MN67604 Eng

The document is a user manual for the PROFINET/PROFIBUS Master Converter (Order Code: HD67604-A1), detailing its features, specifications, and configuration instructions. It includes information on power supply requirements, connection schemes, operational modes, and safety warnings. The manual also provides links for additional product information and software needed for configuration.

Uploaded by

imed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views34 pages

MN67604 Eng

The document is a user manual for the PROFINET/PROFIBUS Master Converter (Order Code: HD67604-A1), detailing its features, specifications, and configuration instructions. It includes information on power supply requirements, connection schemes, operational modes, and safety warnings. The manual also provides links for additional product information and software needed for configuration.

Uploaded by

imed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

User Manual PROFINET / PROFIBUS Master - Converter

Document code: MN67604_ENG Revision 1.002 Page 1 of 34


Industrial Electronic Devices

User Manual For other PROFINET products see also the following link:
Revision 1.002
English Converter PROFINET to
www.adfweb.com?Product=HD67078 (M-bus)
www.adfweb.com?Product=HD67090 (M-bus Wireless)
www.adfweb.com?Product=HD67178 (SNMP Manager)
PROFINET / PROFIBUS Master - Converter www.adfweb.com?Product=HD67600 (NMEA 2000)
(Order Code: HD67604-A1) www.adfweb.com?Product=HD67601 (Serial)
www.adfweb.com?Product=HD67602 (Modbus Master)
www.adfweb.com?Product=HD67603 (Modbus Slave)
for Website information: www.adfweb.com?Product=HD67604 (PROFIBUS Master)
www.adfweb.com/?Product=HD67604 www.adfweb.com?Product=HD67605 (PROFIBUS Slave)
www.adfweb.com?Product=HD67606 (CAN)
www.adfweb.com?Product=HD67607 (CANopen)
for Price information: www.adfweb.com?Product=HD67608 (DeviceNet Master)
www.adfweb.com/?Price=HD67604-A1 www.adfweb.com?Product=HD67609 (DeviceNet Slave)
www.adfweb.com?Product=HD67610 (J1939)
www.adfweb.com?Product=HD67612 (Modbus TCP Slave)
www.adfweb.com?Product=HD67613 (SNMP Agent)
Benefits and Main Features: www.adfweb.com?Product=HD67614 (DMX)
www.adfweb.com?Product=HD67615 (NMEA 0183)
PROFIBUS up to 6Mbps www.adfweb.com?Product=HD67633 (S7comm)
www.adfweb.com?Product=HD67659 (EtherNet)
Two PROFINET ports www.adfweb.com?Product=HD67660 (EtherNet/IP Slave)
Industrial temperature range: www.adfweb.com?Product=HD67661 (EtherNet/IP Master)
www.adfweb.com?Product=HD67679 (BACnet Slave)
-40°C / +85°C (-40°F / +185°F) www.adfweb.com?Product=HD67719 (BACnet Master)
www.adfweb.com?Product=HD67752 (IEC 61850 Server)
www.adfweb.com?Product=HD67778 (IEC 61850 Client)
www.adfweb.com?Product=HD67818 (KNX)
www.adfweb.com?Product=HD67848 (DALI)
www.adfweb.com?Product=HD67876 (IO-Link Master)
www.adfweb.com?Product=HD67912 (HART)
www.adfweb.com?Product=HD67952 (MQTT)
www.adfweb.com?Product=HD67984 (IO-Link Slave)
www.adfweb.com?Product=HD67B22 (OPC UA Client)
www.adfweb.com?Product=HD67B46 (OPC UA Server)
www.adfweb.com?Product=HD67C77 (EnOcean)
www.adfweb.com?Product=HD67D33 (LoRaWAN)
www.adfweb.com?Product=HD67E23 (EtherCAT Slave)
www.adfweb.com?Product=HD67E73 (EtherCAT Master)
www.adfweb.com?Product=HD67F33 (LoRaWAN Gateway)
User manual

