EasyLogic™ APF User Manual EZAPF3160898EN_01
EasyLogic™ APF User Manual EZAPF3160898EN_01
EZAPF3160898EN_01
01/2024
www.se.com
Legal Information
The information provided in this document contains general descriptions, technical
characteristics and/or recommendations related to products/solutions.
This document is not intended as a substitute for a detailed study or operational and
site-specific development or schematic plan. It is not to be used for determining
suitability or reliability of the products/solutions for specific user applications. It is the
duty of any such user to perform or have any professional expert of its choice
(integrator, specifier or the like) perform the appropriate and comprehensive risk
analysis, evaluation and testing of the products/solutions with respect to the relevant
specific application or use thereof.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this document are the property of Schneider Electric SE or
its subsidiaries. All other brands may be trademarks of their respective owner.
This document and its content are protected under applicable copyright laws and
provided for informative use only. No part of this document may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
document or its content, except for a non-exclusive and personal license to consult it
on an "as is" basis.
Schneider Electric reserves the right to make changes or updates with respect to or in
the content of this document or the format thereof, at any time without notice.
To the extent permitted by applicable law, no responsibility or liability is
assumed by Schneider Electric and its subsidiaries for any errors or omissions
in the informational content of this document, as well as any non-intended use
or misuse of the content thereof.
Active Harmonic Filter
Table of Contents
Foreword ......................................................................................................5
Safety Information ......................................................................................5
Safety Precautions .....................................................................................6
Introduction ..................................................................................................7
Active Harmonic Filter .................................................................................7
Operation .....................................................................................................8
Basic Operating Instructions........................................................................8
Introduction to 7-inch HMI .........................................................................10
Home Screen .....................................................................................10
User Access Permission......................................................................10
Menu Interface ...................................................................................12
Measurement Interface .......................................................................13
Setting Interface .................................................................................17
Event Log Interface .............................................................................26
Help Interface .....................................................................................28
Fault Reset.........................................................................................28
About Interface ...................................................................................29
Introduction to 4.3-inch HMI.......................................................................30
Home Screen .....................................................................................30
User Access Permission......................................................................30
Menu Interface ...................................................................................32
Measurement Interface .......................................................................33
Setting Interface .................................................................................38
Event Log Interface .............................................................................46
About Interface ...................................................................................47
Fault Reset.........................................................................................47
Operation Instructions for Startup/Shutdown and Debugging ...........49
Startup Steps ...........................................................................................49
Shutdown Steps .......................................................................................50
System Parameter Configuration ...............................................................51
Quick Parameter Setting .....................................................................51
Advanced Parameter Setting ...............................................................52
System Debugging ...................................................................................54
Cybersecurity.............................................................................................56
Equipment Safety .....................................................................................56
Password Management ............................................................................56
Access Control .........................................................................................57
Local Access............................................................................................57
Modbus RTU based Remote Access..........................................................57
Firmware Update......................................................................................58
Safe Disposal...........................................................................................58
Network Security Vulnerabilities or Events ..................................................58
Open-source Library License Statement.....................................................58
EasyLogic™ APF HMI Firmware Upgrade Instruction ........................60
Troubleshooting ........................................................................................65
EZAPF3160898EN_01 3
Foreword Active Harmonic Filter
Foreword
Safety Information
Important Information
Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service, or maintain
it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
EZAPF3160898EN_01 5
Active Harmonic Filter Foreword
Safety Precautions
Installation, wiring, testing and service must be performed in accordance with all
local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personnel protective equipment (PPE) and follow safe
electrical work practices. Refer to your local regulations.
• This equipment must only be installed in area accessible to electrically
skilled personnel and electrically instructed personnel with the proper
authorization and serviced by qualified electrical personnel.
• This equipment must only be installed in area without combustible materials.
• Turn off all power to auxiliary contacts and short CT secondary’s before
working on or inside the equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Ensure all disconnect switches are disconnected before servicing
equipment. More than one may be present.
• After removing power, wait 15 minutes to allow capacitors to discharge
before opening or removing covers.
• Replace all devices and covers before turning on power to this equipment.
• Carefully inspect the interior for tools left behind before replacing covers.
