0% found this document useful (0 votes)
48 views7 pages

Schneider Electric - PowerLogic-P3-Protection-Relays - REL52034

The document provides a detailed datasheet for the PowerLogic P3U20 universal protection relay, including its specifications, features, and environmental data. Key features include a power supply range of 48-230V, 10 digital inputs, and various communication protocols such as Modbus RTU and DNP3. It also outlines the product's compliance with various standards and its environmental sustainability efforts.

Uploaded by

energyarian2025
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views7 pages

Schneider Electric - PowerLogic-P3-Protection-Relays - REL52034

The document provides a detailed datasheet for the PowerLogic P3U20 universal protection relay, including its specifications, features, and environmental data. Key features include a power supply range of 48-230V, 10 digital inputs, and various communication protocols such as Modbus RTU and DNP3. It also outlines the product's compliance with various standards and its environmental sustainability efforts.

Uploaded by

energyarian2025
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Product datasheet

Specifications

universal protection relay,


PowerLogic P3U20, 4L ringlug, 1U,
10DI/5DO, Uaux: 48-230V, DI:
24-230V, RS-485
REL52034

Main
Range of product PowerLogic P3

Product or component type Protection relay

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Relay application Universal

product reference P3U20-6AAA1ABAA

Mounting case size 20TE

power supply 48...230 V AC/DC

measuring inputs : 1/5 A CT phase current 3


: 1/5 A CT residual current 1
: 100 V/110 V VT voltage 1

number of Digital Inputs (DI) 10

number of analogue inputs 0

number of Digital Outputs (DO) 1 watchdog


5

number of analogue outputs 0

type of temperature module Copper cable external module


connection Fiber optic cable external module

communication ports USB port 1 front


RS485 1 rear

communication protocols IEC 60870-5-101


IEC 60870-5-103
DNP3
Modbus RTU
DeviceNet
SPAbus

Cybersecurity Password protection


Port hardening

15-Feb-2025 1
protection functions Phase undercurrent 37
Negative sequence overcurrent 46
Broken conductor 46 I2/I1
Excessive starting time, locked rotor 48/51LR
Thermal overload protection 49
Phase overcurrent 50/51
Earth fault overcurrent 50N/51N
Breaker failure 50BF
Switch ON to fault (SOTF)
Capacitor bank unbalance 51C
Capacitor overvoltage 59C
Neutral voltage displacement 59N
Motor restart inhibition 66
Directional earth fault 67N
Transient earth fault 67NI
CT supervision 60
VT supervision 60
H2 detection 68H2
H5 detection 68H5
Recloser 79
Lockout relay 86
Cold load pick-up
Programmable stages 99
Programmable curve

Arc flash protection No

measurement functions Current 3-phase


Current zero sequence
Current positive sequence
Current negative sequence
Current ratio of negative and positive
Voltage phase to earth
Voltage phase to phase
Voltage zero sequence
Voltage positive sequence
Voltage negative sequence
Voltage ratio of negative and positive
Short circuit fault reactance
Fault location current
Earth fault reactance
Frequency
Active power
RMS active power
Reactive power
RMS reactive power
Apparent power
RMS apparent power
Active energy
Reactive energy
Cos φ
Tan φ
Power angle
Power factor
Voltage phasor diagram view
Current phasor diagram view
Current 2nd, 15th harmonics with THD
Voltage 2nd, 15th harmonics with THD
Voltage interruption
Condition monitoring CB wear

control functions Switchgear control and monitoring


Programmable switchgear interlocking
Local control on single-line diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with Easergy SmartApp
Web-server
Programmable logic

controllable switchgear devices 2 controlled + 4 displayed

number of setting groups 4

monitoring functions Trip circuit supervision 74


Circuit breaker monitoring
Relay self-monitoring

2 15-Feb-2025
logs and records Event recording
Disturbance recording
Tripping context

Switchgear diagnosis type CT supervision


Trip circuit supervision ANSI code: TCS

Connections - terminals Screw removable (digital input/output)


Ring lugs removable (current transformer)
Pin removable (voltage transformer)

Complementary
Operating threshold 24...230 V AC/DC

Software name EcoStruxure Power Device


ESetup Easergy Pro

Web server Embedded HTTP server

Display type LCD 128 x 64 pixels with single line diagram

Number of key 2 customizable

Local signalling 4 LEDs


8 LEDs programmable

Standards IEC

Height 169.5 mm

Width 170 mm

Depth 205 mm

Net weight 2.5 kg maximum

Environment
climatic withstand Exposure to dry heat Bb tests conforming to EN/IEC 60068-2-2
Exposure to cold Ad tests conforming to EN/IEC 60068-2-1
Exposure to damp heat in service Db tests conforming to EN/IEC 60068-2-30
Exposure to damp heat in service Cab tests conforming to EN/IEC 60068-2-78

Mechanical robustness Vibrations (level: class II) conforming to IEC 60255-21-1


Vibrations: Fc conforming to IEC 60068-2-6
Shocks (level: class II) conforming to IEC 60255-21-2
Shocks: Ea conforming to IEC 60068-2-27
Seismic tests method A (level: class II) conforming to IEC 60255-21-3
Bumps (level: class II) conforming to IEC 60255-21-2
Bumps: Ea conforming to IEC 60068-2-27

Electromagnetic compatibility Emission tests conforming to IEC/EN 60255-26 ed. 3


Emission tests class A conforming to CISPR 11
Emission tests class A conforming to CISPR 22
EMC immunity conforming to IEC/EN 60255-26 ed. 3
EMC immunity conforming to EN/IEC 61000-4-18
EMC immunity level 4 conforming to EN/IEC 61000-4-2
EMC immunity level 3 conforming to EN/IEC 61000-4-3
EMC immunity level 4 conforming to EN/IEC 61000-4-4
EMC immunity level 3 conforming to EN/IEC 61000-4-5
EMC immunity level 3 conforming to EN/IEC 61000-4-6
EMC immunity conforming to EN/IEC 61000-4-8
EMC immunity level 5 conforming to EN/IEC 61000-4-9
EMC immunity conforming to EN/IEC 61000-4-29
EMC immunity conforming to EN/IEC 61000-4-11
EMC immunity conforming to EN/IEC 61000-4-17

Ambient air temperature for -40…65 °C


operation
IP degree of protection IP54 conforming to IEC 60529

maximum operating altitude 2000 m

Protective treatment Conformal coating

Relative humidity 0…95 %, without condensation

15-Feb-2025 3
Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 24.900 cm

Package 1 Width 27.000 cm

Package 1 Length 31.400 cm

Package 1 Weight 2.742 kg

Unit Type of Package 2 P12

Number of Units in Package 2 24

Package 2 Height 110.000 cm

Package 2 Width 80.000 cm

Package 2 Length 120.000 cm

Package 2 Weight 78.490 kg

Contractual warranty
Warranty Up to 10 years extended warranty (Standard warranty 2 years. Please check with
your local SE representative for extended warranty availability and conditions)

4 15-Feb-2025
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard No

Packaging without single use plastic No

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

15-Feb-2025 5
Product datasheet REL52034

Connections and Schema

Functional View

6 15-Feb-2025
Product datasheet REL52034

Dimensions Drawings

Base Unit Dimensions

A B

With screw connector 214 mm/8.43” 192 mm/7.6”

With ring-lug connector 226 mm/8.90” 204 mm/8.0”

15-Feb-2025 7