DN Series™ 430V Full-Function Weatherized Walk-Up Ul, Cen I and Cen Iii Exgas Safes

The DN Series™ 430V is a full-function weatherized walk-up safe designed for automated banking machines, compliant with UL and CEN standards. It requires specific installation practices to meet ADA and CSA standards for accessibility, and has detailed power and weight specifications. The safe includes a basic alarm system and must be secured with recommended anchor bolts to ensure physical security.

Uploaded by

atmrmg03
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views7 pages

DN Series™ 430V Full-Function Weatherized Walk-Up Ul, Cen I and Cen Iii Exgas Safes

The DN Series™ 430V is a full-function weatherized walk-up safe designed for automated banking machines, compliant with UL and CEN standards. It requires specific installation practices to meet ADA and CSA standards for accessibility, and has detailed power and weight specifications. The safe includes a basic alarm system and must be secured with recommended anchor bolts to ensure physical security.

Uploaded by

atmrmg03
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP

UL, CEN I and CEN III EXGAS SAFES


L1377 CALL 1-800-999-3600

REFER TO INSTALLATION MANUAL # 01750370311.


CONSULT WITH DIEBOLD NIXDORF INSTALLATION/SERVICE
FOR ADDITIONAL DETAILS AND INFORMATION.

800
DIMENSIONS IN MILLIMETRES

1
(DIMENSIONS IN INCHES)

(31 2")

POWER DATA PIT FOR


127 187 25mm (1") DIAMETER HOLE DRILLED
UL AND CEN I SAFES
(5") (738") THROUGH THE TOP OF THE DN430
FOR TOPPER OR SURROUND CABLE
POWER DATA PIT FOR
204 ENTRY. FOR INSTALLATION OF 3rd
CEN III EXGAS SAFE
1
(8 16") PARTY TOPPERS OR SURROUNDS,
95
REFER TO THE APPENDIX OF
3
(3 4") INSTALLATION MANUAL # 01750370311
152
(INSTALLING A SYSTEM TOPPER).
(6")

(6")
152

16")
281
1
(11
FOR DN SERIES™ AUTOMATED BANKING MACHINE (ABM)
INSTALLATIONS IN THE US MARKET (OR OTHER AREAS WHERE ADA
STANDARDS ARE RECOGNIZED), INSTALLATION PRACTICES SHOULD

(3 8")
16")

80
BE GUIDED BY THE REQUIREMENTS LISTED IN THE 2010 ADA
1024

1
(43 8")

USA
1108

STANDARDS FOR ACCESSIBLE DESIGN INCLUDING SECTION 707


5
(40
5

WHICH DEFINES THE REQUIREMENTS FOR THE ACCESSIBILITY AND


USABILITY OF AUTOMATIC TELLER MACHINES (ATM) BY PERSONS
WITH DISABILITIES OR THE LATEST VERSIONS / REVISIONS OF THESE
STANDARDS AVAILABLE AT THE TIME OF INSTALLATION.
THIRD ANGLE
PROJECTION

FOR DN SERIES™ AUTOMATED BANKING MACHINE (ABM)


INSTALLATIONS IN THE CANADIAN MARKET (OR OTHER AREAS WHERE
CSA STANDARDS ARE RECOGNIZED), INSTALLATION PRACTICES
SHOULD BE GUIDED BY THE REQUIREMENTS LISTED IN CSA/ASC

CANADA B651:23 ACCESSIBLE DESIGN FOR THE BUILT ENVIRONMENT AS WELL


AS CSA/ASC B651.2:22 ACCESSIBLE DESIGN FOR SELF-SERVICE
INTERACTIVE DEVICES INCLUDING AUTOMATED BANKING MACHINES,
PLAN OR THE LATEST VERSIONS/REVISIONS OF THESE STANDARDS
PUBLISHED AT THE TIME OF INSTALLATION.
PAGE 1 OF 7

1108
5
(43 8")

800
1 1024
(31 2")
5
(40 16")
SUBJECT TO CHANGE WITHOUT NOTICE"
"ALL DIMENSIONS AND DESIGN CRITERIA

16")

16")
1599

1599
15

15
(62

(62
16")

