Ingeteam - Ingecon-Sun-Storage-3power-Hv-C-Series-En-Rev-A4

The INGECON® SUN STORAGE 3Power HV C Series is a three-phase transformerless battery inverter capable of delivering up to 3.93 MVA at 1,500 V, featuring high power density and advanced thermal stability. It utilizes a liquid cooling system for enhanced performance and includes various protections and functionalities for grid support and renewable resource integration. The inverter is designed for both grid-connected and stand-alone systems, with a range of input and output specifications tailored for efficient energy management.

Uploaded by

Prajwal Thorat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
757 views5 pages

Ingeteam - Ingecon-Sun-Storage-3power-Hv-C-Series-En-Rev-A4

The INGECON® SUN STORAGE 3Power HV C Series is a three-phase transformerless battery inverter capable of delivering up to 3.93 MVA at 1,500 V, featuring high power density and advanced thermal stability. It utilizes a liquid cooling system for enhanced performance and includes various protections and functionalities for grid support and renewable resource integration. The inverter is designed for both grid-connected and stand-alone systems, with a range of input and output specifications tailored for efficient energy management.

Uploaded by

Prajwal Thorat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

SUN STORAGE 3Power HV C Series

1,500 Vdc
Specifications included in this datasheet could change without notice. Please contact Ingeteam’s sales department in case of any queries.

UP TO 3.93 MVA AT 1,500 V

THREE-PHASE TRANSFORMERLESS BATTERY INVERTER WITH AN EXTRA THERMAL


STABILITY AND A GREATER POWER DENSITY
The INGECON® SUN STORAGE 3Power HV C Series is a three-phase bidirectional battery inverter that can be used in
grid-connected and stand-alone systems. This one-of-a-kind battery inverter achieves a market-leading power density of
499 kW/m3, as it provides up to 3,928 kVA in just one power stack.
Latest generation electronics
The INGECON® SUN STORAGE 3Power HV C Series battery inverter features an innovative control unit that performs a more
INGECON SUN STORAGE 3Power-HV_C-Series_EN_Rev_A4

efficient and sophisticated inverter control, as it uses a last-generation digital signal processor.
Liquid Cooling System (LCS)
Ingeteam has already supplied +54 GW of liquid -cooled wind power converters worldwide. It offers a greater thermal stability
and a more optimized component usage. The LCS has been designed to refrigerate the IGBTs, the power phases and the IP65
compartment. It features less moving components, so it consumes a lower amount of power and it requires less maintenance
works.
The LCS is a closed circuit supplied totally filled and purged, equipped with fast connectors with an anti-dripping system, so it
offers zero risk of particle entrance. It has been designed to avoid siphons in order to easily purge it if necessary. The coolant
used is a biodegradable glycol water mixture. There is no need of emptying the LCS in order to replace the phases, nor the
sensors.
IP65 protection
A secondary liquid cooling system is used to refrigerate the air inside the IP65-protected compartment. A water-air heat
exchanger is used for that. This compartment contains the power and control electronics, the DC fuses, the DC and AC
protections, the busbars and the power phases.
SUN STORAGE 3Power HV C Series
1,500 Vdc

UP TO 3.93 MVA AT 1,500 V


Three-phase transformerless battery inverter with an extra thermal
stability and a greater power density
Power converter stands both, grid-following and grid forming operating modes:

Real power related functionalities Investment deferral: Safety and quality:


Renewable resources integration: - Peak shaving. - “Un-interruptible” Power.
- Ramp limits. - Load shifting / Load following. - Grid code compliance.
- Power smoothing / firming / - Real power response improvement of - Transmission congestion relief / Power
curtailment. conventional power plants. quality-reliability.
- Time shifting. Power efficiency: Reactive power related functionalities
- Micro grids. - Time shifting.
- Voltage control (Q/V).
Grid support / Ancillary services: - Price arbitrage.
- Voltage control / protection.
- Frequency regulation. - Real power response improvement of
- Fixed power factor (QPF).
- Synthetic inertia. conventional power plants.
- Fixed reactive power output (Qref).
- Black start. - Peak shaving.
- Limitation of response of Reactive Power.
- Frequency control / protection.
- Virtual “Synchronous Machine”. Standard 5 year warranty, extendable
upon request.

