Product datasheet
Specifications
enclosed variable speed drive
ATV61 Plus - 400 kW - 690V - IP23
ATV61EXC2C40Y
notification_critical_stroke Discontinued on: 6 Sept 2024
notification_critical_stroke To be end-of-service on: 31 Dec 2028
notification_critical_stroke Discontinued - Service only
Main
Range of product Altivar 61 Plus
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Variable speed drive
Device short name ATV61
Product destination Asynchronous motors
Synchronous motors
Product specific application Pumping and ventilation machine
Assembly style In floor-standing enclosure compact version
product composition ATV61HC40Y standard drive IP00
A switch and fast-acting fuses
An IP65 remote mounting kit for graphic display terminal
A wired ready-assembled Sarel Spacial 6000 enclosure
A line choke
Terminals/bars for motor connection
EMC filter Integrated
Network number of phases 3 phases
rated supply voltage 690 V +/- 10 %
Supply voltage limits 621…759 V
Supply frequency 50...60 Hz - 5...5 %
Network frequency limits 47.5…63 Hz
Motor power kW 400 kW, 3 phases at 690 V
Line current 394 A at 690 V3 phases / 400 kW
IP degree of protection IP23
Complementary
Apparent power 471 kVA for 690 V, 3 phases 400 kW
Prospective line Isc 100 kA with external fuses
Continuous output current 420 A, 2.5 kHz at 690 V 3 phases
Maximum transient current 504 A for 60 s, 3 phases
Speed drive output frequency 0.1…500 Hz
Nominal switching frequency 2.5 kHz
Switching frequency 2.5...4.9 kHz with derating factor
2...4.9 kHz adjustable
Speed range 1…100 in open-loop mode, without speed feedback
Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback
8 Jan 2025 1
Torque accuracy +/- 15 % in open-loop mode, without speed feedback
Transient overtorque 120 % of nominal motor torque for 60 s
135 % of nominal motor torque for 2 s
Braking torque <= 125 % with braking resistor
30 % without braking resistor
Asynchronous motor control Energy saving ratio
profile Flux vector control without sensor, standard
Voltage/frequency ratio (2 or 5 points)
Synchronous motor control profile Vector control without sensor, standard
Regulation loop Adjustable PI regulator
Motor slip compensation Not available in voltage/frequency ratio (2 or 5 points)
Can be suppressed
Automatic whatever the load
Adjustable
Overvoltage category Class 3 conforming to EN 50178
Local signalling LCD display unit for operation function, status and configuration - mounted in the
front door
Output voltage <= power supply voltage
Isolation Between power and control terminals
type of cable for external IEC cable at 40 °C, copper 70 °C / PVC
connection
Electrical connection Terminal - 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B,
LI1...LI6, PWR)
Terminal M12 - 4 x 240 mm² (U/T1, V/T2, W/T3)
Terminal M12 - 3 x 185 mm² (L1/R, L2/S, L3/T)
Motor recommanded cable cross 2 (3 x 150) mm²
section
Short-circuit protection 630 A fuse protection type gI - power supply upstream
Supply External supply: 24 V (19…30 V)DC, <1 A, 30 W
Internal supply for reference potentiometer: 10 V (10…11 V)DC, <10 mA
Internal supply: 24 V (21…27 V)DC, <100 mA
Analogue input number 2
Analogue input type AI2 software-configurable voltage: 0...10 V DC, 24 V max, impedance: 30 kOhm,
sampling time: 1.5…2.5 ms, resolution: 11 bits
AI1-/Al1+ bipolar differential voltage: +/- 10 V DC, 24 V max, sampling time: 1.5…2.5
ms, resolution: 11 bits + sign
AI2 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm,
sampling time: 1.5…2.5 ms, resolution: 11 bits
Analogue output number 1
Analogue output type Software-configurable voltage: (AO1) 0...10 V DC - 470 Ohm - sampling time: 1.5…
2.5 ms - resolution: 10 bits
Software-configurable current: (AO1) 0...20 mA/4...20 mA - 500 Ohm - sampling
time: 1.5…2.5 ms - resolution: 10 bits
Discrete output number 2
Discrete output type Configurable relay logic: (R1A, R1B, R1C)NO/NC - 6.5...7.5 ms - 100000 cycles