• Verify the rating of the neutral conductor for each unit in the system is
greater than the neutral current limit setting.
Failure to follow these instructions will result in death or serious injury.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords at first use to help prevent unauthorized access
to device settings and information.
• Disable unused ports or services and default accounts, where possible, to
minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cyber security best practices (for example, least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, interruption of services, or unintended operation.
• Restrict unit access to authorized personnel only.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
6 EZAPF3160898EN_01
Introduction Active Harmonic Filter
Introduction
Active Harmonic Filter
Active Harmonic Filters are static power electronic products that employ digital
logic and IGBT semiconductors to synthesize a current waveform that is injected
into the electrical network to cancel harmonic currents caused by nonlinear loads.
Active Harmonic Filter employ current transformers to measure the load current to
determine the content of harmonic current present. By injecting the synthesized
current, network harmonic currents are greatly mitigated, thus reducing the
heating effects of harmonic current and reducing voltage distortion.
Active Harmonic Filter also have the ability to correct for poor displacement power
factor (DPF) and for mains current balancing. DPF correction can be provided for
either leading (capacitive) or lagging (inductive) loads that cause poor DPF. Mains
current balancing is achieved by measuring the negative and zero sequence
current present and injecting the inverse of those currents to balance the current
for the upstream network.
Schneider Electric Active Harmonic Filter, EasyLogic™ APF enclosures are
available in an IP20 rack-mounted, IP20, and IP31 wall-mounted. EasyLogic™
APF can be powered by three phase conductors to provide corrective current for
Line-to-Line connected loads or by three phase conductors and neutral to provide
correction for Line-to-Line and Line-to-Neutral connected loads. The amount of
neutral current for up to three times the phase current correction. The neutral
wiring must be sized appropriately based on the selected neutral current
correction.
The EasyLogic™ APF module can be used as an expansion unit, for example, to
be installed in other types of cabinets such as Motor Control Center (MCC). After
expansion, the whole system is automatically assigned a host unit. The expanded
system shall be equipped with an HMI, which allows to view and change the
parameter settings of the whole system or any other unit in the parallel system.
The expansion unit only needs to connect cables such as power cables and
parallel cables.
EZAPF3160898EN_01 7
Active Harmonic Filter Operation
Operation
The HMI of Schneider Electric EasyLogic™ APF is a color touch LCD screen and
two sizes: 4.3-inch and 7-inch, and the resolutions are 480*272 pixels, 800*480
pixels. Two touch screens have a brightness of 250 nit. The 4.3-inch HMI is built
into the wall-mounted module, and the 7-inch HMI is used externally when the
rack-mounted or wall-mounted modules are connected in parallel.
B A
A. This area displays the current operation status of APF and real-time
measurement indicators of power grid and load, such as THDi indicator.
Other similar areas include areas that display charts and curves.
B. This area displays the function buttons that can be operated by APF.
The functions that can be operated on the HMI are indicated by raised or
highlighted graphic and text buttons, menus, prompt boxes or input boxes, as
shown below:
8 EZAPF3160898EN_01
Operation Active Harmonic Filter
An example of a raised button, which indicates that click to enter the next page.
An example of a prompt box, which indicates that click to select the required
parameter value in the drop-down prompt box.
An example of an input box, which indicates that click and enter the required
parameter value.
NOTICE
AVOID TAPPING THE HMI IN RAPID SUCCESSION
When tapping the touch screen in rapid succession, it will enter the blue
calibration interface.
Failure to follow these instructions can result in equipment damage.
The blue calibration interface is a normal function of the touch screen and entering
this interface does not indicate any abnormal function of the screen. If you enter
this interface by mistake, you can follow the prompts on the screen and
automatically return to the original interface after completing the screen
calibration.
EZAPF3160898EN_01 9
Active Harmonic Filter Operation
The home screen of HMI is used to display the menu button, date, APF status,
number of parallel, user, the Grid, Load and APF output information, home button,
On-off button, including:
• : Menu button, click to menu Interface.
• Grid: Display Grid Frequency, Grid U, Grid THDu, Grid I, Grid THDi, Grid PF.
• Load: Display Load I, Load THDi, Load PF.
