SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
CAFETERIA
CKT. NO. OF CIRCUIT
NO. DESCRIPTION OUTLET WATTS VOLTS AMPS BREAKER SIZE OF WIRE SIZE OF CONDUIT
FACULTY LOUNGE
1 LIGHTING OUTLET 12 1200 W 230 V 5.22 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 LIGHTING OUTLET 4 400 W 230 V 1.74 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 CONVENIENCE OUTLET 7 1260 W 230 V 5.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
4 CONVENIENCE OUTLET 6 1080 W 230 V 4.70 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2797.5
5 1 HP ACU OUTLET 3 W 230V 12.16 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
6 SPARE - - - - - - -
GENERAL CAFETERIA
1 LIGHTING OUTLET 21 2100 W 230 V 9.13 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
2 LIGHTING OUTLET 14 1400 W 230 V 6. 09 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 CONVENIENCE OUTLET 10 1800 W 230 V 7. 83 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
4 CONVENIENCE OUTLET 7 1260 W 230 V 5.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
REFRIGERATOR AND RANGE
5 OUTLET 10 1800 W 230 V 7.83 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
6 1 HP ACU OUTLET 4 3730 W 230 V 16.22 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
7 SPARE - - - - - - -
8 SPARE - - - - - - -
MAIN PANEL
1 FACULTY LOUNGE 32 6737 W 230 V 29.30 A 30A 5.5 mm² 20 mm Ø UPVC PIPE
2 GENERAL CAFETERIA 56 12090 W 230 V 52.58 A 60A 14 mm² 25mm Ø UPVC PIPE
3 SPARE - - - - - - -
4 SPARE - - - - - - -
COMPUTATION OF LOADS:
CIRCUIT 12 X 100 W = 1200 W CIRCUIT 21 X 2100 W = 500 W
1 1200/ 230 V = 5.22 A 1 500/ 230 V = 2.17 A
CIRCUIT 4 X 100 W = 400 W CIRCUIT 14 X 1400 W = 800 W
2 400/ 230 V = 1.74 A 2 800/ 230 V = 3.48 A
CIRCUIT 7 X 180 W = 1260 W CIRCUIT 10 X 180 W = 1800 W
3 3420/ 230 V = 5.48 A 3 1800/ 230 V = 7.83 A
CIRCUIT 6 X 180 W = 1080 W CIRCUIT 7 X 180 W = 1260 W
4 3420/ 230 V = 4.70 A 4 3420/ 230 V = 5.48 A
ACU (1HP): 746 X 3 = 2238 W
Increase by 25% (for conductor):
2238 x 0.25 = 560 W
CIRCUIT 2238 + 559.50 = 2797.5 W CIRCUIT 10 X 180 W = 1800 W
5 2797.5/ 230 V = 2.43 A 5 1800/ 230 V = 7.83 A
ACU (1HP): 746 X 4 = 2984 W
Increase by 25% (for conductor):
2238 x 0.25 = 746 W
CIRCUIT 2984 + 746 = 3730 W
6 3730/ 230 V = 16.22 A
SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
LABORATORIES BUILDING
NO. OF CIRCUIT
CKT. NO. DESCRIPTION OUTLET WATTS VOLTS AMPS BREAKER SIZE OF WIRE SIZE OF CONDUIT
COMPUTER LABORATORY
1 LIGHTING OUTLET 15 1500 W 230 V 6.52 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 CONVENIENCE OUTLET 19 3420 W 230 V 14.87 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
3 1 HP ACU OUTLET 2 1865 W 230 V 8.11 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
4 SPARE - - - - - - -
SCIENCE LABORATORY
