Current Transducer LA 130-P IPN = 130 A
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
Features
Electrical data
●● Closed loop (compensated)
IPN Primary nominal rms current 130 A current transducer using the Hall
IPM Primary current, measuring range 0 .. ±200 A effect
RM Measuring resistance @ 85 °C RM min RM max ●● Insulating plastic case recognized
with ±12 V @ ±130 A max 10 43 Ω according to UL 94-V0.
@ ±200 A max 10 18 Ω
with ±15 V @ ±130 A max 30 65 Ω Advantages
@ ±200 A max 30 32 Ω
●● Excellent accuracy
ISN Secondary nominal rms current 130 mA
●● Very good linearity
KN Conversion ratio 1 : 1000
●● Low temperature drift
UC Supply voltage (±5 %) ±12 .. 15 V
●● Optimized response time
IC Current consumption 10 (@ ±15 V) + Is mA
●● Wide frequency bandwidth
●● No insertion losses
Accuracy - Dynamic performance data
●● High immunity to external
X Accuracy @ IPN, TA = 25 °C <0.5 % interference
εL Linearity error <0.1 % ●● Current overload capability.
Typ Max
Applications
IOE Electrical offset current @ IP = 0, TA = 25 °C ±0.20 mA
IOM Magnetic offset current @ IP = 0 and specified RM, ●● AC variable speed drives and
after an overload of 3 × IPN ±0.50 mA servo motor drives
IOT Temperature variation of IO -40 °C .. +85 °C ±0.30 ±0.60 mA ●● Static converters for DC motor
tra Reaction time <300 ns drives
tr Step response time 1) to 90 % of IPN <500 ns ●● Battery supplied applications
di/dt di/dt accurately followed >100 A/µs ●● Uninterruptible Power Supplies
BW Frequency bandwidth (-1 dB) DC .. 150 kHz (UPS)
●● Switched Mode Power Supplies
General data (SMPS)
TA Ambient operating temperature -40 .. +85 °C ●● Power supplies for welding
TS Ambient storage temperature -40 .. +90 °C applications.
RS Resistance of secondary winding @ TA = 25 °C 21±1.5 Ω Application domain
m Mass <25 g
Standards EN 50178: 1997 ●● Industrial.
UL 508: 2010
Note: 1)
With a di/dt of 100 A/µs.
N° 74.B4.37.000.0 Page 1/4
26June2015/version 4 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
UL 508:Ratings and assumptions of certification LA 130-P
File # E189713 Volume: 2 Section: 1
Standards
●● CSA C22.2 NO. 14 - 10 INDUSTRIAL CONTROL EQUIPMENT - Edition 11 - Revision Date 2011/08/01
●● UL 508 STANDARD FOR INDUSTRIAL CONTROL EQUIPMENT - Edition 17 - Revision Date 2010/04/15.
Parameter Symbol Unit Value
Primary potential involved V AC/DC 600
Max surrounding air temperature TA °C 85
Primary current IP A 0 to 130
Secondary supply voltage UC V DC ±12 .. 15
Output signal ISN mA 130
Conditions of acceptability
When installed in the end-use equiment, consideration shall be given to the following:
1 - These devices must be mounted in a suitable end-use enclosure.
2 - The terminals have not been evaluated for field wiring.
3 - The LA 130 series are intended to be mounted on the printed wiring board of the end-use equipment (with a minimum CTI
of 100).
4 - Low voltage circuits are intended to be powered by a circuit derived from an isolating source (such as a transformer,optical
isolator,limiting impedance or electro-mechanical relay) and having no direct connection back to the primary circuit (other
than through the grounding means).
5 - Base on results of temperature tests, in the end use application, a maximum of 100 °C cannot be exceeded at soldering
point between primary coil pin and soldering point of on the primary bus bar (corrected to the appropriate evaludated max.
surrounding air).
Marking
Only those products bearing the UL or UR Mark should be considered to be Listed or Recognized and covered under UL’s
Follow-Up Service.Always look for the Mark on the product.
Page 2/4
26June2015/version 4 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LA 130-P
Insulation coordination
Ud Rms voltage for AC insulation test, 50 Hz/1 min 4.3 kV
ÛW Impulse withstand voltage 1.2/50 µs 8 kV
Ue Partial discharge extinction rms voltage @ 10 pC 1.3 kV
Min
dCp Creepage distance 8 mm
dCI Clearance 8 mm
CTI Comparative tracking index (group I) 600
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
●● Over voltage category OV 3
●● Pollution degree PD2
●● Non-uniform field
EN 50178 IEC 61010-1
dCp, dCI, ÛW Rated insulation voltage Nominal voltage
Basic insulation 1000 V 1000 V
Reinforced insulation 600 V 400 V
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 3/4
26June2015/version 4 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions LA 130-P (in mm)
dCl dCp
Connection
IP
UC
IS RM
UC
Mechanical characteristics Remarks
●● General tolerance ±0.5 mm ●● IS is positive when IP flows in the direction of the arrow.
●● Primary through-hole 13.5 × 10 mm ●● Temperature of the primary conductor should not exceed
●● Fastening & connection of secondary 3 pins 0.6 × 0.6 mm 100 °C.
Recommended PCB hole ⌀ 1.1 mm ●● Installation of the transducer must be done unless
otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document N°ANE120504 available on our Web site:
Products/Product Documentation.
●● Dynamic performances (di/dt and response time) are
best with a single bar completely filling the primary hole.
●● This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Page 4/4
26June2015/version 4 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com