16")
665

665
3

3
(26

(26
FILE NO. 177-797 REV. 1

FRONT ELEVATION
SIDE
19" DISPLAY SHOWN
CONSUMER ACCESS DIMENSIONS
DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP
L1377 UL, CEN I and CEN III EXGAS SAFES

HEIGHT
* 746mm
DEPTH
67mm
A KEYPAD (CENTER KEY 5 PIP)
(2938") (258")

773mm 139mm
B1 CASH IN / OUT
(30716") (512")

} ACTIVEDGE CARD READER


1008mm 138mm
DIMENSIONS IN MILLIMETRES

11 7
(39 16") (5 16")
(DIMENSIONS IN INCHES)

997mm 124mm
C MOTORIZED CARD READER
(3914") (478")

998mm 203mm
DIP CARD READER
(39516") (8")

99mm
D RECEIPT PRINTER 762mm
(378")
(30")

} (STD) LOW SOFTKEY


947mm
(3714")
158mm
(614")

148mm
E1 (DDC) LOW SOFTKEY 915mm
(51316")
(36")

904mm 144mm
(NDC) LOW SOFTKEY
(35916") (51116")

} (STD) TOP SOFTKEY


1045mm
(4118")

1012mm
190mm
(712")

179mm
E2 (DDC) TOP SOFTKEY
(391316") (7
1
16")

1025mm 184mm
(NDC) TOP SOFTKEY
(4038") (714")
THIRD ANGLE
PROJECTION

} TOP OF SCREEN 15"


1110mm
(43
11
16")
212mm
3
(8 8")
E3
1182mm 236mm
TOP OF SCREEN 19"
(46916") (9
5
16")

} CENTER OF SCREEN 15"


1000mm
(3938")
177mm
(7")
E4
1038mm 189mm
CENTER OF SCREEN 19"
(4078") (7716")

741mm 61mm
F CONTACTLESS CARD READER
(29316") (238")

710mm 2mm
G HEADPHONE JACK
(271516") 1
(16")

696mm 9mm
H BAR CODE READER
(2738") 3
( 8")

*
HEIGHT DIMENSIONS ARE FROM
PAGE 2 OF 7

735mm 43mm
I FINGERPRINT READER BOTTOM OF SAFE. IN CASES WHERE
(281516") (11116")
THE OPTIONAL INSTALLATION PLINTH
1116mm 242mm IS USED (SEE PAGE 7), HEIGHT
J CHECK DEPOSIT
(912") DIMENSIONS FROM FLOOR WILL NEED
(431516")
TO BE INCREASED 51mm (2").
139mm
O DRIVER'S LICENSE READER 889mm
1
(5 2")
(35")

HEIGHT - FROM BOTTOM OF SAFE


DEPTH - FROM FRONT EDGE OF BEZEL
SUBJECT TO CHANGE WITHOUT NOTICE"
"ALL DIMENSIONS AND DESIGN CRITERIA

J E3 J
E3
C E2 C
E4
O E4 O
B1
D E1 D
A
I B1 I
H
F A F

G H G
FILE NO. 177-797 REV. 1

FRONT ELEVATION FRONT ELEVATION


19" DISPLAY 15" DISPLAY
CANOPY REQUIREMENT POWER REQUIREMENTS
IT IS RECOMMENDED THE UNIT BE PLACED UNDER COVER/CANOPY FOR SUN THE ATM REQUIRES SINGLE-PHASE THREE WIRE UNSWITCHED POWER. WIRING TO
PROTECTION, WATER INGRESS AND OPERATOR/SERVICE. THE ATM MUST USE A THIRD-WIRE EARTH GROUND (CONDUIT GROUND IS NOT
L1377 NOTE: IN ORDER TO ENSURE THE PROTECTION FROM WATER INGRESS THE ACCEPTABLE). THE POWER SUPPLIED MUST BE AS SPECIFIED BELOW.

