33kV GTP of CT

The document outlines the minimum requirements for a 33 kV, 400/1-1A current transformer, specifying details such as manufacturer, type, model, and country of origin. It includes characteristics like nominal system voltage, rated lightning impulse withstand voltage, and accuracy class. Additionally, it details design and construction aspects, including materials and permissible discharge levels.

Uploaded by

Mahin Akter
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views1 page

33kV GTP of CT

The document outlines the minimum requirements for a 33 kV, 400/1-1A current transformer, specifying details such as manufacturer, type, model, and country of origin. It includes characteristics like nominal system voltage, rated lightning impulse withstand voltage, and accuracy class. Additionally, it details design and construction aspects, including materials and permissible discharge levels.

Uploaded by

Mahin Akter
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Current Transformer 33 kV, 400/1-1A


Minimum Requirements
No. Description Guaranteed
Unit Data
1, Current Transformers - General
1.1. Manufacturer Insert ABB
1,2 Type Insert TPO
1,3 Model designation Insert TPO 70.11
1,4 Country of origin Insert CZ
1,5 Standards IEC 60044-1 IEC 61869-2
1,6 Quality control ISO 9001 ISO 9001
1,7 Type Outdoor, post type Outdoor, post type
2, Current Transformers - Characteristics
2,1 Nominal system voltage kV rms 33 33
2,2 Highest voltage for equipment Un kV rms 36 36
2,3 Rated lightning impulse withstand kV peak 170 170
voltage
2,4 Rated short duration power frequency kV 70 70
voltage
2,5 Rated frequency fr Hz 50 50
2,6 Rated short-time thermal current Ith, 1 kA 31,5 31,5
s
2,7 Rated dynamic current Idyn kV peak 78,75 78,75
Rated continuous thermal current
(40°C):
2,8 ● I core % In 120 120
● II core % In 120 120
Rated transformer ratio:
2,9 ● I core A/A 400/1 400/1
● II core A/A 400/1 400/1
Accuracy class:
2,10 ● I core 5P10 5P10
● II core 1 1
2,11 Security factor:
● I core 5 5
Rated power:
2,12 ● I core VA 30 30
● II core VA 30 30
3, Current Transformers - Design and Construction
3,1 Insulator material Porcelain or HCEP
araldite
3,2 Insulating medium Oil-paper or HCEP
araldite
3,3 Minimum creepage distance mm/ kV Min. ≥ 25 mm/ kV Min. ≥ 25 mm/ kV
3,4 Max. radio interference voltage at 0.5-2 μV
MHz Max. 2500 N/A
(acc. IEC 60694)
Permissible level of partial discharges:
3,5 ● Test voltage 1.2*UM/√3 Max. ≤ 5(liquid)/20
pC Max. ≤ 5(liquid)/20 (Solid)
(Solid)

2021-05-23 1/3