Mekanisa - Gofa Line at Mekanisa End

The document is a settings file report for the MEKANESA substation, detailing the configuration of the MiCOM model P442311B3M0090C. It includes system data, control settings, date and time, configuration, CT and VT ratios, record control, disturbance recorder, measurement setup, and commission tests. The report was printed on May 7, 2023, and outlines various operational parameters and statuses of the substation equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views7 pages

Mekanisa - Gofa Line at Mekanisa End

The document is a settings file report for the MEKANESA substation, detailing the configuration of the MiCOM model P442311B3M0090C. It includes system data, control settings, date and time, configuration, CT and VT ratios, record control, disturbance recorder, measurement setup, and commission tests. The report was printed on May 7, 2023, and outlines various operational parameters and statuses of the substation equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Page: 1

Settings File Report


Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:27

SYSTEM DATA
00.01: Language: English
00.02: Password: ****
00.04: Description: MiCOM
00.05: Plant Reference: ALSTOM
00.06: Model Number: P442311B3M0090C
00.08: Serial Number: 526427W
00.09: Frequency: 50 Hz
00.0A: Comms Level: 2
00.0B: Relay Address: 1
00.0C: Plant Status: 0000000000000010
00.0D: Control Status: 0000000000000000
00.0E: Active Group: 1
00.10: CB Trip/Close: No Operation
00.11: Software Ref. 1: B1.4
00.20: Opto I/P Status: 0000100000001110
00.21: Relay Status 1: 000000000000000000000
00.22: Alarm Status 1: 00000000000000000000000000000000
00.40: Relay Status 1: 000000000000000000000
00.50: Alarm Status 1: 00000000000000000000000000000000
00.51: Alarm Status 2: 00000000000000000000000000000000
00.52: Alarm Status 3: 00000000000000000000000000000000
00.D0: Access Level: 2
00.D1: Password Control: 2
00.D2: Password Level 1: ****
00.D3: Password Level 2: ****
CB CONTROL
07.01: CB Control by: Local+Remote
07.02: Close Pulse Time: 500.0 ms
07.03: Trip Pulse Time: 500.0 ms
07.04: Man Close Delay: 10.00 s
07.05: Healthy Windows: 5.000 s
07.06: C/S Window: 5.000 s
07.07: A/R Single Pole: Disabled
07.08: A/R Three Pole: Disabled
DATE AND TIME
08.01: Date/Time: 2022-08-29 12:19:37.351
08.06: Battery Status: Healthy
08.07: Battery Alarm: Enabled
CONFIGURATION
09.01: Restore Defaults: No Operation
09.02: Setting Group: Select via Menu
09.03: Active Settings: Group 1
09.04: Save Changes: No Operation
09.05: Copy From: Group 1
09.06: Copy To: No Operation
09.07: Setting Group 1: Enabled
09.08: Setting Group 2: Disabled
09.09: Setting Group 3: Disabled
09.0A: Setting Group 4: Disabled
09.0D: Dist. Protection: Enabled
09.10: Power-Swing: Enabled
09.11: Back-up I>: Disabled

Easergy Studio
Page: 2
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:27

09.12: Neg Sequence O/C: Disabled


09.13: Broken Conductor: Disabled
09.14: Earth Fault PROT: Disabled
09.15: Aided D.E.F: Disabled
09.16: Volt Protection: Disabled
09.17: CB Fail & I<: Enabled
09.18: Supervision: Enabled
09.19: System Checks: Enabled
09.24: Internal A/R: Enabled
09.25: Input Labels: Visible
09.26: Output Labels: Visible
09.28: CT & VT Ratios: Visible
09.29: Record Control: Visible
09.2A: Disturb Recorder: Visible
09.2B: Measure't Setup: Visible
09.2C: Comms Settings: Visible
09.2D: Commission Tests: Visible
09.2E: Setting Values: Secondary
CT AND VT RATIOS
0A.01: Main VT Primary: 132.0 kV
0A.02: Main VT Sec'y: 100.0 V
0A.03: C/S VT Primary: 132.0 kV
0A.04: C/S VT Secondary: 100.0 V
0A.07: Phase CT Primary: 300.0 A
0A.08: Phase CT Sec'y: 1.000 A
0A.0D: MComp CT Primary: 1.000 A
0A.0E: MComp CT Sec'y: 1.000 A
0A.0F: C/S Input:A-N
0A.10: Main VT Location: Line
RECORD CONTROL
0B.04: Alarm Event: Enabled
0B.05: Relay O/P Event: Enabled
0B.06: Opto Input Event: Enabled
0B.07: General Event: Enabled
0B.08: Fault Rec Event: Enabled
0B.09: Maint Rec Event: Enabled
0B.0A: Protection Event: Enabled
0B.0B: DDB 31 - 0: 11111111111111111111111111111111
0B.0C: DDB 63 - 32: 11111111111111111111111111111111
0B.0D: DDB 95 - 64: 11111111111111111111111111111111
0B.0E: DDB 127 - 96: 11111111111111111111111111111111
0B.0F: DDB 159 - 128: 11111111111111111111111111111111
0B.10: DDB 191 - 160: 11111111111111111111111111111111
0B.11: DDB 223 - 192: 11111111111111111111111111111111
0B.12: DDB 255 - 224: 11111111111111111111111111111111
0B.13: DDB 287 - 256: 11111111111111111111111111111111
0B.14: DDB 319 - 288: 11111111111111111111111111111111
0B.15: DDB 351 - 320: 11111111111111111111111111111111
0B.16: DDB 383 - 352: 11111111111111111111111111111111
0B.17: DDB 415 - 384: 11111111111111111111111111111111
0B.18: DDB 447 - 416: 11111111111111111111111111111111
0B.19: DDB 479 - 448: 11111111111111111111111111111111
0B.1A: DDB 511 - 480: 11111111111111111111111111111111