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 2 of 34
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2 Updated;
REVISION LIST 2
Related to the product you own.
WARNING 2
TRADEMARKS 2
To obtain the most recently updated document, note the “document code”
SECURITY ALERT 3
that appears at the top right-hand corner of each page of this document.
EXAMPLE OF CONNECTION 4
CONNECTION SCHEME 5
With this “Document Code” go to web page www.adfweb.com/download/
CHARACTERISTICS 6
and search for the corresponding code on the page. Click on the proper
CONFIGURATION 6
“Document Code” and download the updates.
POWER SUPPLY 7
FUNCTION MODES 8 To obtain the updated documentation for the product that you own, note
LEDS 9 the “Document Code” (Abbreviated written "Doc. Code" on the label on
PROFIBUS 10 the product) and download the updated from our web site
PROFINET 10 www.adfweb.com/download/
USB 11
USE OF CONFIGURATOR SW67604 12
NEW CONFIGURATION / OPEN CONFIGURATION 13 REVISION LIST:
SET COMMUNICATION 14
PROFIBUS NETWORK 15 Revision Date Author Chapter Description
MASTER PROFIBUS OPTIONS 16 1.000 26/07/2012 Fl All First release version
PROFIBUS DEVICE 17 1.001 09/01/2013 Nt All Added new chapters
- MODULE SELECTION 18 1.002 16/04/2024 Ln All Revision
- USER PARAMETERS 20
- MODULE PARAMETERS 22
- CAPABILITIES 23
- OPTIONS 24 WARNING:
XML FILE 25
UPDATE DEVICE 26 ADFweb.com reserves the right to change information in this manual
MECHANICAL DIMENSIONS 28 about our product without warning.
ORDER CODE 29 ADFweb.com is not responsible for any error this manual may contain.
ACCESSORIES 29
PLC CONFIGURATION 30
DISCLAIMER 33 TRADEMARKS:
OTHER REGULATIONS AND STANDARDS 33
WARRANTIES AND TECHNICAL SUPPORT 33 All trademarks mentioned in this document belong to their respective
Pagina 2 di 34
RETURN POLICY 34 owners.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 3 of 34
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.

CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 4 of 34
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

Used with only one PROFINET connection.

Used like switch, it allows to connect a second device to the network, without using an external switch; or to connect the device to an Access
Point for connect them to a Wireless network (also internet).

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 5 of 34
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1: Connection scheme for HD67604-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 6 of 34
Industrial Electronic Devices

CHARACTERISTICS:

The configurable “PROFINET / PROFIBUS Master - Converter” allows the following characteristics:
Triple isolation between PROFINET/PROFIBUS, PROFINET/Power Supply, PROFIBUS/Power Supply.
Mountable on 35mm Rail DIN;
Power Supply 8...24V AC or 12...35V DC;
Temperature range -40°C to +85°C;
Up to 1440 bytes from PROFINET to PROFIBUS (IN);
Up to 1440 bytes from PROFIBUS (OUT) to PROFINET;
Ethernet switch for enter/exit connection.

CONFIGURATION:

You need Compositor SW67604 software on your PC in order to perform the following:
Define the parameter of the PROFIBUS;
Define the parameter of the PROFINET;
Define the PROFIBUS network.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 7 of 34
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered between a wide range of tensions. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
HD67604-A1 8V 24V 12V 35V

Consumption at 24V DC:

Device W/VA
HD67604-A1 4

Caution: Not reverse the polarity power

HD67604-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 8 of 34
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:
The first, with Dip2 in Off position (factory setting), is used for the normal working of the device.
The second, with Dip2 in On position, is used for upload the Project/Firmware.

For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).

According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).

Warning:
Dip1 of ‘Dip-Switch A’ must be at ON position for working even if the Ethernet cable isn’t inserted.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 9 of 34
Industrial Electronic Devices

LEDS:

The device has got six LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode


1: ON [supply voltage ] ON: Device powered ON: Device powered
(green) OFF: Device not powered OFF: Device not powered
ON: Device not able to communicate with at least one
2: MT [maintenance display] Blinks quickly: Boot state
PROFIBUS Slave
(yellow) Blinks very slowly (~0.5Hz): update in progress
OFF: No maintenance are present
ON: The Ethernet connection is defective; the IP
address exists several times in the network; the own
NameOfStation exists several times in the network; no
IP address has been set Blinks quickly: Boot state
3: BF [bus fault] (red)
Flashing: At least one configured AR is no longer in Blinks very slowly (~0.5Hz): update in progress
the data exchange
OFF: No errors are present
ON: At least one AR is not in the data exchange Blinks quickly: Boot state
4: SF [group error] (red)
OFF: No errors are present Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
5: Ethernet1 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
6: Ethernet2 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 10 of 34
Industrial Electronic Devices

PROFIBUS:

The PROFIBUS uses a 9-pin D-SUB connector. The pin assignment is defined
like in the right figure.

Here some codes of cables:


Belden: p/n 183079A - Continuous Armor DataBus® ISA/SP-50
PROFIBUS Cable.

