TECO Westinghouse RTD Alarm Trip Settings

TECO recommends specific temperature settings for R.T.D trip and alarm for windings, A.F. bearings, and sleeve bearings, with allowable running temperatures of 155˚C, 80-90˚C, and 75-80˚C respectively. Alarm and trip temperatures vary by component, with windings set at 140-170˚C, A.F. bearings at 90-120˚C, and sleeve bearings at 80-90˚C. The document notes that these are recommended values and actual conditions may necessitate adjustments.

Uploaded by

Sean Kim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
242 views1 page

TECO Westinghouse RTD Alarm Trip Settings

TECO recommends specific temperature settings for R.T.D trip and alarm for windings, A.F. bearings, and sleeve bearings, with allowable running temperatures of 155˚C, 80-90˚C, and 75-80˚C respectively. Alarm and trip temperatures vary by component, with windings set at 140-170˚C, A.F. bearings at 90-120˚C, and sleeve bearings at 80-90˚C. The document notes that these are recommended values and actual conditions may necessitate adjustments.

Uploaded by

Sean Kim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

TECO'S RECOMMENDED R.T.

D TRIP
AND ALARM TEMPERATURE SETTINGS

WINDINGS (1) A.F. BEARINGS (2) SLEEVE BEARINGS (3)

ALLOWABLE RUNNING
155˚C(1) 80-90˚C 75-80˚C
TEMPERATURE

ALARM TEMPERATURE 140-160˚C 90-110˚C 80-85˚C


TRIP TEMPERATURE 160-170˚C 95-120˚C 85-90˚C

Notes:
(1). Based on Class F insulation.
(2). Grease lubricated ball or roller bearings. Grease temperature will be 5-10˚C
below actual bearing temperature.

(3). Oil lubricated bearing. Oil temperatures will be 15-20˚C below actual bearing temperature.
* The above information are recommended values only. Specific application conditions
may change the auggested temperature settings.

(4). Alarm and shutdown levels for motor bearing housing vibration shall not exceed the limits
as stated in NEMA MG1-2006 part 7, page 7 - 7.8 limits of bearing housing vibration.