• APF: Display APF Output, APF Load Rate.
ON
• : You can turn on or turn off the APF.
10 EZAPF3160898EN_01
Operation Active Harmonic Filter
CAUTION
OPERATE THE EQUIPMENT IN COMPLIANCE WITH CYBERSECURITY
REQUIREMENTS
Always follow Schneider Electric's cybersecurity guidelines to operate the
equipment.
Failure to follow these instructions can result in injury or equipment
damage.
Before updating your password, you must answer three password security
questions correctly. To set security questions, see Setting Interface, page 17
section for details.
EZAPF3160898EN_01 11
Active Harmonic Filter Operation
After answering the security questions correctly, you can set the new password as
follows:
Menu Interface
Click the on the home screen to enter the menu interface.
This section introduces the Menu interface of the 7-inch HMI, which contains six
sub-menu interfaces: Measurement, Event Log, Setting, Help, Fault Reset, and
About.
12 EZAPF3160898EN_01
Operation Active Harmonic Filter
Measurement Interface
Click Measurement on the menu screen to enter the measurement interface.
This section introduces the measurement interface of the 7-inch HMI, which
contains four sub-menu interfaces: Power, Harmonics Histogram,
Waveform, Module Info.
EZAPF3160898EN_01 13
Active Harmonic Filter Operation
14 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 15
Active Harmonic Filter Operation
Under level II permission Click Module Info measurement menu, the information
of Others is different, including Total Operate Time and T:More Than 50% Load.
16 EZAPF3160898EN_01
Operation Active Harmonic Filter
Setting Interface
Schneider Electric APFs main objective is to filter out harmonic current in the
power grid, meanwhile to compensate reactive power and unbalance of the power
grid. In the setting interface, you can set the corresponding operation mode and
adjust the equipment operation parameters according to the on-site power grid
status.
Click the Setting option on the menu screen to enter the Setting interface.
You need to enter the permission password to access different permission setting
interfaces. For permission login, see User Access Permission, page 10 section.
This section introduces the Setting interface of the 7-inch HMI, which contains four
sub-menu interfaces: System, Compensation, Communication and
Customize.
EZAPF3160898EN_01 17
Active Harmonic Filter Operation
NOTICE
USE AND CONFIGURE CT OF CORRECT SPECIFICATION
• Use CT that meets the technical requirements of APF.
• The same transformation ratio parameters as the CT must be
configured and adopted in the HMI.
Failure to follow these instructions can result in equipment damage.
• CT Location: Divided into Load side and Grid side. It needs to be selected
according to actual installation position of the external CT.
• L1/L2/L3 CT Wiring: The default value is A+,B+ and C+. If there is a wiring
error, you can adjust this setting to correct it without changing the wiring.
• Power On Mode: It is divided into Automatic and Manual.
◦ In Automatic mode, APF will automatically start filtering output after the
system is powered on.
◦ In Manual mode, the system needs to be started manually in HMI.
◦ The system defaults to Manual mode.
18 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 19
Active Harmonic Filter Operation
20 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 21
Active Harmonic Filter Operation
22 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 23
Active Harmonic Filter Operation
•
◦ Working day: Select Working day in a week (Monday to Sunday is
optional) and enter the on-off time of each day, and click Time Switch to
complete the working day setting.
◦ Non-working day: Enter the start and end date of the desired rest date,
and click the Add Item to complete the setting. If you no longer need a
certain rest day setting, just click to select Non-working day setting (in
this case, a green arrow will be added before the selected rest day
setting), and then click Delete Item to complete the deletion.
• The password setting interface under each permission is the same: As
shown in the figure below, set a new password and confirm the password.
24 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 25
Active Harmonic Filter Operation
Schneider Electric APF 7-inch HMI can record a total of 500 Active Alarm and
Historic Alarms. A total of 1000 Operations can be recorded. When the internal
record is full, the oldest record will be automatically overwritten.
1. Active Alarm interface
As shown in the figure, this interface displays active alarm information of the
equipment and the occurrence time of the alarm.
In the Active Alarm interface, click at the lower left corner to turn on and
off the alarm warning tone of the HMI.