1 LIGHTING OUTLET 15 1500 W 230 V 6.52 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 CONVENIENCE OUTLET 19 3420 W 230 V 14.87 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
3 1 HP ACU OUTLET 2 1865 W 230 V 8.11 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
4 SPARE - - - - - - -
ART & MUSIC ROOM
1 LIGHTING OUTLET 15 1500 W 230 V 6.52 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 CONVENIENCE OUTLET 4 720 W 230 V 3.13 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 1 HP ACU OUTLET 2 1865 W 230 V 8.11 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
4 SPARE - - - - - - -
MAIN PANEL
1 LIGHTING OUTLET 14 1400 W 230 V 6.09 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 LIGHTING OUTLET 14 1400 W 230 V 6.09 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 LIGHTING OUTLET 24 2400 W 230 V 10.43 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
4 CONVENIENCE OUTLET 7 1260 W 230 V 5.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
5 CONVENIENCE OUTLET 7 1260 W 230 V 5.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
6 COMPUTER LAB 36 6785 W 230 V 29.5 A 35 A 8.0 mm² THHN 32 mm Ø UPVC PIPE
7 SCIENCE LABORATORY 36 6785 W 230 V 29.5 A 35 A 8.0 mm² THHN 32 mm Ø UPVC PIPE
8 ARTMUSIC ROOM 21 4085 W 230 V 17.76 A 30 A 8.0 mm² THHN 32 mm Ø UPVC PIPE
9 SPARE - - - - - - -
10 SPARE - - - - - - -
COMPUTATION OF LOADS:
COMPUTER LABORATORY SCIENCE LABORATORY ART & MUSIC ROOM MAIN PANEL
CIRCUIT 15 X 100 W = 1500 W CIRCUIT 15 X 100 W = 1500 W CIRCUIT 15 X 100 W = 1500 W CIRCUIT 14 X 100 W = 1400 W
1 1500/ 230 V = 6.52 A 1 1500/ 230 V = 6.52 A 1 1500/ 230 V = 6.52 A 1 1400/ 230 V = 6.09 A
CIRCUIT 19 X 180 W = 3420 W CIRCUIT 19 X 180 W = 3420 W CIRCUIT 4 X 180 W = 720 W CIRCUIT 14 X 100 W = 1400 W
2 3420/ 230 V = 14.87 A 2 3420/ 230 V = 14.87 A 2 720/ 230 V = 3.13 A 2 1400/ 230 V = 6.09 A
ACU (1HP): 746 X 2 = 1492 W ACU (1HP): 746 X 2 = 1492 W "ACU (1HP): 746 X 2 = 1492 W
Increase by 25% (for conductor): Increase by 25% (for conductor): Increase by 25% (for conductor):
1492 x 0.25 = 373 W 1492 x 0.25 = 373 W 1492 x 0.25 = 373 W
CIRCUIT 1492 + 373= 1865 W CIRCUIT 1492 + 373= 1865 W CIRCUIT 1492 + 373= 1865 W CIRCUIT 24 X 100 W = 2400 W
3 1865/ 230 V = 8.11 A 3 1865/ 230 V = 8.11 A 3 1865/ 230 V = 8.11 A" 3 2400/ 230 V = 10.43 A
CIRCUIT 7 X 180 W = 1260 W
4 1260/ 230 V = 5.48 A
CIRCUIT 7 X 180 W = 1260 W
5 1260/ 230 V = 5.48 A
15+19+2= 36
CIRCUIT 1500 W+3420 W+1865 W=6785 W
7 6.52 A+14.87 A+8.11 A=29.5 A
15+19+2= 36
CIRCUIT 1500 +3420 +1865 = 6785 W
8 6.52 +14.87 +8.11 =29.5 A
15+4+2= 21
CIRCUIT 1500 +720 +1865 = 4085 W
9 6.52 +3.13 +8.11 = 17.76 A
SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
ACADEMIC BUILDING
NO. OF CIRCUIT
CKT. NO. DESCRIPTION OUTLET WATTS VOLTS AMPS BREAKER SIZE OF WIRE SIZE OF CONDUIT
1ST FLOOR ACADEMIC BUILDING