Protections Optional Accessories Liquid cooling system


- Short-circuits and overloads at the - Heating kit, for operating at an ambient - LCS to refrigerate the IGBTs.
output. temperature of down to -30 ºC. - More optimized component usage:
- Anti-islanding with automatic - DC surge arresters type I+II. greater thermal stability.
disconnection. - AC surge arresters type I+II. - Less moving components: lower power
- Insulation failure DC. - DC fuses. consumption and less maintenance
- Up to 24 pairs of fuse-holders. - Monitoring of the DC currents. works.
- Lightning induced DC and AC surge - Grounding kit. - No risk of particle entrance.
arresters, type II. - Anti-corrosion protection with stainless
- Motorized DC switch. steel components
Specifications included in this datasheet could change without notice. Please contact Ingeteam’s sales department in case of any queries.

- Motorized AC circuit breaker. - LCS is used in many industries. Thus,


- Hardware protection via firmware. it is very reliable, as its components are
- Additional protection for the power stack, subject to many validation tests.
liquid cooled, IP65 rated and air cooled - Fast connectors with anti-dripping
by a closed loop. system.
- Biodegradable glycol water mixture.
- No need of emptying the LCS in order to
replace the phases, nor the sensors.

INGECON® SUN STORAGE 3930TL

+24
...

Optional
+3
+2
DC-Pre-charge

+1 AC output for
AC-Pre-charge

L1
Filter

L2 connection to
-1 L3 a MV network
INGECON SUN STORAGE 3Power-HV_C-Series_EN_Rev_A4

-2 Inverter
-3 M M

...
-24
Optional

Size and weight (mm and kg)


2,800 kg
2,215

3,50
0
50
1,0

www.ingeteam.com
SUN STORAGE 3Power HV C Series
1,500 Vdc

INGECON® SUN STORAGE 3930TL HV

C600 C615 C630 C645 C660 C675


INPUT (DC)
Battery voltage range for off-grid mode 854 - 1,500 V 873 - 1,500 V 895 - 1,500 V 917 - 1,500 V 938 - 1,500 V 958 - 1,500 V
Battery voltage for grid-tied mode(1) 938 - 1,500 V 960 - 1,500 V 985 - 1,500 V 1,006 - 1,500 V 1,029 - 1,500 V 1,052 - 1,500 V
Maximum voltage 1,500 V
Maximum current 3,357 A
Nº inputs with fuse-holders Up to 24
Fuse dimensions Up to 630 A / 1,500 V / aR (optional)
DC short circuit withstand
250 kA, ≤5 ms / 825 MA²s
capacity per DC input
Type of connection Connection to copper bars
Power blocks 1

INPUT PROTECTIONS
Overvoltage protections Type II surge arresters (type I+II optional)
DC switch Motorized DC load break disconnect
Other protections Up to 24 pairs of DC fuses (optional) / Reverse polarity / Insulation failure monitoring / Anti-islanding protection

OUTPUT (AC)
Discharge power @1,500 Vdc 2,806 kVA / 2,876 kVA / 2,946 kVA / 3,016 kVA / 3,087 kVA / 3,157 kVA /
(30 ºC / 50 ºC) 2,265 kVA 2,322 kVA 2,379 kVA 2,435 kVA 2,492 kVA 2,549 kVA
Discharge current @1,500 Vdc
2,700 A / 2,180 A
(30 ºC / 50 ºC)
Charge power @1,500 Vdc 2,666 kVA / 2,732 kVA / 2,799 kVA / 2,866 kVA / 2,932 kVA / 2,999 kVA /
(30 ºC / 50 ºC) 2,152 kVA 2,206 kVA 2,260 kVA 2,314 kVA 2,368 kVA 2,421 kVA
Charge current @1,500 Vdc
2,565 A / 2,071 A
(30 ºC / 50 ºC)
Rated voltage (2)
600 V IT System 615 V IT System 630 V IT System 645 V IT System 660 V IT System 675 V IT System
Frequency 50 / 60 Hz
Power Factor(3) 1
Power Factor adjustable Yes, 0 - 1 (leading / lagging)
Specifications included in this datasheet could change without notice. Please contact Ingeteam’s sales department in case of any queries.

