The document provides detailed specifications for a 5.0 MVA inverter duty transformer, including its ratings, installation requirements, insulation withstand capabilities, and optional fittings. It outlines technical data such as voltage levels, cooling type, and earthing details, as well as standards for manufacturing and loading. Essential spare parts and evaluation criteria for bids are also included.

Uploaded by

MOHAMED ANIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
386 views7 pages

5000KVA - 800 - 800V - 11KV Inverter Duty Transfomer - 3 Winding - Dy11y11 - OLTC - ONAN

The document provides detailed specifications for a 5.0 MVA inverter duty transformer, including its ratings, installation requirements, insulation withstand capabilities, and optional fittings. It outlines technical data such as voltage levels, cooling type, and earthing details, as well as standards for manufacturing and loading. Essential spare parts and evaluation criteria for bids are also included.

Uploaded by

MOHAMED ANIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

DOCUMENT No. 5.

0 MVA INVERTER DUTY TRANSFORMER


PAGE : 1 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA
1.1 3 Winding Inverter
GENERAL Application/ Designation
Duty Transformer
1.2 Quantity Required Nos. 01
Indoor /
1.3 Installation Outdoor
Outdoor
1.0

1.4 Degree of protection as per IEC 60529 IP55


2.1 Rating kVA 5000
2.2 Number of phases & frequency 3Φ, 50Hz
2.3 Number of windings 3
2.4 Type of cooling ONAN
HV kV 11.00
2.5 No load voltage
LV kV 0.800 / 0.800

HV ∆
2.6 Winding Connection
LV Y/Y
2.7 Vector group Dy11y11
RATINGS

2.8 Percentage impedance % 6.50% (± IS Tol.)

Maximum flux density at rated condition at


2.9
2.0

principal tap

Maximum current density at Principal tap


2.10 3.50 A/mm2

HV to LV
LV to HV
2.11 Direction of Power Flow Yes
Bi
directional

HV Uniformly/ Uniformly
Winding Insulation Non
2.12
Category uniformly
LV Insulated Uniformly

2.13 HV kV 11.00
VOLTAGE
SYSTEM

Nominal System
Voltage
LV1 / LV2 kV 0.800 / 0.800

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 2 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA

HV kV 12.00
Highest System
2.14
Voltage
LV1 / LV2 kV 0.920 / 0.920

HV kA
2.15 System Fault Level
LV kA

HV
3.1 System Neutral
EARTHING
NEUTRAL

LV
3.0

HV NA
3.2 Transformer Neutral
LV NA

Impulse (1.2/50  sec HV kVp 75


4.1
wave)
INSULATION WITHSTAND

LV kVp NA

Power Frequency HV kV 28
Withstand Voltage DRY LV kV 3
4.2
Power Frequency HV kV 28
4.0

Withstand Voltage
WET LV kV 3

Transformer Neutral HV kV NA
4.3 power frequency
withstand voltage LV kV 3

5.1 Reference Ambient Temperature OC 50


TEMPERA
TURE
RISE

5.2 Oil by thermometer over the ambient OC 50/ As per IS 2026-2


5.0

5.3 Winding by resistance over the ambient OC 55/ As per IS 2026-2


6.1 Taps required: On load / off circuit Off Circuit (OCTC)
6.2 Tapping on windings HV
TAP CHANIGING

6.3 Total tapping range % +5 to -5


6.4 Tapping Steps % 2.5
Manual / Automatic Manual
6.5 Control
Local / Remote Local
6.0

6.6 Control cubicle by


By Bidder
6.7 Voltage class of OCTC kV

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 3 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA
6.8 Current rating of OCTC A
In tank

Type of OCTC Separately


6.9
installation mounted

7.1 Manufacturer’s name


DETAILS OF TRAFO. FOR

7.2 Rating kVA

7.3 Exact turns ratio


PARALLEL

7.4 Tapping range NA


7.0

7.5 Full load loss corrected to 75OC kW

7.6 % impedance at principal tapping %

7.7 Vector group

HV Line end kV 12

LV Line end kV 3
8.1 Voltage class
HV neutral kV NA

LV neutral kV 3
Impulse wave HV kVp 75
8.2 withstand (1.2/50 
sec wave) LV kVp NA
BUSHINGS

HV Line end kV 28

Power frequency LV Line end kV 3


8.3
withstand for 1 Min. HV neutral kV NA
8.0

LV neutral kV 3

HV phase to phase mm 110

LV phase to phase mm 25
8.4 Minimum clearance
HV phase to earth mm 110

LV phase to earth mm 25
8.5 Minimum creepage HV Line end mm 300

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 4 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA
distance (total LV Line end mm 25
protected)
HV neutral mm NA

LV neutral mm 25

HV phase Nos. NA
Bushings Parameters NA
HV Neutral NA
8.6 Bushing CT details bushing.