FASCIA OF THE TERMINAL MUST BE PROPERLY SEALED AND LATCHED CHOOSE AND SUPPLY THE PROPER POWER FOR THE SITE:
CORRECTLY. TO VERIFY IT IS HAS BEEN LATCHED CORRECTLY, THE USER 100-127 VAC (+6%, -10%) AT 50 (±1%) Hz, SINGLE-PHASE
CAN PULL ON THE FASCIA TO ENSURE NEITHER SIDE PULLS OUT. 100-127 VAC (+6%, -10%) AT 60 (±1%) Hz, SINGLE-PHASE
200-240 VAC (±10%) AT 50 (±1%) Hz, SINGLE-PHASE
WEIGHT OF UNIT 200-240 VAC (±10%) AT 60 (±1%) Hz, SINGLE-PHASE

UL / CEN I ---------------- 955kg (2,106 LBS.) POWER TO THE ATM IS TO BE A DEDICATED SERVICE AND MUST BE PROTECTED
BY A SAFETY QUICK-DISCONNECT DEVICE TO BREAK LINE VOLTAGE (SUCH AS A
CEN III EXGAS -------- 1136kg (2,506 LBS.)
CIRCUIT BREAKER AT THE ELECTRICAL SERVICE PANEL). THE QUICK DISCONNECT
ALARM PROTECTION DEVICE (OR CIRCUIT BREAKER) MUST TURN OFF THE LINE VOLTAGE AT THE AMPERAGE
SPECIFIED BELOW.
THE SAFE IS EQUIPPED WITH A BASIC ALARM SENSOR PACKAGE. THE BASIC
100-127 VAC SERVICE, DISCONNECT AT 30 AMPERES
DIMENSIONS IN MILLIMETRES

PACKAGE INCLUDES A SAFE DOOR OPEN SWITCH, ALARM SHUNTING SWITCH,


200-240 VAC SERVICE, DISCONNECT AT 15 AMPERES
(DIMENSIONS IN INCHES)

AND RATE-OF-RISE HEAT SENSOR.

MINIMUM CONCRETE SLAB SIZE POWER USAGE


851mm (2'-912") WIDE X 1075mm (3'-2516") DEEP X 203mm (8") MIN. THICKNESS 110-120 V 220-240 V

WITHOUT UPS IDLE MODE OPERATION IDLE MODE OPERATION


PHYSICAL SECURITY
(MAXIMUM) (MAXIMUM)
UL SAFE
THE SAFE MEETS THE REQUIREMENTS OF UL STANDARD 291 LEVEL 1 FOR RATED CURRENT
1.2A 2.4A 0.6A 1.4A
AUTOMATED TELLER SYSTEMS FOR 24 HOUR SERVICE. THE SAFE DOOR IS CONSUMPTION*:
PROVIDED WITH UL LISTED RELOCKING DEVICES AND A UL LISTED
GROUP 1 ELECTRICAL LOCK WITH SINGLE OR DUAL COMBINATION LOCK. 370 WATTS 330 WATTS
ACTIVE POWER: 160 WATTS 130 WATTS
(WITHOUT HEATER) (WITHOUT HEATER)

TO MEET REQUIREMENTS OF UL 291. DIEBOLD NIXDORF RECOMMENDS 1070 WATTS 1030 WATTS
(4) M20 ANCHOR BOLTS THAT ARE 170mm (6 1116”) LONG FOR PROPERLY
(WITH HEATER) (WITH HEATER)

SECURING THE UNIT (PART #01750308241). THE OVERALL DRILLING DEPTH 1770 WATTS 1730 WATTS
(WITH 2 HEATERS) (WITH 2 HEATERS)
DEPENDS ON STRUCTURAL CONDITIONS. THE MOUNTING ANCHORS
MUST BE LOCATED AT LEAST 125mm (4 1516”) DEEP IN THE LOAD BEARING 1060 WATTS 1000 WATTS
(WITH AIR CONDITIONER) (WITH AIR CONDITIONER)
CONCRETE (SEE DETAIL). ANCHOR BOLTS MUST BE USED IN ALL (4) AVAILABLE
ANCHOR HOLES. IF MOUNTING KIT IS NOT PROVIDED, USE EQUIVALENT
WITH UPS
FASTENING MATERIAL. INSTALL ANCHORS IN ACCORDANCE WITH INSTALLATION
TEMPLATE PART NUMBER #01750338732 (ALSO PROVIDED).
RATED CURRENT
2.3A 3.5A 1.2A 2.0A
CONSUMPTION*:
CEN SAFES
THE SAFE MEETS THE REQUIREMENTS FOR EN 1143-1 CEN RESISTANCE
ACTIVE POWER: 300 WATTS 500 WATTS 240 WATTS 460 WATTS
GRADE FOR ATM SAFES.