THD (Total Harmonic Distortion)(4) <3%

OUTPUT PROTECTIONS
Overvoltage protections Type II surge arresters (type I+II optional)
AC breaker Motorized AC circuit breaker
Anti-islanding protection Yes, with automatic disconnection
Other protections AC short-circuits and overloads

FEATURES
Operating efficiency 98.9%
CEC 98.5%
Max. consumption aux. services 7,600 W
Stand-by or night consumption(5) 185 W
Average power consumption per day 2,500 W

GENERAL INFORMATION
Ambient temperature -20 ºC to +60 ºC
Relative humidity (non-condensing) 0-100% (Outdoor)
Protection class IP65(6)
INGECON SUN STORAGE 3Power-HV_C-Series_EN_Rev_A4

Corrosion protection External corrosion protection


Maximum altitude 4,500 m (for installations beyond 1,000 m, please contact Ingeteam’s BESS sales department)
Cooling system Liquid cooling system and forced air cooling system with temperature control (400V 3 phase + neutral power supply, 50/60 Hz)
Air flow range 0 - 18,000 m3/h
Average air flow 12,000 m3/h
Acoustic emission (100% / 50% load) <57 dB(A) at 10m / <49.7 dB(A) at 10m
Marking CE
IEC 62920, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-4, IEC 61000-3-11, IEC 61000-3-12, IEC 62109-1, IEC 62109-2,
EMC and security standards
EN 50178, FCC Part 15, AS3100
Grid connection standards IEC 62116, EN 50530, IEC 61683, EU 631/2016 (EN 50549-2, CEI 0-16, NTS Spain, VDE-AR-N 4120, VDE-AR-N 4110,
Arrêté du 9 juin 2020, Terna A68), G99, South African Grid Code, Mexican Grid code, Chilean Grid Code, Ecuadorian Grid
Code, Peruvian Grid Code, IEC61727, ABNT NBR 16149, ABNT NBR 16150, IEEE 1547, IEEE1547.1, DEWA (Dubai), Abu
Dhabi Grid Code, Jordan Grid Code, Egyptian Grid Code, Saudi Arabia Grid Code, RETIE Colombia, Australian Grid Code

Notes
(1) Minimum voltage DC (VDC, min) for Vgrid,max = 1.1 p.u. and Power Factor=1. If Vgrid,max is higher than this value, the minimum voltage should be corrected as VDC, min * Vgrid,max
/ 1.1. For other DC voltage ranges, please contact Ingeteam’s BESS sales department
(2) Other AC voltages and powers available upon request
(3) For Pout>25% of the rated power
(4) For Pout>25% of the rated power and voltage in accordance with IEC 61000-3-4
(5) Consumption from Battery
(6) Except for the LC filter and the air-water heat exchanger, that are IP54.

www.ingeteam.com
SUN STORAGE 3Power HV C Series
1,500 Vdc

INGECON® SUN STORAGE 3930TL HV

C690 C715 C730 C745 C800 C840


INPUT (DC)
Battery voltage range for off-grid mode 979 - 1,500 V 1,014 - 1,500 V 1,035 - 1,500 V 1,056 - 1,500 V 1,132 - 1,500 V 1,188 - 1,500 V
Battery voltage for grid-tied mode(1) 1,075 - 1,500 V 1,113 - 1,500 V 1,136 - 1,500 V 1,159 - 1,500 V 1,244 - 1,500 V 1,305 - 1,500 V
Maximum voltage 1,500 V
Maximum current 3,357 A
Nº inputs with fuse-holders Up to 24
Fuse dimensions Up to 630 A / 1,500 V / aR / 100 kA (L/R=5mS) (optional)
Type of connection Connection to copper bars
Power blocks 1