PROFINET:

The PROFINET connection must be made using Connector3 and/or Connector4 of HD67604-A1 with at least a Category 5E cable. The
maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to
100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to connect the device to a PC/PLC/other is
recommended the use of a cross cable.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 11 of 34
Industrial Electronic Devices

USE OF CONFIGURATOR SW67604:

To configure the Converter, use the available software that runs with Windows, called SW67604. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10 or 11; 32/64bit).

When launching the SW67604 this window appears (Fig. 2).

Figure 2: Main window for SW67604

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 12 of 34
Industrial Electronic Devices

NEW CONFIGURATION / OPEN CONFIGURATION:

The “New Configuration” button creates the folder which contains the entire device configuration.

A device configuration can also be imported or exported:


To clone the configurations of a programmable “PROFINET / PROFIBUS Master - Converter”
in order to configure another device in the same manner, it is necessary to maintain the
folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the button
“Open Configuration”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 13 of 34
Industrial Electronic Devices

SOFTWARE OPTIONS:

By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.

In the section “Language” it is possible to change the language of the software.

In the section “Connection Options”, it is possible to check if there are some


updatings of the software compositor in ADFweb.com website.
Checking the option “Check Software Update at Start of Program”, the
SW67602 check automatically if there are updatings when it is launched.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 14 of 34
Industrial Electronic Devices

SET COMMUNICATION:

This section defines the fundamental communication parameter of two buses, PROFIBUS and
PROFINET.

By pressing the “Set Communication” button from the main window for SW67604 (Fig. 2) the
window “SET COMMUNICATION” appears (Fig. 3).

The window is divided in two sections, one for the PROFIBUS and the other for the PROFINET.

The means of the fields for “PROFIBUS” are:


In the field “ID Dev.” the address of the PROFIBUS side is defined;
In the field “Baudrate” the baudrate for the PROFIBUS side is defined;
If the field “Send Sync” is checked, the converter will send Sync signal at every cycle;
If the field “Send Freeze” is checked, the converter will send Freeze signal at every cycle.

The means of the fields for “PROFINET” are:


In the fields “IP ADDRESS” insert the IP address that you want to give to the Converter;
In the fields “SUBNET Mask” insert the Subnet Mask;
In the fields “GATEWAY” insert the default gateway that you want to use. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for PROFINET communication is defined. The port has a fixed
value of 34964;
In the field "PROFINET Name of Station" is possible to assign a name to the PROFINET node.
If the field “Diagnostic” is checked, the converter will create an additional Diagnostic module
inside the GSDML file used for checking the status of PROFIBUS communication with each
slave. The status is passed as a bit for each slave;
If the field “Extended Diagnostic” is checked, the converter will create an additional
Diagnostic module inside the GSDML file used for checking the status of PROFIBUS
communication with each slave. The status is passed as a byte for each slave.
Figure 3: “Set Communication” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 15 of 34
Industrial Electronic Devices

PROFIBUS NETWORK:

By pressing the “PROFIBUS Network” button from the main window for SW67604 (Fig. 2) the window “PROFIBUS Network Management”
(Fig. 4) appears.

In this window is possible to:


Modify the PROFIBUS Master Options (“Master PROFIBUS Options”);
Add a PROFIBUS Slave in the Network of the Master (“Add Slave PROFIBUS”);
Modify a PROFIBUS Slave in the Network (“Modify Slave PROFIBUS”);
Remove a PROFIBUS Slave from the Network (“Remove Slave PROFIBUS”).

Figure 4: “PROFIBUS Network” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 16 of 34
Industrial Electronic Devices

MASTER PROFIBUS OPTIONS:

By pressing the “Master PROFIBUS Options” button from the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Master Options”
window appears (Fig. 5).

In this window is possible to set the WatchDog Time for the PROFIBUS Slaves.

Figure 5: “PROFIBUS Master Options” window

Note:
Fact1 and Fact2 could be write in decimal o hexadecimal (with prefix “0x” or “$”) and the values must between 1 and 255

Warning:
The WatchDog time must be between 200 and 650250 milliseconds.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 17 of 34
Industrial Electronic Devices

PROFIBUS DEVICE:

By pressing the “Add Slave PROFIBUS” and “Modify Slave PROFIBUS” button (or double click above an existent PROFIBUS Slave) from
the “PROFIBUS Network” window (Fig. 4) the “PROFIBUS Device” window appears (Fig. 6).