Easergy Studio
Page: 3
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:28

0B.1B: DDB 543 - 512: 11111111111111111111111111111111


0B.1C: DDB 575 - 544: 11111111111111111111111111111111
0B.1D: DDB 607 - 576: 11111111111111111111111111111111
0B.1E: DDB 639 - 608: 11111111111111111111111111111111
0B.1F: DDB 671 - 640: 11111111111111111111111111111111
0B.20: DDB 703 - 672: 11111111111111111111111111111111
0B.21: DDB 735 - 704: 11111111111111111111111111111111
0B.22: DDB 767 - 736: 11111111111111111111111111111111
0B.23: DDB 799 - 768: 11111111111111111111111111111111
0B.24: DDB 831 - 800: 11111111111111111111111111111111
0B.25: DDB 863 - 832: 11111111111111111111111111111111
0B.26: DDB 895 - 864: 11111111111111111111111111111111
0B.27: DDB 927 - 896: 11111111111111111111111111111111
0B.28: DDB 959 - 928: 11111111111111111111111111111111
0B.29: DDB 991 - 960: 11111111111111111111111111111111
0B.2A: DDB 1022 - 992: 1111111111111111111111111111111
DISTURB RECORDER
0C.01: Duration: 1.500 s
0C.02: TriggerPosition: 33.30 %
0C.03: TriggerMode: Single
0C.04: AnalogChannel1: VA
0C.05: AnalogChannel2: VB
0C.06: AnalogChannel3: VC
0C.07: AnalogChannel4: VN
0C.08: AnalogChannel5: IA
0C.09: AnalogChannel6: IB
0C.0A: AnalogChannel7: IC
0C.0B: AnalogChannel8: IN
0C.0C: DigitalInput1: Relay Label 01
0C.0D: Input1Trigger: No trigger
0C.0E: DigitalInput2: Relay Label 02
0C.0F: Input2Trigger: No trigger
0C.10: DigitalInput3: Relay Label 03
0C.11: Input3Trigger: No trigger
0C.12: DigitalInput4: Relay Label 04
0C.13: Input4Trigger: No trigger
0C.14: DigitalInput5: Relay Label 05
0C.15: Input5Trigger: No trigger
0C.16: DigitalInput6: Relay Label 06
0C.17: Input6Trigger: No trigger
0C.18: DigitalInput7: Relay Label 07
0C.19: Input7Trigger: No trigger
0C.1A: DigitalInput8: Relay Label 08
0C.1B: Input8Trigger: No trigger
0C.1C: DigitalInput9: Relay Label 09
0C.1D: Input9Trigger: No trigger
0C.1E: DigitalInput10: Relay Label 10
0C.1F: Input10Trigger: No trigger
0C.20: DigitalInput11: Relay Label 11
0C.21: Input11Trigger: No trigger
0C.22: DigitalInput12: Relay Label 12
0C.23: Input12Trigger: No trigger
0C.24: DigitalInput13: Relay Label 13