FUSE: 30 A AUTOMATIC CIRCUIT 16 A AUTOMATIC CIRCUIT


TO MEET REQUIREMENTS OF CEN. DIEBOLD NIXDORF RECOMMENDS
THIRD ANGLE
PROJECTION

BREAKER BREAKER
(4) M20 ANCHOR BOLTS THAT ARE 170mm (6 1116”) LONG FOR PROPERLY
SECURING THE UNIT (PART #01750308241). THE OVERALL DRILLING DEPTH
DEPENDS ON STRUCTURAL CONDITIONS. THE MOUNTING ANCHORS EFFECTIVE POWER AND HEAT OUTPUT
MUST BE LOCATED AT LEAST 125mm (4 1516”) DEEP IN THE LOAD BEARING
CONCRETE (SEE DETAIL). ANCHOR BOLTS MUST BE USED IN ALL (4) AVAILABLE EFFECTIVE POWER (W) HEAT OUTPUT (W)
ANCHOR HOLES. IF MOUNTING KIT IS NOT PROVIDED, USE EQUIVALENT
FASTENING MATERIAL. INSTALL ANCHORS IN ACCORDANCE WITH INSTALLATION IDLE SPEED OPERATION 190
TEMPLATE PART NUMBER 01750338732 (ALSO PROVIDED).

DIEBOLD NIXDORF M20 ANCHOR BOLTS (OR EQUIVALENT) MEET/EXCEED 168 250
THE FOLLOWING RESISTANCE GRADE REQUIREMENTS WHEN PROPERLY
INSTALLED:
CEN I and CEN III EXGAS SAFE: 50 kN (PULLOUT FORCE) CLIMATIC ENVIRONMENTAL CONDITIONS
AIR TEMPERATURE RELATIVE AIR HUMIDITY %

OPERATION (OUTSIDE) -40°C to 50°C


(-40°F to 122°F)
5 to 85%
(INSIDE) 0°C to 40°C
(32°F to 104°F)
PAGE 3 OF 7

TRANSPORT -25°C to 60°C (-13°F to 140°F) 5 to 98%

STORAGE -10°C to 60°C (14°F to 140°F) 5 to 95%

800 1108
1 5
(31 2") (43 8")

353 294 152 1024


15 9 5
(13 16") (11 16") (6") (40 16")

ALTERNATE LOCATION FOR


19mm 3
(4") DIAMETER CONDUIT
SUBJECT TO CHANGE WITHOUT NOTICE"

POWER, COMMUNICATION
"ALL DIMENSIONS AND DESIGN CRITERIA

HOLE FOR ALTERNATE AND DATA (CONDUIT AS


ELECTRICAL POWER SUPPLY
(19 8")

REQUIRED BY OWNER'S G.C.)


499

LOCATION (HARD WIRED)


5

19mm 3
(4") DIAMETER CONDUIT
HOLE FOR ALTERNATE ALARM,
COMMUNICATION AND DATA
LOCATION
(35 8")

19mm 3
(4") DIAMETER CONDUIT
898
3

HOLE FOR AIR CONDITIONER


DRAIN TUBE ROUTING AIR CONDITIONER DRAIN
TUBE ROUTING

AIR CONDITIONER DRAIN


FILE NO. 177-797 REV. 1

TUBE ROUTING

1024
5
(40 16")

1104
7
(43 16")

REAR VIEW SIDE VIEW


SCHEMATIC
L1377
DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP
DIMENSIONS IN MILLIMETRES
(DIMENSIONS IN INCHES)

8
THIRD ANGLE
PROJECTION

13

12

1
3
9
2
5 1
4
10
PAGE 4 OF 7

11
5
SECTION
SUBJECT TO CHANGE WITHOUT NOTICE"
"ALL DIMENSIONS AND DESIGN CRITERIA

1. COMMUNICATIONS CABLE - DIEBOLD NIXDORF TO FURNISH (OPTIONAL AND EXTRA) RJ-45 CABLE TO BE INSTALLED BY THE OWNER.

2. VIDEO SURVEILLANCE SYSTEM CABLE-FURNISHED AND INSTALLED BY OWNER.

3. ALARM CABLE-TO CONFORM TO GRADE A REQUIREMENTS, ALARM CABLE MUST BE HOME RUN FROM THE ATM BACK TO THE ALARM CONTROL
CABINET, FURNISHED AND INSTALLED BY OWNER.