3.5 mm²
1 LIGHTING OUTLET 40 4000 W 230 V 17.39 A 20 A THHN 15 mm Ø UPVC PIPE
3.5 mm²
2 LIGHTING OUTLET 27 2700 W 230 V 11.74 A 15 A THHN 15 mm Ø UPVC PIPE
5.5 mm²
3 LIGHTING OUTLET 59 5900 W 230 V 25.65 A 30 A THHN 20 mm Ø UPVC PIPE
5.5 mm²
4 CONVENIENCE OUTLET 28 5040 W 230 V 21.91 A 30 A THHN 20 mm Ø UPVC PIPE
3.5 mm²
5 CONVENIENCE OUTLET 13 2340 W 230 V 10.17 A 15 A THHN 15 mm Ø UPVC PIPE
3.5 mm²
6 CONVENIENCE OUTLET 12 2160 W 230 V 9.39 A 15 A THHN 15 mm Ø UPVC PIPE
5.5 mm²
7 1 HP ACU OUTLET 8 7460 W 230 V 32.43 A 35 A THHN 20 mm Ø UPVC PIPE
8 SPARE - - - - - - -
2ND FLOOR ACADEMIC BUILDING
3.5 mm²
1 LIGHTING OUTLET 40 4000 W 230 V 17.39 A 20 A THHN 15 mm Ø UPVC PIPE
3.5 mm²
2 LIGHTING OUTLET 26 2600 W 230 V 11.30 A 15 A THHN 15 mm Ø UPVC PIPE
5.5 mm²
3 LIGHTING OUTLET 75 7500 W 230 V 32.61 A 35 A THHN 20 mm Ø UPVC PIPE
3.5 mm²
4 CONVENIENCE OUTLET 24 4320 W 230 V 18.78 A 20 A THHN 15 mm Ø UPVC PIPE
3.5 mm²
5 CONVENIENCE OUTLET 10 1800 W 230 V 7.83 A 15 A THHN 15 mm Ø UPVC PIPE
3.5 mm²
6 CONVENIENCE OUTLET 18 3240 W 230 V 14.09 A 20 A THHN 15 mm Ø UPVC PIPE
5.5 mm²
7 1 HP ACU OUTLET 8 7460 W 230 V 32.43 A 35 A THHN 20 mm Ø UPVC PIPE
8 SPARE - - - - - - -
ROOF TOP
3.5 mm²
1 LIGHTING OUTLET 20 2000 W 230 V 8.70 A 15 A THHN 15 mm Ø UPVC PIPE
2.0 mm²
2 CONVENIENCE OUTLET 4 720 W 230 V 3.13 A 10 A THHN 13 mm Ø UPVC PIPE
MAIN PANEL
1ST FLOOR ACADEMIC 38 mm²
1 BUILDING 187 29600 W 230 V 128.68 A 150A THHN 32 mm Ø UPVC PIPE
2ND FLOOR ACADEMIC 50 mm²
2 BUILDING 193 30920 W 230 V 201 A 150A THHN 38 mm Ø UPVC PIPE
3.5 mm²
3 ROOF TOP 24 2720 230 V 11.83 A 15A THHN 20 MM Ø UPVC PIPE
4 SPARE - - - - - - -
COMPUTATION OF LOADS:
1ST FLOOR ACADEMIC BUILDING 2ND FLOOR ACADEMIC BUILDING ROOF TOP
CIRCUIT 40 X 100 W = 4000 W CIRCUIT 40 X 100 W = 4000 W CIRCUIT 20 X 100 W = 2000 W
1 4000/ 230 V = 17.39 A 1 4000/ 230 V = 17.39 A 1 2000/ 230 V = 8.70 A
CIRCUIT 27 X 100 W = 2700 W CIRCUIT 26 X 100 W = 2600 W CIRCUIT 4 X 180 W = 720 W
2 2700/ 230 V = 11.74 A 2 2600/ 230 V = 11.30 A 2 720/ 230 V = 3.13 A
CIRCUIT 59 X 100 W = 5900 W CIRCUIT 75 X 100 W = 7500 W
3 5900/ 230 V = 25.65 A 3 7500/ 230 V = 32.61 A
CIRCUIT 28 X 180 W = 5040 W CIRCUIT 24 X 180 W = 4320 W
4 3420/ 230 V = 5.48 A 4 4320/ 230 V = 18.78 A
CIRCUIT 13 X 180 W = 2340 W CIRCUIT 10 X 180 W = 1800 W
5 3420/ 230 V = 4.70 A 5 1800/ 230 V = 7.83 A
CIRCUIT 12 X 180 W = 2160 W CIRCUIT 18 X 180 W = 3240 W
6 3420/ 230 V = 4.70 A 6 3240/ 230 V = 14.09 A
ACU (1HP): 746 X 8 =5968 W ACU (1HP): 746 X 8 =5968 W
Increase by 25% (for conductor): Increase by 25% (for conductor):
2238 x 0.25 = 1492 W 2238 x 0.25 = 1492 W
CIRCUIT 5968 + 1492 = 7460 W CIRCUIT 5968 + 1492 = 7460 W
7 7460/ 230 V = 32.43 A 7 7460/ 230 V = 32.43 A
SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
ADMINISTRATIVE BUILDING
NO. OF CIRCUIT
