R45C 222571

The R45C Discrete to Serial Converter is a compact device that integrates discrete I/O devices into a PICK-IQ network, featuring a rugged design that meets IP65, IP67, and IP68 standards. It utilizes a Modbus RTU compatible serial bus protocol to enhance communication efficiency and reduce latency in pick-to-light systems. The device supports configurable input/output points and includes detailed specifications for wiring, indicators, and environmental ratings.

Uploaded by

hibo1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views4 pages

R45C 222571

The R45C Discrete to Serial Converter is a compact device that integrates discrete I/O devices into a PICK-IQ network, featuring a rugged design that meets IP65, IP67, and IP68 standards. It utilizes a Modbus RTU compatible serial bus protocol to enhance communication efficiency and reduce latency in pick-to-light systems. The device supports configurable input/output points and includes detailed specifications for wiring, indicators, and environmental ratings.

Uploaded by

hibo1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

R45C Discrete to Serial Converter

Datasheet

• Compact configurable discrete I/O to PICK-IQ converter


• Rugged over-molded design meets IP65, IP67, and IP68
• Connects directly to a sensor or anywhere in-line for ease of use

Overview
The R45C-B22-SQ is an easy-to-use converter that allows addition of a discrete I/O device to a PICK-IQ network. This converter can be placed
anywhere in the PICK-IQ network. Both I/O points on the discrete connection can be configured as inputs or outputs.

Communications
These devices are powered by PICK-IQ®, a purpose-built, Modbus RTU compatible serial bus protocol that uses a Common ID to reduce the typical
latency that results from polling multiple devices.
The standard Modbus protocol structure does not offer the performance required to operate medium to large sized pick-to-light systems with low
latency response times. Adding more devices to a pick-to-light system running standard Modbus protocol eventually makes a pick-to-light system
unusable because of the request/response nature of the protocol. The communication latency to and from the master device is too slow.
Using PICK-IQ adds a simple change to the devices that allow the Modbus master controller to run standard Modbus protocol, but achieve the
performance required by a medium to large sized pick-to-light system. This change is the addition of a common ID addressing scheme.

PICK-IQ Configuration
For more information on the PICK-IQ network functionality, see Banner P/N 206185 PICK-IQ Devices Instruction Manual.
Table 1: Holding Registers

Modbus Register Address Description Holding Register Registration Comments

I/O Register Block


3000 Input 1 Status 0 = Inactive Returns the status of an input on Channel 1
1 = Active

3001 Input 2 Status 0 = Inactive Returns the status of an input on Channel 2


1 = Active

3002 Output 1 Enable 0 = Disabled Activates the output on Channel 1 1


1 = Enabled

3003 Output 2 Enable 0 = Disabled Activates the output on Channel 2 1


1 = Enabled

Input Settings Register Block


3430 Input 1 Enable 0 = Disabled Monitors Channel 1 or input signals
1 = Enabled

3431 Input 1 Polarity 0 = NPN Defines the input signal type on Channel 1
1 = PNP

3432 Input 2 Enable 0 = Disabled Monitors Channel 2 or input signals


1 = Enabled

3433 Input 2 Polarity 0 = NPN Defines the input signal type on Channel 2
1 = PNP

Output Settings Register Block


3440 Output 1 Push/Pull Enable 0 = Disabled Enables a push/pull circuit, stabilizing Output 1 2
1 = Enabled

3441 Output 1 Polarity 0 = NPN Defines the output signal type on Channel 1
1 = PNP

3442 Output 2 Push/Pull Enable 0 = Disabled Enables a push/pull circuit, stabilizing Output 2 2
1 = Enabled

3443 Output 2 Polarity 0 = NPN Defines the output signal type on Channel 2
1 = PNP

Note: Alternative Modbus interface is not available for this device.

1 When enabling an output, it is important to disable the input on the corresponding channel. This prevents the output from triggering the common ID.
2 Push/pull should only be enabled when using the output on the corresponding channel. Otherwise, if used while an input is enabled and in use, it is possible to lock the value of
the input signal.