4. 102mm (4") DIAMETER PVC PIPE-FURNISHED AND INSTALLED BY OWNER.

5. ELECTRICAL POWER CONDUIT-FURNISHED AND INSTALLED BY OWNER.

6. ALARM.

7. VIDEO SURVEILLANCE SYSTEM.

8. OPTIONAL REMOTE STATUS INDICATOR (RSI).

9. TO NETWORK

10. ELECTRICAL CONDUIT TO BUILDINGS ELECTRICAL PANEL.

11. FLOOR OPENING FOR CABLES (RECOMMENDED TO BE IN THE ELECTRICAL EQUIPMENT ROOM).
FILE NO. 177-797 REV. 1

12. RSI CABLING - FURNISHED BY DIEBOLD NIXDORF AND INSTALLED BY OWNER.

13. 25mm (1") DIAMETER HOLE DRILLED THROUGH THE TOP OF THE DN430 FOR TOPPER OR SURROUND
CABLE ENTRY. FOR INSTALLATION OF 3rd PARTY TOPPERS OR SURROUNDS, REFER TO THE APPENDIX
OF INSTALLATION MANUAL # 01750370311 (INSTALLING A SYSTEM TOPPER).
THIRD ANGLE DIMENSIONS IN MILLIMETRES
"ALL DIMENSIONS AND DESIGN CRITERIA PROJECTION (DIMENSIONS IN INCHES)
FILE NO. 177-797 REV. 1 SUBJECT TO CHANGE WITHOUT NOTICE" PAGE 5 OF 7 L1377

5
600

(1
(23 8")

15
50

1
16")

1072

(42 4")
3
1
800

2000

(78 4")
(31 2")

SIDE
PLAN

3
949

(37 8")
(1
15

949 153
50
MINIMUM SERVICE AREA

3
(6")
16")

(37 8")
5
600

(23 8")
UL, CEN I and CEN III EXGAS SAFES

153

(6")
1072 1102
1599 152 3 3
(42 16") (43 8")
15
(62 16") (6")
DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP

MINIMUM SERVICE AREA


SAFE ANCHOR LOCATIONS AND DETAILS
DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP
L1377
UL, CEN I and CEN III EXGAS SAFES

NOTES:
NEW CONSTRUCTION:
1. OWNER'S E.C. TO FURNISH AND INSTALL (1) 19mm (34") RIGID CONDUIT
FOR ELECTRICAL POWER. (SEE POWER REQUIREMENTS)

2. OWNER'S E.C. TO FURNISH AND INSTALL 102 mm (4") P.V.C. PIPE


DIMENSIONS IN MILLIMETRES

(RECOMMENDED METHOD FOR ROUTING COMMUNICATION CABLE, EXPRESS


(DIMENSIONS IN INCHES)

BUS CABLE, ALARM CABLE, AND VIDEO CABLE).


800 SAFE
1 (ALTERNATE METHOD) OWNER'S ELECTRICAL CONTRACTOR TO FURNISH
(31 2")
AND INSTALL (1) 25mm (1") RIGID CONDUIT FOR ALARM CABLE AND (1) 38mm
203 169 (112") RIGID CONDUIT FOR COMMUNICATION CABLE, EXTERNAL OPTIONS
5 CABLE, AND VIDEO CABLE.
(8") (6 8")
92 125
5 15 3. PLEASE CONTACT THE DIEBOLD NIXDORF INSTALLING BRANCH IF
(3 8") 583 (4 16")
CONSIDERING ATTACHMENT OF A REMOTE DESKTOP MONITOR/KEYBOARD
SLAB OPENING (22
15
16") TO THIS PRODUCT.