CKT. NO. DESCRIPTION OUTLETS WATTS VOLTS AMPS BREAKER SIZE OF WIRE SIZE OF CONDUIT
ADMINISTRATIVE AREAS (1ST FLR)
1 LIGHTING OUTLET 2 200 W 230V 0.87 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 LIGHTING OUTLET 5 500 W 230V 2.17 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 LIGHTING OUTLET 16 1600 W 230V 6.96 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
4 LIGHTING OUTLET 2 200 W 230V 0.87 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
5 CONVENIENCE OUTLET 7 1260 W 230V 5.47 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
6 CONVENIENCE OUTLET 10 1800 W 230V 7.83 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
7 1 HP ACU OUTLET 3 2797.5 W 230V 12.16 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
8 REFRIGERATOR 1 180 W 230V 0.78 A 15A 2.0 mm² THHN 15 mm Ø UPVC PIPE
9 RANGE OUTLET 1 8000 W 230V 27.83 A 30A 8.0 mm² THHN 32 mm Ø UPVC PIPE
10 SPARE - - - - - - -
ADMINISTRATIVE AREAS (2ND FLR)
1 LIGHTING OUTLET 5 500 W 230 V 2.17 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
2 LIGHTING OUTLET 8 800 W 230 V 3.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 LIGHTING OUTLET 5 500 W 230 V 2.17 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
4 LIGHTING OUTLET 8 800 W 230 V 3.48 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
5 LIGHTING OUTLET 9 900 W 230 V 3.91 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
6 CONVENIENCE OUTLET 16 2880 W 230 V 12.52 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
7 CONVENIENCE OUTLET 5 900 W 230 V 3.91 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
8 1 HP ACU OUTLET 5 4662.50 W 230 V 20.27 A 30 A 5.5 mm² THHN 20 mm Ø UPVC PIPE
9 SPARE - - - - - - -
10 SPARE - - - - - - -
CLINIC AREA (1ST FLR)
1 LIGHTING OUTLET 23 2300 W 230 V 10 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
2 LIGHTING OUTLET 7 700 W 230 V 3.04 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 LIGHTING OUTLET 7 700 W 230 V 3.04 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
4 LIGHTING OUTLET 33 3300 W 230 V 14.35 A 20 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
5 CONVENIENCE OUTLET 13 2340 W 230 V 10.17 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
6 CONVENIENCE OUTLET 4 720 W 230 V 3.13 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
7 CONVENIENCE OUTLET 5 900 W 230 V 3.91 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
8 1 HP ACU OUTLET 2 1865 W 230 V 8.11 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
9 SPARE - - - - - - -
10 SPARE - - - - - - -
LIBRARY AREA (2ND FLR)
1 LIGHTING OUTLET 18 1800 W 230 V 7.83 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
2 LIGHTING OUTLET 6 600 W 230 V 2.61 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
3 LIGHTING OUTLET 4 400 W 230 V 1.74 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