Configurable relay logic: (R2A, R2B)NO - 6.5...7.5 ms - 100000 cycles
Minimum switching current 3 mA at 24 V DC (configurable relay logic)
Maximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 for configurable relay logic
5 A at 30 V DC on resistive load - L/R = 0 ms for configurable relay logic
2 A at 250 V AC on inductive load - cos phi = 0.4 for configurable relay logic
2 A at 30 V DC on inductive load - L/R = 7 ms for configurable relay logic
Discrete input number 7
2 8 Jan 2025
Discrete input type Programmable (LI1...LI5) at 24 V DC <= 30 V level 1 PLC 3.5 kOhm (duration=1.5…
2.5 ms)
Switch-configurable (LI6) at 24 V DC <= 30 V level 1 PLC 1.5 kOhm (duration=1.5…
2.5 ms)
Safety input (PWR) at 24 V DC <= 30 V 1.5 kOhm
Discrete input logic Positive logic (source) (LI1...LI6), 0...5 V (state 0), 11...30 V (state 1)
Negative logic (sink) (LI1...LI6), 16...30 V (state 0), 0...10 V (state 1)
Positive logic (source) (PWR), 0...2 V (state 0), 17...30 V (state 1)
Acceleration and deceleration S, U or customized
ramps Linear adjustable separately from 0.01 to 9000 s
Braking to standstill By DC injection
Protection type Against exceeding limit speed: drive
Against input phase loss: drive
Break on the control circuit: drive
Input phase breaks: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Overvoltages on the DC bus: drive
Power removal: drive
Short-circuit between motor phases: drive
Thermal protection: drive
Motor phase break: motor
Power removal: motor
Thermal protection: motor
Dielectric strength 3110 V DC between earth and power terminals
5345 V DC between control and power terminals
Insulation resistance > 1 mOhm 500 V DC for 1 minute to earth
Frequency resolution Analog input: 0.024/50 Hz
Display unit: 0.1 Hz
Communication port protocol Modbus
CANopen
Connector type 1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen
Physical interface 2-wire RS 485 for Modbus
Transmission frame RTU for Modbus
Transmission rate 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
9600 bps, 19200 bps for Modbus on front face
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
Data format 8 bits, 1 stop, even parity for Modbus on front face
8 bits, odd even or no configurable parity for Modbus on terminal
Type of polarization No impedance for Modbus
Number of addresses 1…127 for CANopen
1…247 for Modbus
Method of access Slave CANopen
8 Jan 2025 3
Function available Safe standstill for power circuit
PTC relay for power circuit
Pt100 relay for power circuit
Insulation monitoring for power circuit
Design for IT networks for power circuit
External 230 V supply terminals for power circuit
Buffer voltage 24 V DC power supply for power circuit
Enclosure lighting for power circuit
Key switch (local/remote) for power circuit
Motor heating for power circuit
External motor fan for power circuit
Voltmeter for power circuit
Door handle for main switch for power circuit
Line contactor for power circuit
12-pulse supply for power circuit
Ammeter for power circuit
Enclosure heating for power circuit
Motor choke for power circuit
Cable entry via the top for power circuit
Enclosure plinth for power circuit
Braking unit for power circuit
Relay output C/O for control circuit
External 24 V DC supply terminals for power circuit
Control terminals for control circuit
Adaptor for 115 V logic inputs for control circuit
Isolated amplifier for control circuit
Option card Communication card for APOGEE FLN
Communication card for BACnet
Communication card for CC-Link
Communication card for DeviceNet
Communication card for EtherNet/IP
Communication card for Fipio
Communication card for Interbus-S
Communication card for LonWorks
Communication card for METASYS N2
Communication card for Modbus Plus
Communication card for Modbus TCP
Communication card for Modbus/Uni-Telway
Communication card for Profibus DP
Communication card for Profibus DP V1
Controller inside programmable card
Multi-pump card
Basic I/O extension card