4. DIEBOLD NIXDORF RECOMMENDS (4) M20 ANCHOR BOLTS 170mm (61116")


16")

LONG FOR PROPERLY SECURING THE UNIT (PART #01750308241). THE

(9")
229
274

OVERALL DRILLING DEPTH DEPENDS ON STRUCTURAL CONDITIONS. THE


13

15
(10

MOUNTING ANCHORS MUST BE LOCATED AT LEAST 125mm (4 16") DEEP IN


THE LOAD BEARING CONCRETE (SEE DETAIL). ANCHOR BOLTS MUST BE

(8")
USED IN ALL (4) AVAILABLE ANCHOR HOLES. IF MOUNTING KIT IS NOT

203
PROVIDED, USE EQUIVALENT FASTENING MATERIAL. INSTALL ANCHORS IN
1024 SAFE

ACCORDANCE WITH INSTALLATION TEMPLATE PART NUMBER #01750338732


A
16")

(ALSO PROVIDED).
(23 8")
5
(40

600

5. CONCRETE SLAB TO BE FLAT AND LEVEL IN AREA OF UNIT.


5

6. CONCRETE SLAB CONSTRUCTION MUST SUPPORT WEIGHT OF THE DN


430 UNIT 955kg (2,106 LBS.) FOR UL or CEN I or 1136kg. (2,506 LBS.) FOR CEN III
EXGAS SAFE.
THIRD ANGLE
PROJECTION

7. OWNER'S INSTALLER TO SET LEVEL, SECURE UNIT TO CONCRETE SLAB


(5 8")
150

AND CAULK AROUND BASE. ADDITIONAL ANCHORING OF THE SLAB MAY BE


7

NECESSARY DEPENDING ON SITE CONDITIONS TO PREVENT REMOVAL OF


ATM AND SLAB.

OPTIONAL (4) MOUNTING EXISTING CONSTRUCTION:


TEAR-OFF HOLES SEE 1. EXISTING ELECTRICAL CONDUIT, PNEUMATIC TUBE AND/OR P.V.C. PIPE

SENSOR NOTE #4 MUST BE RE-ROUTED TO ALIGN WITH REQUIRED CONCRETE SLAB OPENING.
EXISTING PNEUMATIC TUBE OR P.V.C. PIPE MAY BE USED TO ROUTE
HOLE COMMUNICATION CABLE, EXPRESS BUS CABLE, ALARM CABLE, AND VIDEO
CABLE.

PLAN VIEW

(6")
152
PAGE 6 OF 7

19mm 3
(4") DIA. RIGID
102mm (4") DIA. P.V.C.
CONDUIT (BY OWNER'S E.C.)
PIPE (BY OWNER'S E.C.)
(SEE NOTES)
(SEE NOTES)

102 76

25 (4") (3")

(1")

SECTION "A"
(4) SAFE FLOOR
MOUNTING SETS
16")

SAFE
SUBJECT TO CHANGE WITHOUT NOTICE"

OPTIONAL
"ALL DIMENSIONS AND DESIGN CRITERIA

27- 37

FLOOR
7
-1

TEAR-OFF
SENSOR
16"
1
(1
MINIMUM
(1916")
40

(41516")
MINIMUM
125
FILE NO. 177-797 REV. 1

SECTION THROUGH SAFE FLOOR


FOR ILLUSTRATION ONLY - NOT TO SCALE
OPTIONAL 51mm (2") INSTALLATION PLINTH
ANCHOR LOCATIONS AND DETAILS
L1377
DN SERIES™ 430V FULL-FUNCTION WEATHERIZED WALK-UP
UL, CEN I and CEN III EXGAS SAFES

800 SAFE
1
(31 2")

517
5
(20 16")
DIMENSIONS IN MILLIMETRES

92 583
(DIMENSIONS IN INCHES)

5 15
(3 8") (22 16")

EDGE OF SAFE
SEE NOTE BELOW

(7 8")
194
16")

5
274
1 - ATTACHMENT POINTS FOR

13
(10
INSTALLATION PLINTH

16")
2 - SAFE ATTACHMENT POINTS

437
3
3 - TEAR-OFF-SENSOR ATTACHMENT

(17
1 1
POINT
4 - CABLE LEAD-INS INTO THE
2 2
INSTALLATION PLINTH
16")
859

POWER DATA
13

OPENING IN
(33
1024 SAFE

16")

16")
BOTTOM OF SAFE
(26 4")

150
5

15
680
(40

4 4

(5
(26 4")
680
3
THIRD ANGLE
PROJECTION

CONDUITS CAN BE INSTALLED ON


EITHER SIDE. THE SIDE NOT USED TO
BE COVERED WITH BLANK PLATE.