INPUT PROTECTIONS
Overvoltage protections Type II surge arresters (type I+II optional)
DC switch Motorized DC load break disconnect
Other protections Up to 24 pairs of DC fuses (optional) / Reverse polarity / Insulation failure monitoring / Anti-islanding protection

OUTPUT (AC)
Discharge power @1,500 Vdc 3,227 kVA / 3,344 kVA / 3,414 kVA / 3,484 kVA / 3,741 kVA / 3,928 kVA /
(30 ºC / 50 ºC) 2,605 kVA 2,700 kVA 2,756 kVA 2,813 kVA 3,021 kVA 3,172 kVA
Discharge current @1,500 Vdc
2,700 A / 2,180 A
(30 ºC / 50 ºC)
Charge power @1,500 Vdc 3,066 kVA / 3,177 kVA / 3,243 kVA / 3,310 kVA / 3,554 kVA / 3,732 kVA /
(30 ºC / 50 ºC) 2,475 kVA 2,565 kVA 2,618 kVA 2,672 kVA 2,870 kVA 3,013 kVA
Charge current @1,500 Vdc
2,565 A / 2,071 A
(30 ºC / 50 ºC)
Rated voltage (2)
690 V IT System 715 V IT System 730 V IT System 745 V IT System 800 V IT System 840 V IT System
Frequency 50 / 60 Hz
Power Factor(3) 1
Power Factor adjustable Yes, 0 - 1 (leading / lagging)
THD (Total Harmonic Distortion)(4) <3%

OUTPUT PROTECTIONS
Specifications included in this datasheet could change without notice. Please contact Ingeteam’s sales department in case of any queries.

Overvoltage protections Type II surge arresters (type I+II optional)


AC breaker Motorized AC circuit breaker
Anti-islanding protection Yes, with automatic disconnection
Other protections AC short-circuits and overloads

FEATURES
Operating efficiency 98.9%
CEC 98.5%
Max. consumption aux. services 7,600 W
Stand-by or night consumption(5) 185 W
Average power consumption per day 2,500 W

GENERAL INFORMATION
Ambient temperature -20 ºC to +60 ºC
Relative humidity (non-condensing) 0-100% (Outdoor)
Protection class IP65(6)
Corrosion protection External corrosion protection
Maximum altitude 4,500 m (for installations beyond 1,000 m, please contact Ingeteam’s BESS sales department)
INGECON SUN STORAGE 3Power-HV_C-Series_EN_Rev_A4

Cooling system Liquid cooling system and forced air cooling system with temperature control (400V 3 phase + neutral power supply, 50/60 Hz)
Air flow range 0 - 18,000 m3/h
Average air flow 12,000 m3/h
Acoustic emission (100% / 50% load) <57 dB(A) at 10m / <49.7 dB(A) at 10m
Marking CE
IEC 62920, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-4, IEC 61000-3-11, IEC 61000-3-12, IEC 62109-1, IEC 62109-2,
EMC and security standards
EN 50178, FCC Part 15, AS3100
Grid connection standards IEC 62116, EN 50530, IEC 61683, EU 631/2016 (EN 50549-2, CEI 0-16, NTS Spain, VDE-AR-N 4120, VDE-AR-N 4110,
Arrêté du 9 juin 2020, Terna A68), G99, South African Grid Code, Mexican Grid code, Chilean Grid Code, Ecuadorian Grid
Code, Peruvian Grid Code, IEC61727, ABNT NBR 16149, ABNT NBR 16150, IEEE 1547, IEEE1547.1, DEWA (Dubai), Abu
Dhabi Grid Code, Jordan Grid Code, Egyptian Grid Code, Saudi Arabia Grid Code, RETIE Colombia, Australian Grid Code

