MN67604 Eng
MN67604 Eng
User Manual For other PROFINET products see also the following link:
Revision 1.002
English Converter PROFINET to
www.adfweb.com?Product=HD67078 (M-bus)
www.adfweb.com?Product=HD67090 (M-bus Wireless)
www.adfweb.com?Product=HD67178 (SNMP Manager)
PROFINET / PROFIBUS Master - Converter www.adfweb.com?Product=HD67600 (NMEA 2000)
(Order Code: HD67604-A1) www.adfweb.com?Product=HD67601 (Serial)
www.adfweb.com?Product=HD67602 (Modbus Master)
www.adfweb.com?Product=HD67603 (Modbus Slave)
for Website information: www.adfweb.com?Product=HD67604 (PROFIBUS Master)
www.adfweb.com/?Product=HD67604 www.adfweb.com?Product=HD67605 (PROFIBUS Slave)
www.adfweb.com?Product=HD67606 (CAN)
www.adfweb.com?Product=HD67607 (CANopen)
for Price information: www.adfweb.com?Product=HD67608 (DeviceNet Master)
www.adfweb.com/?Price=HD67604-A1 www.adfweb.com?Product=HD67609 (DeviceNet Slave)
www.adfweb.com?Product=HD67610 (J1939)
www.adfweb.com?Product=HD67612 (Modbus TCP Slave)
www.adfweb.com?Product=HD67613 (SNMP Agent)
Benefits and Main Features: www.adfweb.com?Product=HD67614 (DMX)
www.adfweb.com?Product=HD67615 (NMEA 0183)
PROFIBUS up to 6Mbps www.adfweb.com?Product=HD67633 (S7comm)
www.adfweb.com?Product=HD67659 (EtherNet)
Two PROFINET ports www.adfweb.com?Product=HD67660 (EtherNet/IP Slave)
Industrial temperature range: www.adfweb.com?Product=HD67661 (EtherNet/IP Master)
www.adfweb.com?Product=HD67679 (BACnet Slave)
-40°C / +85°C (-40°F / +185°F) www.adfweb.com?Product=HD67719 (BACnet Master)
www.adfweb.com?Product=HD67752 (IEC 61850 Server)
www.adfweb.com?Product=HD67778 (IEC 61850 Client)
www.adfweb.com?Product=HD67818 (KNX)
www.adfweb.com?Product=HD67848 (DALI)
www.adfweb.com?Product=HD67876 (IO-Link Master)
www.adfweb.com?Product=HD67912 (HART)
www.adfweb.com?Product=HD67952 (MQTT)
www.adfweb.com?Product=HD67984 (IO-Link Slave)
www.adfweb.com?Product=HD67B22 (OPC UA Client)
www.adfweb.com?Product=HD67B46 (OPC UA Server)
www.adfweb.com?Product=HD67C77 (EnOcean)
www.adfweb.com?Product=HD67D33 (LoRaWAN)
www.adfweb.com?Product=HD67E23 (EtherCAT Slave)
www.adfweb.com?Product=HD67E73 (EtherCAT Master)
www.adfweb.com?Product=HD67F33 (LoRaWAN Gateway)
User manual
Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2 Updated;
REVISION LIST 2
Related to the product you own.
WARNING 2
TRADEMARKS 2
To obtain the most recently updated document, note the “document code”
SECURITY ALERT 3
that appears at the top right-hand corner of each page of this document.
EXAMPLE OF CONNECTION 4
CONNECTION SCHEME 5
With this “Document Code” go to web page www.adfweb.com/download/
CHARACTERISTICS 6
and search for the corresponding code on the page. Click on the proper
CONFIGURATION 6
“Document Code” and download the updates.
POWER SUPPLY 7
FUNCTION MODES 8 To obtain the updated documentation for the product that you own, note
LEDS 9 the “Document Code” (Abbreviated written "Doc. Code" on the label on
PROFIBUS 10 the product) and download the updated from our web site
PROFINET 10 www.adfweb.com/download/
USB 11
USE OF CONFIGURATOR SW67604 12
NEW CONFIGURATION / OPEN CONFIGURATION 13 REVISION LIST:
SET COMMUNICATION 14
PROFIBUS NETWORK 15 Revision Date Author Chapter Description
MASTER PROFIBUS OPTIONS 16 1.000 26/07/2012 Fl All First release version
PROFIBUS DEVICE 17 1.001 09/01/2013 Nt All Added new chapters
- MODULE SELECTION 18 1.002 16/04/2024 Ln All Revision
- USER PARAMETERS 20
- MODULE PARAMETERS 22
- CAPABILITIES 23
- OPTIONS 24 WARNING:
XML FILE 25
UPDATE DEVICE 26 ADFweb.com reserves the right to change information in this manual
MECHANICAL DIMENSIONS 28 about our product without warning.
ORDER CODE 29 ADFweb.com is not responsible for any error this manual may contain.
ACCESSORIES 29
PLC CONFIGURATION 30
DISCLAIMER 33 TRADEMARKS:
OTHER REGULATIONS AND STANDARDS 33
WARRANTIES AND TECHNICAL SUPPORT 33 All trademarks mentioned in this document belong to their respective
Pagina 2 di 34
RETURN POLICY 34 owners.
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.
CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.
EXAMPLE OF CONNECTION:
Used like switch, it allows to connect a second device to the network, without using an external switch; or to connect the device to an Access
Point for connect them to a Wireless network (also internet).
CONNECTION SCHEME:
CHARACTERISTICS:
The configurable “PROFINET / PROFIBUS Master - Converter” allows the following characteristics:
Triple isolation between PROFINET/PROFIBUS, PROFINET/Power Supply, PROFIBUS/Power Supply.