Easergy Studio
Page: 4
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:28

0C.25: Input13Trigger: No trigger


0C.26: DigitalInput14: Relay Label 14
0C.27: Input14Trigger: No trigger
0C.28: DigitalInput15: Unused
0C.2A: DigitalInput16: Unused
0C.2C: DigitalInput17: Unused
0C.2E: DigitalInput18: Unused
0C.30: DigitalInput19: Unused
0C.32: DigitalInput20: Unused
0C.34: DigitalInput21: Unused
0C.36: DigitalInput22: Unused
0C.38: DigitalInput23: Unused
0C.3A: DigitalInput24: Unused
0C.3C: DigitalInput25: Unused
0C.3E: DigitalInput26: Unused
0C.40: DigitalInput27: Unused
0C.42: DigitalInput28: Unused
0C.44: DigitalInput29: Unused
0C.46: DigitalInput30: Unused
0C.48: DigitalInput31: Unused
0C.4A: DigitalInput32: Unused
MEASURE'T SETUP
0D.01: Default Display: P - Q
0D.02: Local Values: Primary
0D.03: Remote Values: Primary
0D.04: Measurement Ref: VA
0D.05: Measurement Mode: 0
0D.06: Demand Interval: 30.00 min
0D.07: Distance Unit: Kilometres
0D.08: Fault Location: Distance
COMMISSION TESTS
0F.01: Opto I/P Status: 0000100000001110
0F.02: Relay Status 1: 000000000000000000000
0F.04: Test Port Status: 00000000
0F.05: LED Status: 00100000
0F.06: Monitor Bit 1: Relay Label 01
0F.07: Monitor Bit 2: Relay Label 02
0F.08: Monitor Bit 3: Relay Label 03
0F.09: Monitor Bit 4: Relay Label 04
0F.0A: Monitor Bit 5: Relay Label 05
0F.0B: Monitor Bit 6: Relay Label 06
0F.0C: Monitor Bit 7: Relay Label 07
0F.0D: Monitor Bit 8: Relay Label 08
0F.0E: Test Mode: Disable
0F.0F: Test Pattern 1: 000000000000000000000
0F.11: Contact Test: No operation
0F.12: Test LEDs: No operation
0F.13: Autoreclose Test: No Operation
CB MONITOR SETUP
10.01: Broken I^: 2.000
10.02: I^ Maintenance: Alarms Disabled
10.04: I^ Lockout: Alarms Disabled
10.06: No CB Ops Maint: Alarms Disabled

Easergy Studio
Page: 5
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:28

10.08: No CB Ops Lock: Alarms Disabled


10.0A: CB Time Maint: Alarms Disabled
10.0C: CB Time Lockout: Alarms Disabled
10.0E: Fault Freq Lock: Alarms Disabled
10.11: Lockout Reset: No
10.12: Reset Lockout By: CB Close
10.13: Man Close RstDly: 5.000 s
OPTO CONFIG
11.01: Global Nominal V: 110/125V
Group 1
GROUP 1 DISTANCE ELEMENT
30.01: GROUP 1 Line Setting:
30.02: Line Length: 1700 m
30.04: Line Impedance: 790.0mOhm ( 311.2mOhm)
30.05: Line Angle: 66.80 deg (j 726.1mOhm)
30.06: GROUP 1 Zone Setting:
30.07: Zone Status: 01010
30.08: kZ1 Res Comp: 670.0e-3
30.09: kZ1 Angle: 11.70 deg
30.0A: Z1: 140.0 mOhm
30.0C: R1G: 1.780 Ohm
30.0D: R1Ph: 1.340 Ohm
30.0E: tZ1: 0s
30.0F: kZ2 Res Comp: 670.0e-3
30.10: kZ2 Angle: 11.70 deg
30.11: Z2: 230.0 mOhm
30.12: R2G: 2.220 Ohm
30.13: R2Ph: 1.670 Ohm
30.14: tZ2: 300.0 ms
30.15: kZ3/4 Res Comp: 670.0e-3
30.16: kZ3/4 Angle: 11.70 deg
30.17: Z3: 19.63 Ohm
30.18: R3G-R4G: 2.780 Ohm
30.19: R3Ph-R4Ph: 2.090 Ohm
30.1A: tZ3: 1.000 s
30.24: Serial Cmp. Line: Disabled
30.25: Overlap Z Mode: Disabled
30.26: GROUP 1 Fault Locator:
30.27: kZm Mutual Comp: 0
30.28: kZm Angle: 0 deg
GROUP 1 DISTANCE SCHEMES
31.01: Program Mode: Standard Scheme
31.02: Standard Mode: Basic + Z1X
31.03: Fault Type: Both enabled
31.04: Trip Mode: Force 3 poles
31.08: tReversal Guard: 20.00 ms
31.09: Unblocking Logic: None
31.0A: SOTF/TOR Mode: 00000000110000
31.0B: SOTF Delay: 110.0 s
31.0C: Z1Ext Fail: Disabled
31.12: GROUP 1 Loss Of Load:
31.13: LoL:Mode Status: Disabled
GROUP 1 POWER-SWING