In this window is possible to:


Set the PROFIBUS Slave ID (“ID Slave
PROFIBUS”);
Select the Modules present in the
PROFIBUS Slave from the Available
Modules in GSD file (“Module
Selection”);
Modify the User Parameters (if present) of
the PROFIBUS device (“User
Parameters”);
Modify the Parameters (if present) of the
Module Selected (“Module
Parameters”);
Watch Features and Baudrate supported
from the PROFIBUS device
(“Capabilities”);
Select the Sync, Freeze and Reset of Data
Options (“Options”).

Figure 6: “PROFIBUS Device” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 18 of 34
Industrial Electronic Devices

MODULE SELECTION:

The section “Module Selection” is used to select which


Modules are present in the Slave (Fig. 7).

In this section is possible to:


Check the list of the Modules selected (“Select
Modules”) (Fig. 7, point (1)) and the list of Modules
Available in GSD file (“Available Modules") (Fig. 7,
point (7));
Add a Module from the list of GSD file (Fig. 7, point
(6));
Remove a Module from selected list (Fig. 7, point
(5));
Add all Modules present in the GSD file (Fig. 7, point
(4));
Remove all Modules from selected list (Fig. 7, point
(3));
Insert a Module not present in the GSD file (“Manual
Module”) (Fig. 7 point (2)). For more info see the
section “Manual Module” below;
Enable the read of configuration directly from the
PROFIBUS Slave (“Use module configuration
readed from device”) (Fig 7, point (8)). If this
option is enable the configuration of the modules is
discorded and the device read the correct
configuration directly to the PROFIBUS slave.

Figure 7: “PROFIBUS Device – Module Selection” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 19 of 34
Industrial Electronic Devices

By pressing the “Manual Module” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually” window appears (Fig. 8).

In this window is possible to add a Module manually, i.e. writing the configuration of the module (in hexadecimal).

The means of the fields are:


In the field “Description of Module” a name of the Module is defined;
In the field “Insert the Configuration of Module (HEX)” the
configuration of the module is defined. The configuration must be write in
hexadecimal mode (without prefix “0x” o “$”).

To modify a Module inserted manually, is neccessary to do a double click on the


module to change in the “Select Module” list (Fig. 7, point (1)). It is possible to
change only the module inserted manually.

Note:
The Values inserted in the table must between 00 and FF

Figure 8: “Add/Modify Module Manually” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 20 of 34
Industrial Electronic Devices

USER PARAMETERS:

The section “User Parameters” is used to modify the parameters of the PROFIBUS slave (Fig. 9).

In this section there are:


The List of all Parameters available for the
PROFIBUS device (“User Parameters”) (Fig. 9,
point (1));
The Configuration of all parameters in RAW
(“Parameters in RAW (Hex)”) (Fig. 9,
point(2));
The “Use Parameter Inserted Manually”,
enable this option is possible to insert
manually the parameters of Device and also of
the Modules. Using the “Modify User
Parameters Manually” button is possible to
insert/modify the parametrization of the device
(and/or modules). For more info see below.
(Fig. 9, point(3));
The admited value for the selected parameter.
It is possible to select the value desired and
confirm it with the “Apply” button. If no value
appears in this table, the “Min Value” and “Max
Value” are the limit of the parameter. (Fig. 9,
point(4));
The “Apply” button is used to confirm the new
value of the parameter, the “Default” button
is used to load the factory value for the
parameter. In “New Value” edit box it is
possible to set the new value. (Fig. 9,
point(5)).
Figure 9: “PROFIBUS Device – User Parameters” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 21 of 34
Industrial Electronic Devices

By pressing the “Modify User Parameters Manually” button from the “PROFIBUS Device” window (Fig. 6) the “Add Module Manually”
window appears (Fig. 10).

In this window is possible to add/modify the User and/or Modules Parameters manually, i.e. writing the configuration of the parameters (in
hexadecimal).

The means of the fields are:


In the field “Insert the number of User and Module Parameters”
the number of byte for the parameter have to be inserted;
In the field “Insert the Configuration of Module (HEX)” the
configuration of the User and/or Modules Parameters is defined. The
configuration must be write in hexadecimal mode (without prefix “0x”
o “$”).

Note:
The Values inserted in the table must between 00 and FF

Figure 10: “Add/Modify User Parameters Manually” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 22 of 34
Industrial Electronic Devices

MODULE PARAMETERS:

The section “Module Parameters” is used to modify the parameters of the Modules (Fig. 11).