LV Phase Nos.
Bushings Parameters
LV Neutral bushing NA
Cable box with
HV line end bushing/Cable Box/Cable Box
9.1 disconnecting
with disconnecting chamber.
chamber
Cable box with
LV line end bushing/Cable Box/Cable Box
9.2 disconnecting
with disconnecting chamber/Bus duct.
chamber
HV neutral bushing/ Cable box/ Cable box NA
9.3
with disconnecting chamber
TERMINAL CONNECTIONS

LV neutral bushing/ Cable box/ Cable box


9.4 NA
with disconnecting chamber/ Bus duct.

Required Yes/No
9.5 Bushing terminals Size of take off HV NA
conductor LV
Required Yes/No Yes
HV 1Rx3Cx300Sq.mm
9.0

XLPE 11kV grade


(E) Armoured Al.
Bus Duct, Cable box, Cable.
9.6
lugs and glands Size of cable HV Neutral -
LV 8Rx1Cx300Sq.mm /
Phase, XLPE 3.3kV
grade Armoured Al.
Cable
10.0
EARTHING 10.1 Material of conductor Copper

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 5 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA
TERMINAL

10.2 Size of conductor mm 50x8

Plain/ flanged Plain


11.1 Wheels Unidirectional/ bi-
Bi-directional
MISCELLANEOUS

directional
Vacuum withstand capability of Main tank with
11.2 760mm of HG
bushings, radiators, fittings & accessories
Filled with oil Yes/No Yes
Without oil with Yes/No
Transformer to be inertgas,
11.0

11.3 Gas
transported Cylinder and NA
accessories,
pressure gauge
11.4 Maximum Sound Level dBA 65
Magnetic oil level gauge with low oil level
12.1 Yes/No Yes
alarm contacts

12.2 Pressure relief device Yes/No Yes


OPTIONAL FITTINGS REQUIRED

Dial type thermometer with two contacts for


12.3 Yes/No Yes
oil temperature

12.4 Gas and oil actuated i.e., Buchholz relay Yes/No Yes

Winding temperature indicator with two


12.5 Yes/No Yes
contacts with two contacts

12.6 On load tap changer Yes/No NA

12.7 Off Load Tap changer

Oil surge relay with alarm and trip contacts for


12.0

12.8 Yes/No NA
OLTC

12.9 Valves Yes/No Yes

12.10 Four plain rollers in place of fixing channels Yes/No Yes

Formula for evaluation of bids (Wi = No Load


EVALUAT

PENALTY

13.1 ≤ 0.12%
ION &

loss, Wc = Load loss & Wp = Auxiliary Loss )


13.0

13.2 Rates of penalty for exceeding the Wi

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 6 of 16
DATA SHEETS

DATA SHEET – A1
SL. NO. DESCRIPTION UNIT DATA
guaranteed losses per kW Wc
≤ 1.1% Max.
Wp

14.1 Complete set of gaskets Set 1 Set

14.2 Bushing of each type No. 1 No.


14.3 Dial type thermometer No. 1 No.
14.4 Complete WTI equipment No. 1 No.
Pressure relief valve/Explosion vend
14.5 No. 1 No.
ESSENTIAL SPARES

diaphragms
14.6 Silica gel breather No. 1 No.
14.7 Buchholz relay No. 1 No.
14.8 One valve of each type No. 1 No.
14.9 Cooler fan & Fan motor of each type No. NA
14.10 Oil pump & Pump motor of each type No. NA
14.0

14.11 OLTC motor No. NA


14.12 Oil Level gauge No. 1 No.
14.13 Bushing CT of each type No. NA
Miscellaneous spare (contractors control 10% of
14.14 switches, MCBs, indication lamps in cooler quantity Yes As Applicable
control Cabinet) used
15.0 NOTES

ISSUE No.: R0
DATE: 27-12-2023
DOCUMENT No. 5.0 MVA INVERTER DUTY TRANSFORMER
PAGE : 7 of 16
DATA SHEETS

DATA SHEET – A2
SL. NO. DESCRIPTION STANDARDS
Power transformer IS 2026 / IEC 61378 /
1.0
IS1180/ECBC
2.0 Guide for Loading of oil immersed transformers IS 10028
3.0 Insulating Oil IS 335
4.0 Bushings IS 2099
5.0 Degree of protection IS 2147/ IEC 60529

ISSUE No.: R0
DATE: 27-12-2023