Mountable on 35mm Rail DIN;
Power Supply 8...24V AC or 12...35V DC;
Temperature range -40°C to +85°C;
Up to 1440 bytes from PROFINET to PROFIBUS (IN);
Up to 1440 bytes from PROFIBUS (OUT) to PROFINET;
Ethernet switch for enter/exit connection.
CONFIGURATION:
You need Compositor SW67604 software on your PC in order to perform the following:
Define the parameter of the PROFIBUS;
Define the parameter of the PROFINET;
Define the PROFIBUS network.
POWER SUPPLY:
The devices can be powered between a wide range of tensions. For more details see the two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
HD67604-A1 8V 24V 12V 35V
Device W/VA
HD67604-A1 4
HD67604-A1
FUNCTION MODES:
The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.
For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).
According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).
Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position for working even if the Ethernet cable isn’t inserted.
LEDS:
The device has got six LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
PROFIBUS:
The PROFIBUS uses a 9-pin D-SUB connector. The pin assignment is defined
like in the right figure.
PROFINET:
The PROFINET connection must be made using Connector3 and/or Connector4 of HD67604-A1 with at least a Category 5E cable. The
maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to
100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is
recommended the use of a cross cable.
To configure the Converter, use the available software that runs with Windows, called SW67604. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10 or 11; 32/64bit).
The “New Configuration” button creates the folder which contains the entire device configuration.
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
SET COMMUNICATION:
This section defines the fundamental communication parameter of two buses, PROFIBUS and
PROFINET.
By pressing the “Set Communication” button from the main window for SW67604 (Fig. 2) the
window “SET COMMUNICATION” appears (Fig. 3).
The window is divided in two sections, one for the PROFIBUS and the other for the PROFINET.
PROFIBUS NETWORK:
By pressing the “PROFIBUS Network” button from the main window for SW67604 (Fig. 2) the window “PROFIBUS Network Management”
(Fig. 4) appears.
By pressing the “Master PROFIBUS Options” button from the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Master Options”
window appears (Fig. 5).
In this window is possible to set the WatchDog Time for the PROFIBUS Slaves.
Note:
Fact1 and Fact2 could be write in decimal o hexadecimal (with prefix “0x” or “$”) and the values must between 1 and 255
Warning:
The WatchDog time must be between 200 and 650250 milliseconds.
PROFIBUS DEVICE:
By pressing the “Add Slave PROFIBUS” and “Modify Slave PROFIBUS” button (or double click above an existent PROFIBUS Slave) from
the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Device” window appears (Fig. 6).
MODULE SELECTION:
By pressing the “Manual Module” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually” window appears (Fig. 8).
In this window is possible to add a Module manually, i.e. writing the configuration of the module (in hexadecimal).
Note:
The Values inserted in the table must between 00 and FF
USER PARAMETERS:
The section “User Parameters” is used to modify the parameters of the PROFIBUS slave (Fig. 9).
By pressing the “Modify User Parameters Manually” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually”
window appears (Fig. 10).
In this window is possible to add/modify the User and/or Modules Parameters manually, i.e. writing the configuration of the parameters (in
hexadecimal).
Note:
The Values inserted in the table must between 00 and FF
MODULE PARAMETERS:
The section “Module Parameters” is used to modify the parameters of the Modules (Fig. 11).
CAPABILITIES:
The section “Capabilities” is used only to show which features/baudrates available in the PROFIBUS device. The Green Icon indicate that
capability/baudrate is available, the Red Icon indicate no compatibilities with that capability/baudrate (Fig. 12).
OPTIONS:
XML FILE:
By Pressing the “PROFINET XML” button from the main window for SW67604 (Fig. 2) it is possible to generate the xml file to be imported
into the master PROFINET.
UPDATE DEVICE:
By pressing the “Update Device” button, it is possible to load the created Configuration into the
device; and also the Firmware, if necessary. This by using the Ethernet port.
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.
If you know the actual IP address of the device, you have to use this procedure:
Turn ON the Device with the Ethernet cable inserted; Figure 15: “Update device” windows
Insert the actual IP of the Converter;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67604 device.
Warning:
If Fig. 16 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System;
If you are using Windows Seven, Vista, 8, 10 or 11 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you
have to cancel the ARP table every time you connect a new device on Ethernet. For
do this you have to launch the "Command Prompt" and write the command "arp -
d". Pay attention that with Windows Vista, Seven, 8, 10 or 11 you have to launch
the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
Figure 16: “Error” window
Warning:
In the case of HD67604 you have to use the software “SW67604”: www.adfweb.com\download\filefold\SW67604.zip.
MECHANICAL DIMENSIONS:
ORDERING INFORMATIONS:
Connectors Type
1: Removable 5mm Screw Terminal
Enclosure Type
A: 1M, 35mm DIN Rail mounting
Device Family
HD67604: PROFINET / PROFIBUS Master - Converter
ACCESSORIES:
Order Code: AC34011 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V DC
Order Code: AC34012 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 24 V DC
PLC CONFIGURATION:
The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the
TIA Portal V11-software of Siemens. In case of using a control system from another supplier please attend to the associated documentation.
These are the steps to follow:
2) Import the module in the network; connect the device to the PLC network and edit the parameters of IP, station name etc.
DISCLAIMER
All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.
ADFweb.com S.r.l.
Via Strada Nuova, 17
IT-31010 Mareno di Piave
TREVISO (Italy)
Phone +39.0438.30.91.31
Fax +39.0438.49.20.99
www.adfweb.com