Extended I/O extension card
Encoder interface cards
Operating position Vertical +/- 10 degree
Colour of enclosure Light grey (RAL 7035)
width 800 mm
Height 2162 mm
Depth 642 mm
Net weight 553 kg
Environment
Electromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Standards EN 61800-3 environments 1 category C3
EN 55011 class A group 2
EN 61800-3 environments 2 category C3
EN/IEC 61800-5-1
EN/IEC 61800-3
Product certifications GOST
ATEX
4 8 Jan 2025
Marking CE
Noise level 66 dB
Pollution degree 2 conforming to EN/IEC 61800-5-1
Vibration resistance 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…10 Hz) conforming to EN/IEC 60068-2-6
3M3 conforming to EN/IEC 60721-3-3
Shock resistance 4 gn for 11 ms conforming to EN/IEC 60068-2-27
3M2 conforming to EN/IEC 60721-3-3
Environmental characteristic 3C2 without condensation conforming to IEC 60721-3-3
3S2 without condensation conforming to IEC 60721-3-3
3K3 without condensation conforming to IEC 60721-3-3
Relative humidity 0…95 %
Ambient air temperature for 0…40 °C (without derating)
operation 40…50 °C (with current derating of 1 % per °C)
Ambient air temperature for -25…70 °C
storage
Volume of cooling air 1200 m3/h
Operating altitude <= 1000 m without derating
1000...2260 m with current derating 1 % per 100 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 216.0 cm
Package 1 Width 66.0 cm
Package 1 Length 101.6 cm
Package 1 Weight 555.0 kg
Contractual warranty
Warranty 18 months
8 Jan 2025 5
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain
partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use
Longer, Use Again” campaign to extend product lifetimes and recyclability.
How this information helps you
Use Better
Materials and Substances
Packaging made with recycled
No
cardboard
Packaging without single use
No
plastic
Use Again
Repack and remanufacture
Take-back No
6 8 Jan 2025
Product datasheet ATV61EXC2C40Y
Dimensions Drawings
IP 23 Floor-Standing Enclosure Compact Version
Standard Compact Floor-Standing Enclosure
Standard Compact Floor-Standing Enclosure + Additional Floor-Standing Enclosures,
According to the Configuration
(1) Seal. For each floor-standing enclosure added, allow a 4 mm/0.15 in. space for the seal.
(2) Standard IP 23 compact version floor-standing enclosure.
NOTE: The position of the enclosures must be complied with during
installation. The number of additional enclosures can vary according to the
chosen configuration.
8 Jan 2025 7
Product datasheet ATV61EXC2C40Y
Options a a1 a2 a3 a4
With or without common options or options 816 mm/ 816 mm/
– – –
dependent on the drive rating 32.1 in. 32.1 in.
808 mm/ 408 mm/ 1220 mm/
Cable entry via the top option – –
31.8 in. 16 in. 48 in.
808 mm/ 408 mm/ 1220 mm/
Braking unit option – –
31.8 in. 16 in. 48 in.
808 mm/ 408 mm/ 400 mm/ 1624 mm/
Braking unit + cable entry via the top options –
31.8 in. 16 in. 15.7 in. 63.9 in.
(3) Except sinus filter option, which requires an additional enclosure. The sinus filter option is not compatible with
the cable entry via the top option.
(4) The cable entry via the top option is not compatible with the sinus filter option.
8 8 Jan 2025
Product datasheet ATV61EXC2C40Y
Connections and Schema
Floor-Standing Enclosure Compact Version
Wiring Diagram
A1 Drive
A2 Enclosure
F1 Fast-acting semi-conductor fuse
IL1 Line choke
Q1 Switch
(1) Fault relay contacts. For remote signalling of drive status.
8 Jan 2025 9
Product datasheet ATV61EXC2C40Y
Performance Curves
Floor-Standing Enclosure Compact Version
Derating Curves
The derating curves for the drive nominal current (In) are dependent on the temperature and switching frequency. For
intermediate temperatures, interpolate between 2 curves.
NOTE: The drive will reduce the switching frequency automatically in the
event of excessive temperature rise.
X Switching frequency (kHz)
NOTE: The temperatures shown correspond to the temperature of the air
entering the enclosure.
10 8 Jan 2025