Easergy Studio
Page: 6
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:28

32.01: Delta R: 500.0 mOhm


32.02: Delta X: 500.0 mOhm
32.03: IN> status: Enabled
32.04: IN> (%Imax): 40.00 %
32.05: I2> status: Enabled
32.06: I2> (%Imax): 30.00 %
32.07: ImaxLine> Status: Enabled
32.08: ImaxLine >: 3.000 A
32.09: Unblocking delay: 5.000 s
32.0A: Blocking Zones: 11111
GROUP 1 CB FAIL & I<
45.01: GROUP 1 BREAKER FAIL:
45.02: CB Fail 1 Status: Enabled
45.03: CB Fail 1 Timer: 200.0 ms
45.04: CB Fail 2 Status: Disabled
45.06: CBF Non I Rst: I< Only
45.07: CBF Ext Reset: I< Only
45.08: GROUP 1 UNDERCURRENT I<:
45.09: I< Current set: 200.0 mA
GROUP 1 SUPERVISION
46.01: GROUP 1 VT SUPERVISION:
46.02: VTS Time Delay: 5.000 s
46.03: VTS I2 & I0 Inh: 50.00 mA
46.04: Detect 3P: Enabled
46.05: Threshold 3P: 20.00 V
46.06: Delta I>: 100.0 mA
46.07: GROUP 1 CT SUPERVISION:
46.08: CTS Status: Disabled
46.0C: GROUP 1 CVT SUPERVISION:
46.0D: CVTS Status: Disabled
GROUP 1 SYSTEM CHECKS
48.01: Chk scheme A/R: 111
48.02: Chk scheme ManCB: 111
48.03: V< Dead Line: 13.00 V
48.04: V> Live Line: 32.00 V
48.05: V< Dead Bus: 13.00 V
48.06: V> Live Bus: 32.00 V
48.07: Diff Voltage: 6.500 V
48.08: Diff Frequency: 50.00 mHz
48.09: Diff Phase: 20.00 deg
48.0A: Bus-Line Delay: 200.0 ms
GROUP 1 AUTORECLOSE
49.01: GROUP 1 AUTORECLOSE MODE:
49.09: Reclaim Time: 25.00 s
49.0A: Close Pulse Time: 500.0 ms
49.0C: A/R Inhibit Wind: 5.000 s
49.0E: GROUP 1 AUTORCLE LOCKOUT:
49.0F: Block A/R:01111111111111
GROUP 1 INPUT LABELS
4A.01: Opto Input 1: Opto Label 01
4A.02: Opto Input 2: Opto Label 02
4A.03: Opto Input 3: Opto Label 03
4A.04: Opto Input 4: Opto Label 04

Easergy Studio
Page: 7
Settings File Report
Substation: MEKANESA
File: 000.set
Model Number: P442311B3M0090C Printed on: 05/07/2023 15:37:28

4A.05: Opto Input 5: Opto Label 05


4A.06: Opto Input 6: Opto Label 06
4A.07: Opto Input 7: Opto Label 07
4A.08: Opto Input 8: Opto Label 08
4A.09: Opto Input 9: Opto Label 09
4A.0A: Opto Input 10: Opto Label 10
4A.0B: Opto Input 11: Opto Label 11
4A.0C: Opto Input 12: Opto Label 12
4A.0D: Opto Input 13: Opto Label 13
4A.0E: Opto Input 14: Opto Label 14
4A.0F: Opto Input 15: Opto Label 15
4A.10: Opto Input 16: Opto Label 16
GROUP 1 OUTPUT LABELS
4B.01: Relay 1: Relay Label 01
4B.02: Relay 2: Relay Label 02
4B.03: Relay 3: Relay Label 03
4B.04: Relay 4: Relay Label 04
4B.05: Relay 5: Relay Label 05
4B.06: Relay 6: Relay Label 06
4B.07: Relay 7: Relay Label 07
4B.08: Relay 8: Relay Label 08
4B.09: Relay 9: Relay Label 09
4B.0A: Relay 10: Relay Label 10
4B.0B: Relay 11: Relay Label 11
4B.0C: Relay 12: Relay Label 12
4B.0D: Relay 13: Relay Label 13
4B.0E: Relay 14: Relay Label 14
4B.0F: Relay 15: Relay Label 15
4B.10: Relay 16: Relay Label 16
4B.11: Relay 17: Relay Label 17
4B.12: Relay 18: Relay Label 18
4B.13: Relay 19: Relay Label 19
4B.14: Relay 20: Relay Label 20
4B.15: Relay 21: Relay Label 21
Group 2
Group 3
Group 4

Easergy Studio