Notes
(1) Minimum voltage DC (VDC, min) for Vgrid,max = 1.1 p.u. and Power Factor=1. If Vgrid,max is higher than this value, the minimum voltage should be corrected as VDC, min * Vgrid,max
/ 1.1. For other DC voltage ranges, please contact Ingeteam’s BESS sales department
(2) Other AC voltages and powers available upon request
(3) For Pout>25% of the rated power
(4) For Pout>25% of the rated power and voltage in accordance with IEC 61000-3-4
(5) Consumption from Battery
(6) Except for the LC filter and the air-water heat exchanger, that are IP54.

www.ingeteam.com
EUROPE Ingeteam LTD. ASIA
Unit 10 Gordano 19, Garanor Way, Portbury
Ingeteam Power Technology, S.A. Bristol, BS20 TXE - United Kingdom Ingeteam Power Technology Shanghai, Co. Ltd.
Avda. Ciudad de la Innovación, 13 Tel.: +44 (0) 331 630 0305 Room 2606-F, No.360 South Pudong Road
31621 Sarriguren (Navarra) - Spain China (Shanghai) pilot free trade zone
Tel.: +34 948 288 000 NORTH AMERICA C.P 200120
Fax: +34 948 288 001 Tel.: +86 139 1622 4886
e-mail: [email protected] Ingeteam Inc. e-mail: [email protected]
3550 W. Canal St.
Ingeteam S.r.l. Milwaukee, WI 53208 - USA Ingeteam India Pvt. Ltd.
Via Emilia Ponente, 232 Tel.: +1 (414) 934 4100 / +1 (855) 821 7190 Survey No. 111/1-111/3 & 111/5-111/7,
48014 Castel Bolognese (RA) - Italy Fax: +1 (414) 342 0736 Village No.155, Mambakkam Village,
Tel.: +39 0546 651 490 e-mail: [email protected] Chennai - Bangalore Main Road,
Fax: +39 054 665 5391 Sriperumbudur Taluk,
e-mail: [email protected] Ingeteam Power Technology México S de RL de CV Kancheepuram District - 602106,
Av. Ejército Nacional Mexicano 351, Tamilnadu, India
Ingeteam SAS Chapultepec Morales, Granada,
140 Rue Carmin - Le Naurouze B Miguel Hidalgo, Ingeteam Power Technology S.A. UAE Branch
31670 Labège - France CP: 11520 Al Bateen tower c6 Bainunah 1st floor
Tel.: +33 (0)5 61 25 00 00 Ciudad de México, CDMX Street 34
Fax: +33 (0)5 61 25 00 11 Tel.: (+52) 55 6586 9930 Abu Dhabi - UAE
e-mail: [email protected] e-mail: [email protected] Tel.: +971 2 207 6666

Ingeteam, a.s. Ingeteam Power Technology S.A.


Technologická 371/1 SOUTH AMERICA Thailand representative office
70800 Ostrava - Pustkovec 100/67 Vongvanij B Building, 22nd floor,
Ingeteam Ltda. Rama IX Road., HuayKwang,
Czech Republic Rua Estácio de Sá, 560
Tel.: +420 59 747 6800 10320 Bangkok
Santa Genebra Te.: +66 22461798
Fax: +420 59 732 6899 Campinas - SP
e-mail: [email protected] e-mail: [email protected]
CEP: 13080-010; São Paulo - Brazil
Ingeteam GmbH Tel.: (+55) 19 30 37 37 73
Grand Bateau – Zollhof 6 e-mail: [email protected] AUSTRALIA
D-40221 – Düsseldorf, Germany Ingeteam Chile SpA Ingeteam Australia Pty Ltd.
Tel.: +49 (0) 211 78177950 Balmoral n.º 309, Piso 10º, Oficina 1008, Iaccelerate Centre, Building 239
e-mail: [email protected] 7561282 Las Condes Innovation Campus, Squires Way
Santiago, Chile North Wollongong, NSW 2500 - Australia
Ingeteam Poland Spzoo Tel.: +61 429 111 190
Ul. Koszykowa 60/62 m 39 Tel.: (+56) 229 253 825
e-mail: [email protected] e-mail: [email protected]
00-673, Warsaw, Poland
Tel.: (+48) 22 821 99 30
e-mail: [email protected]

www.ingeteam.com

You might also like