SPECIFICATIONS
Voltage input range Capacitance measurement accuracy (23 °C)
85-265 V rms, 50/60 Hz, 60 VA ±5% ±5 nF
Battery life Voltage output accuracy (0 °C to 30 °C)
Typical capacity is 6 hours continuous testing at 5 kV with a 100 MΩ +4%, -0% ±10 V of nominal test voltage at 1 GΩ load
load
Current measurement range
Test voltages 0.01 nA to 5 mA
250 V, 500 V, 1 kV, 2.5 kV, 5 kV ranges, adjustable in 10 V steps from
Current measurement accuracy (23 °C)
50 V to 1 kV, and 25 V steps from 1 kV to 5 kV
±5% ±0.2 nA at all voltages
Accuracy (23°C, 5 kV)
Interference rejection
5000 V 2500 V 1000 V 500 V 250 V
1 mA per 250 V up to a maximum of 3 mA
±5% to 1 TΩ 500 GΩ 200 GΩ 100 GΩ 50 GΩ
Timer range
±20% to 10 TΩ 5 TΩ 2 TΩ 1 TΩ 500 GΩ Counts up to 99 minutes and 59 seconds from start of test
15 second minimum setting for test voltage ≥1000 V
Guard
30 second minimum setting for test voltage <1000 V
2% error guarding 500 kΩ leakage with 100 MΩ load
Test regimes
Display range
Auto IR, PI, SV, DD
Digital display 10 kΩ to 15 TΩ (3 digits)
DAR is calculated automatically if timers T1 and T2 are set
Analogue display 100 kΩ to 1 TΩ
Interface
Short circuit/charge current RS232: 38400 Baud, 8 data bits, 0 parity, 1 stop bit, no flow control.
5 mA 5 kV
USB
Capacitor charge time
<1.5 seconds per µF at 5mA to 5 kV Data storage
Data stored: selected voltage, test time elapsed, voltage applied, leakage
Capacitor discharge time current, and insulation resistance. The PI, DAR, capacitance, time
<120 ms per µF to discharge from 5 kV to 50 V constant and DD values are also stored if available at the end of the test.
Megger Download Manager may be used to transfer this data to a PC.
Capacitance measurement (500 V minimum test voltage)
10 nF to 50 µF (dependent on test voltage)