annual
water consumption of the proposed building with that of a reference building which
meets the elemental requirements of H.5.2.2. The reference building shall be equal in
shape, size and operational patterns to the proposed building.
Compliance will be demonstrated if the calculated annual water consumption of the
proposed building is equal to or lower than the annual water consumption of the
reference building.
As per the DBC Requirements, the following water-efficient fittings shall be used:
a) Fixtures with a flow rate less than or equal to the flow rates shown in Table H.5;
b) Dual flush toilets;
c) Automatic (proximity detection) or push-button faucets in all public facilities;
d) Cisterns serving single or multiple urinals in public, commercial and industrial
buildings with manual or automatic flush controls that operate based on usage
patterns. Only sanitary flushing shall be possible in the event of building closure or
shutdown (including overnight). Faucets installed for specialized application may be
exempted from meeting the flow rates, subject to authority approval.
Page 21 of 26
H.7.2 Lighting power densities – interior
The lighting power density (LPD) design of the project is as per ASHRAE 90.1-2019
based on building area method.
The average lighting power density for the interior connected lighting load for the
project Warehouse/Office interior areas – does not exceed the maximum average
LPD recommended in Table H.15 of DBC
The lighting power density shall be calculated using either the building area method or
the “space-by-space” method as set out in Sections 9.5 and 9.6 of ASHRAE 90.1-2019
When using the building area method, the maximum average lighting power density for
the interior connected lighting load shall not exceed the values given in Table H.15
Lighting power density values for occupancies not listed in Table H.15 shall not exceeds
the values given in ASHRAE 90.1 or equivalent as approved by the Authority.
Average exterior lighting power density values for areas not listed in Table H.16 shall
Page 22 of 26
not exceed the values indicated in ASHRAE 90.1 or equivalent as approved by the
authority.
If the average exterior lighting power density values exceed the values specified in
Table H.16, the additional lighting load should be powered entirely through renewable
energy sources (such as photovoltaic systems or similar). Any lighting power reduction
generated by the renewable energy source shall be deducted from the annual energy
consumption in the performance-based method.
COMMISSIONING
H.8 Commissioning
Commissioning of air distribution systems, water distribution systems, lighting,
central control and building management systems, refrigeration systems and boilers
shall be carried out in accordance with the CIBSE commissioning codes [Ref. H.38,
Ref. H.39, Ref. H.40, Ref. H.41, Ref. H.42, Ref. H.43] or other commissioning code/
standard approved by the Authority.
A systems manual shall be developed, and shall be provided to the
Warehouse/Office operator upon completion of commissioning works. The systems
manual shall document the information required to allow future operations staff to
understand and optimally operate the commissioned services.
A non-technical user guide shall be developed for building occupiers.
Commissioning Requirements
Commissioning of the Warehouse/Office systems will be carried out in a systematic manner
to provide documented confirmation that Warehouse/Office systems perform according to
the criteria set forth in the design intent and satisfy the owner’s operational needs.
Documentation of the design intent has been followed into the detail design development.
The same will be continued through construction, acceptance and the warranty period with
actual verification of performance. The commissioning process shall encompass and
coordinate the traditionally separate functions of system documentation, equipment
startup, control system calibration, testing and balancing, performance testing and training.
Commissioning plan, as developed by the CxA during the design phase for the project will
be passed on to the Contractor to be followed into the construction phase. The Contractor
is to be fully aware of and adhere to the requirements in the Commissioning plan.
The commissioning plan is to be maintained as the master reference for all commissioning
related activities. The specifications below are to be treated as key points from the same.
Commissioning during the Construction Phase is intended to achieve the following specific
objectives according to the Contract Documents:
o Verify that applicable equipment and systems are installed according to the
manufacturer’s recommendations and to industry accepted minimum standards
and that they receive adequate operational checkout by installing contractors.
Page 24 of 26
o Verify and document proper performance of equipment and systems.
o Verify that O&M documentation left on site is complete.
o Verify that the Owner’s operating personnel are adequately trained.
The Commissioning Process does not take away from or reduce the responsibility of the
system designers or installing contractors to provide a finished and fully functioning
product.
Team members and their specific roles are listed below :
Page 25 of 26
CxA to draft the final commissioning report for
Commissioning Report the project reflecting the overall commissioning
process
CxA to have fortnightly site visits during the on-site commissioning activities for the
installation, pre functional and functional testing of the equipment. Further sit visit
frequency schedule and sampling of testing witness shall be coordinated between the CxA,
Main consultant and the contractor. CxA to issue the Site Inspection Report for after the
site visits and the contractor to ensure adherence to comments in the SIR by the following
visit.
Systems included under the commissioning scope are as follows :
Water Pump Booster Pump, Transfer pump, Hot water Circulation Pump
Water Heating Solar Hot Water Heater
Page 26 of 26