4 CONVENIENCE OUTLET 10 1800 W 230 V 7.83 A 15 A 3.5 mm² THHN 15 mm Ø UPVC PIPE
5 CONVENIENCE OUTLET 5 900 W 230 V 3.91 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
6 1 HP ACU OUTLET 1 932.5 W 230 V 4.05 A 10 A 2.0 mm² THHN 13 mm Ø UPVC PIPE
7 SPARE - - - - - - -
8 SPARE - - - - - - -
MAIN PANEL
165557.5
1 ADMIN AREA (1ST FLR) 42 W 230 V 64.94 A 70 A 22 mm² THHN 32 mm Ø UPVC PIPE
2 ADMINAREA (2NDFLR) 61 11943.5 W 230 V 51.91 A 60 A 14 mm² THHN 25 mm Ø UPVC PIPE
3 CLINIC AREA (1ST FLR) 94 12825 W 230 V 55.75 A 60 A 14 mm² THHN 25 mm Ø UPVC PIPE
4 LIBRARY AREA (2ND FLR) 44 6432.5 W 230 V 27.97 A 30 A 5.5 mm² THHN 20 mm Ø UPVC PIPE
5 SPARE - - - - - - -
6 SPARE - - - - - - -
COMPUTATION OF LOADS:
ADMINISTRATIVE AREAS (2ND
ADMINISTRATIVE AREAS (1ST FLR) FLR) CLINIC AREA (1ST FLR) LIBRARY AREA (2ND FLR)
CIRCUIT 2 X 100 W = 200 W CIRCUIT 5 X 100 W = 500 W CIRCUIT 23 X 100 W = 2300 W CIRCUIT 18 X 100 W = 1800 W
1 200/ 230 V = 0.87 A 1 500/ 230 V = 2.17 A 1 2300/ 230 V = 10 A 1 1800/ 230 V = 7.83 A
CIRCUIT 5 X 100 W = 500 W CIRCUIT 8 X 100 W = 800 W CIRCUIT 7 X 100 W = 700 W CIRCUIT 6 X 100 W = 600 W
2 500/ 230 V = 2.17 A 2 800/ 230 V = 3.48 A 2 700/ 230 V = 3.04 A 2 600/ 230 V = 2.61 A
CIRCUIT 16 X 100 W = 1600 W CIRCUIT 5 X 100 W = 500 W CIRCUIT 7 X 100 W = 700 W CIRCUIT 4 X 100 W = 400 W
3 1600/ 230 V = 6.96 A 3 500/ 230 V = 2.17 A 3 700/ 230 V = 3.04 A 3 400/ 230 V = 1.74 A
CIRCUIT 2 X 100 W = 200 W CIRCUIT 8 X 100 W = 800 W CIRCUIT 33 X 100 W = 3300 W CIRCUIT 10 X 180 W = 1800 W
4 200/ 230 V = 0.87 A 4 800/ 230 V = 3.48 A 4 3300/ 230 V = 14.35 A 4 1800/ 230 V = 7.83 A
CIRCUIT 7 X 180 W = 1260 W CIRCUIT 9 X 100 W = 900 W CIRCUIT 13 X 180 W = 2340 W CIRCUIT 5 X 180 W = 900 W
5 1260/ 230 V = 5.47 A 5 900/ 230 V = 3.91 A 5 2340/ 230 V = 10.17 A 5 900/ 230 V = 3.91 A
ACU (1HP): 746 X 1 = 746
W
Increase by 25% (for
conductor): 746 x 0.25 =
16 X 180 W = 2880 W 185.5 W
CIRCUIT 10 X 180 W = 1800 W CIRCUIT 2880/ 230 V = 12.52 CIRCUIT 4 X 180 W = 720 W CIRCUIT 746 + 186.5 = 932.5 W
6 1800/ 230 V = 7.83 A 6 A 6 720/ 230 V = 3.13 A 6 932.5/ 230 V = 4.05 A
ACU (1HP): 746 X 3 =
2238 W
Increase by 25% (for
conductor): 2238 x 0.25
= 560 W
2238 + 559.50 = 2797.5
CIRCUIT W CIRCUIT 5 X 180 W = 900 W CIRCUIT 5 X 180 W = 900 W
7 2797.5/ 230 V = 2.43 A 7 900/ 230 V = 3.91 A 7 900/ 230 V = 3.91 A
ACU (1HP): 746 X 5 =
3730 W
Increase by 25% (for ACU (1HP): 746 X 2 =
conductor): 3730 x 1492 W
0.25 = 932.50 W Increase by 25% (for
3730 + 932.50= conductor): 1492 x
4662.50 W 0.25 = 373 W
CIRCUIT 1 X 180 W = 180 W 4662.50/ 230 V = CIRCUIT 1492 + 373= 1865 W
8 180/ 230 V = 0.78 A 20.27 A 8 1865/ 230 V = 8.11 A
Range Power: 8000 W
Apply Demand Factor
(80%):
Effective Power = 8000
CIRCUIT x 0.80 = 6400 W
9 6400/ 230 = 27. 83 A