3
2 2

1 1

SAFE DOOR SIDE

PLAN
NOTES:
THE INSTALLATION PLINTH SHOULD BE ANCHORED IN THE FLOOR AT SAFE INCLUDES A DRILLED HOLE FOR MOUNTING A TEAR-OFF SENSOR.
PAGE 7 OF 7

FOUR ATTACHMENT POINTS. THESE ATTACHMENT POINTS ARE AT


POSITION (1). DRILLED HOLE FOR TEAR-OFF SENSOR:
TO ENSURE THAT THE TEAR-OFF SENSOR CAN BE MOUNTED AFTER THE
THE INSTALLATION PLINTH IS SECURED WITH A TOTAL OF (4) SUPPLIED INSTALLATION PLINTH HAS BEEN INSTALLED, A MAX. 20mm (1316") DIA. HOLE
THREADED RODS (PART #01750006706). THE SAFE ATTACHMENT POINTS
FOR THE TEAR-OFF SENSOR MUST BE DRILLED AT THE TIME THE INSTALLATION
ARE DIMENSIONED ABOVE BASED ON THE OUTER EDGE OF THE SAFE.
PLINTH IS MOUNTED. ASK YOUR ALARM TECHNICIAN ABOUT THE SIZE OF
1
THE INSTALLATION PLINTH IS 3mm( 8") SMALLER THAN THE SAFE ALL THE DRILLED HOLE AND THE FIXING.
AROUND.
THE SYSTEM UL SAFE IS SECURED TO THE INSTALLATION PLINTH USING (4) M16 X 40mm
DRILLED HOLES FOR INSTALLATION PLINTH: (1.57”) PAN HEAD SCREWS AND WASHERS (PART #01750308238). IF MOUNTING KIT IS
11
DIEBOLD NIXDORF RECOMMENDS (4) M20 ANCHOR BOLTS 170mm (6 16”) NOT PROVIDED, USE EQUIVALENT FASTENING MATERIAL.
LONG FOR PROPERLY SECURING THE UNIT (PART #01750308241). THE
OVERALL DRILLING DEPTH DEPENDS ON STRUCTURAL CONDITIONS.
15 WEIGHT OF PLINTH:
THE MOUNTING ANCHORS MUST BE LOCATED AT LEAST 125mm (4 16”)
DEEP IN THE LOAD BEARING CONCRETE (SEE DETAIL). ANCHOR BOLTS UL, CEN 1 (PART #01750378145) - 51mm (2") INSTALLATION PLINTH - 66kg. (146 lbs)
SUBJECT TO CHANGE WITHOUT NOTICE"

MUST BE USED IN ALL (4) AVAILABLE ANCHOR HOLES. IF MOUNTING KIT


"ALL DIMENSIONS AND DESIGN CRITERIA

CEN III ExGAS (PART #01750378146) - 51mm (2") INSTALLATION PLINTH - 66kg. (146 lbs)
IS NOT PROVIDED, USE EQUIVALENT FASTENING MATERIAL. INSTALL
ANCHORS IN ACCORDANCE WITH INSTALLATION TEMPLATE (PART
#01750338732) (ALSO PROVIDED).
(4) UL SAFE MOUNTING SETS

OPTIONAL TEAR-OFF SENSOR

SAFE FLOOR

(4) INSTALLATION BASE MOUNTING SETS


(2")
51

INSTALLATION BASE
FILE NO. 177-797 REV. 1

40 MINIMUM

16")

125 MINIMUM

16")
9
(1

15
(4

SECTION THROUGH INSTALLATION PLINTH


FOR ILLUSTRATION ONLY - NOT TO SCALE

You might also like