In this section there are:


The List of all Module selected in the GSD file
(“Available modules”) (Fig. 11, point (1));
The List of all Parameters available for the Module
selected (“Parameters of module”) (Fig. 11, point
(2));
The Configuration of all parameters in RAW for the
Module selected (“Parameters in RAW (Hex)”) (Fig.
11, point(3));
The admited value for the selected parameter. It is
possible to select the value desired and confirm it
with the “Apply” button. If no value appears in this
table, the “Min Value” and “Max Value” are the limit
of the parameter. (Fig. 11, point(4));
The “Apply” button is used to confirm the new
value of the parameter, the “Default” button is
used to load the factory value for the parameter. In
“New Value” edit box it is possible to set the new
value. (Fig. 11, point(5));

Figure 11: “PROFIBUS Device – Module Parameters” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 23 of 34
Industrial Electronic Devices

CAPABILITIES:

The section “Capabilities” is used only to show which features/baudrates available in the PROFIBUS device. The Green Icon indicate that
capability/baudrate is available, the Red Icon indicate no compatibilities with that capability/baudrate (Fig. 12).

Figure 12: “PROFIBUS Device – Capabilities” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 24 of 34
Industrial Electronic Devices

OPTIONS:

The section “Options” is used to enable


some option for each PROFIBUS device
(Fig. 13).

The means of the fields are:


In the field “Enable Sync” the
PROFIBUS Sync command is
enable. This option is enable only
if the “Sync Mode” is supported
by the device (see Capabilities
section to check it);
In the field “Enable Freeze” the
PROFIBUS Freeze command is
enable. This option is enable only
if the “Freeze Mode” is supported
by the device (see Capabilities
section to check it);
In the field “Reset data if
PROFIBUS master loses
communication with the
slave” is possible to select to
cancel the data of the slave if the
Master lost the connection with
the device;
In the field “Reset data if
PROFINET master doesn’t
poll the slave in ...
milliseconds” is possible to
select to cancel the data sended
to the slave PROFIBUS if the Figure 13: “PROFIBUS Device – Options” window
Converter don’t receive a
PROFINET frame within the time expressed in the field.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 25 of 34
Industrial Electronic Devices

XML FILE:

By Pressing the “PROFINET XML” button from the main window for SW67604 (Fig. 2) it is possible to generate the xml file to be imported
into the master PROFINET.

Figure 14: “PROFINET XML File Name”


window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 26 of 34
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the “Update Device” button, it is possible to load the created Configuration into the
device; and also the Firmware, if necessary. This by using the Ethernet port.

If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip1 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.

If you know the actual IP address of the device, you have to use this procedure:

Turn ON the Device with the Ethernet cable inserted; Figure 15: “Update device” windows
Insert the actual IP of the Converter;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.

At this point the configuration/firmware on the device is correctly updated.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 27 of 34
Industrial Electronic Devices

Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67604 device.

Warning:
If Fig. 16 appears when you try to do the Update try these points before seeking
assistance:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System;
If you are using Windows Seven, Vista, 8, 10 or 11 make sure that you have the
administrator privileges;
In case you have to program more than one device, using the "UDP Update", you
have to cancel the ARP table every time you connect a new device on Ethernet. For
do this you have to launch the "Command Prompt" and write the command "arp -
d". Pay attention that with Windows Vista, Seven, 8, 10 or 11 you have to launch
the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
Figure 16: “Error” window

Warning:
In the case of HD67604 you have to use the software “SW67604”: www.adfweb.com\download\filefold\SW67604.zip.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 28 of 34
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 17: Mechanical dimensions scheme for HD67604-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 29 of 34
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:


HD67604 – A 1

Connectors Type
1: Removable 5mm Screw Terminal

Enclosure Type
A: 1M, 35mm DIN Rail mounting

Device Family
HD67604: PROFINET / PROFIBUS Master - Converter

Order Code: HD67604-A1 - PROFINET / PROFIBUS Master - Converter

ACCESSORIES:

Order Code: AC34011 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V DC
Order Code: AC34012 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz – 24 V DC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 30 of 34
Industrial Electronic Devices

PLC CONFIGURATION:

The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the
TIA Portal V11-software of Siemens. In case of using a control system from another supplier please attend to the associated documentation.
These are the steps to follow:

1) Install the description file of the module.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 31 of 34
Industrial Electronic Devices

2) Import the module in the network; connect the device to the PLC network and edit the parameters of IP, station name etc.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 32 of 34
Industrial Electronic Devices

3) Load the configuration into the PLC.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 33 of 34
Industrial Electronic Devices

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual PROFINET / PROFIBUS Master - Converter
Document code: MN67604_ENG Revision 1.002 Page 34 of 34
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.