Original Document 20 August 2021


222571 Rev. A

222571
R45C Discrete to Serial Converter

Table 2: Holding Registers When Common ID is Active

Modbus Register Address Description Holding Register Registration Comments

7940 Modbus Device ID of Active Device — —


7941 Device Output Latch Register 0 = None triggered Values in this register latch until acknowledged and
1 = Primary triggered cleared by the master
2 = Secondary triggered
3 = Both triggered

7942 Device Output Status 0 = None triggered Values in this register reflect the real time status of the
1 = Primary triggered device's outputs
2 = Secondary triggered
3 = Both triggered

Wiring Diagrams
Male Female Pin Wire Color

1 Brown

1 2
2 White
3 Blue
2 1 4 Black
4 3
3 5 4 5 Gray

Female (Serial In) Male (Serial Out) Signal Description Female (Discrete Input) Signal Description

Pin 1 12 V DC to 30 V DC Pin 1 12 V DC to 30 V DC
Pin 2 RS-485 (+) Pin 2 IO Channel 2
Pin 3 DC common Pin 3 Ground
Pin 4 RS-485 (–) Pin 4 IO Channel 1
Pin 5 Shield Pin 5 Shield

Status Indicators
Power LED Indicator (Green)
• Solid Green = Power On
• Off = Power Off
PICK-IQ Communication LED Indicator (Amber)
• Flashing Amber = PICK-IQ communications are active
• Off = PICK-IQ communications are not present

Specifications
Supply Voltage Operating Conditions
12 V DC to 30 V DC at 50 mA maximum Temperature: –40 °C to +50 °C (–40 °F to +122 °F)
Supply Protection Circuitry 90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA

2 www.bannerengineering.com - Tel: + 1 888 373 6767 P/N 222571 Rev. A


R45C Discrete to Serial Converter

Output Protection Circuitry Required Overcurrent Protection


Protected against output short-circuit
Indicators WARNING: Electrical connections must be made by
Green power qualified personnel in accordance with local and
Amber PICK-IQ communications national electrical codes and regulations.
Connections Overcurrent protection is required to be provided by end product application per the
Integral male/female 5-pin M12 quick disconnect supplied table.
Construction Overcurrent protection may be provided with external fusing or via Current Limiting,
Coupling Material: Nickel-plated brass Class 2 Power Supply.
Connector Body: PVC translucent black Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 Supply Wiring (AWG) Required Overcurrent Protection (Amps)
minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave) 20 5.0
Environmental Rating 22 3.0
IP65, IP67, IP68
NEMA/UL Type 1 24 2.0
Certifications 26 1.0
28 0.8
30 0.5

Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.

Accessories
Cordsets
5-Pin Threaded M12 Cordsets—Double Ended

Model Length Style Dimensions Pinout (Male) Pinout (Female)

40 Typ. 1 2
2 1
MQDEC-501SS 0.31 m (1.02 ft)
4 3
M12 x 1 3 5 4 5
Male Straight/ ø 14.5
MQDEC-503SS 0.91 m (2.99 ft) Female Straight
44 Typ.
MQDEC-506SS 1.83 m (6 ft)
1 = Brown 4 = Black
2 = White
5 = Gray
MQDEC-512SS 3.66 m (12 ft) 3 = Blue
M12 x 1
ø 14.5

P/N 222571 Rev. A www.bannerengineering.com - Tel: + 1 888 373 6767 3


R45C Discrete to Serial Converter

Banner Engineering Corp. Limited Warranty


Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge,
any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the
improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER
PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR
FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner
Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such
purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this
document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is
provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.

FCC Part 15 and CAN ICES-3 (B)/NMB-3(B)


This device complies with part 15 of the FCC Rules and CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules and CAN ICES-3 (B)/NMB-3(B). These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the manufacturer.

© Banner Engineering Corp. All rights reserved