26 EZAPF3160898EN_01
Operation Active Harmonic Filter
3. Operations interface
As shown in the figure, this interface records operations that distribute
parameters to the equipment, including the occurrence time and the change
of operations value.
4. Download
In the Event Log interface, click Download in the upper right corner to
download the alarm records, operation records, historical data and fault point
information recorded on the HMI to the USB disk.
Before downloading, insert the USB disk into the USB port of the HMI. Enter
the Event Log interface, click Download, and jump to the Get Permissions
interface. After obtaining permission confirmation, enter the common
operation interface. Click Download, the interface will pop up the function
selection dialog box. After clicking the data button to be downloaded, and the
interface prompts download succeeded , the Record-x folder will be
automatically generated in the USB disk, which contains the downloaded
record report.
EZAPF3160898EN_01 27
Active Harmonic Filter Operation
Help Interface
Click Help on the menu to enter the Help interface.
This section introduces the Help interface of the 7-inch HMI, which contains eight
sub interfaces of Inverter Over-temperature, Voltage Issue, Frequency Issue,
Non-compen. I output, Inverter Overload, CT Ratio setting Error, Monitor
Setting Error and Emergency shutdown.
Introduction to each help topic:
• Inverter Over-temperature
• Voltage Issue
• Frequency Issue
• Non-compen. I output
• Inverter Overload
• CT Ratio setting Error
• Monitor Setting Error
• Emergency shutdown
Fault Reset
When APF encounters some fault alarms (such as over-temperature alarm), the
equipment will automatically enter the operation locking state: the equipment
stops harmonic output and cannot automatically resume operation. After the fault
is removed, it is necessary to click the Fault Reset button to manually clear the
fault locking state before restarting the equipment.
28 EZAPF3160898EN_01
Operation Active Harmonic Filter
It should be noted that the operation of clicking Fault Reset only releases the
operation locking status of the equipment and does not clear the fault alarm
records generated before.
About Interface
Click About on menu screen to enter the about interface.
EZAPF3160898EN_01 29
Active Harmonic Filter Operation
The home screen of HMI is used to display the menu button, date, APF status,
user, the Grid, Load and APF output information, home button, On-off button,
including:
• : Menu button, click to menu Interface.
• Grid: Display Grid Frequency, Grid U, Grid THDu, Grid I, Grid THDi, Grid PF.
• Load: Display Load I, Load THDi, Load PF.
• APF: Display APF Output, APF Load Rate.
ON
• : You can turn on or turn off the APF.
30 EZAPF3160898EN_01
Operation Active Harmonic Filter
CAUTION
OPERATE THE EQUIPMENT IN COMPLIANCE WITH CYBERSECURITY
REQUIREMENTS
Always follow Schneider Electric's cybersecurity guidelines to operate the
equipment.
Failure to follow these instructions can result in injury or equipment
damage.
Before updating your password, you must answer three password security
questions correctly. To set security questions, see Setting Interface, page 38
section.
After answering the security questions correctly, you can set the new password as
follows:
EZAPF3160898EN_01 31
Active Harmonic Filter Operation
Menu Interface
Click on the home screen to enter the Menu interface.
This section introduces the Menu interface of the 4.3-inch HMI, which contains five
sub-menu interfaces: Measurement, Event Log, Setting, Fault Reset and
About.
32 EZAPF3160898EN_01
Operation Active Harmonic Filter
Measurement Interface
Click the measurementon menu screen to enter the measurement interface.
Measurement interface of 4.3-inch HMI is as follows:
At the bottom of the interface, click Wave and Histogram respectively to view
corresponding information.
Click Wave to enter the waveform display interface, as shown below:
EZAPF3160898EN_01 33
Active Harmonic Filter Operation
Click buttons of different phases at the bottom of the histogram to view the voltage
information of corresponding phases.
Click < or >in the lower right corner of the screen to turn the page back and forth to
check the content of each harmonic. The 4.3-inch HMI screen can display the
content of 50th harmonic at most.
Click Wave and Histogram at the bottom of the interface to access relevant
information.
Click Wave to enter the grid current waveform interface, as follows:
34 EZAPF3160898EN_01
Operation Active Harmonic Filter
Click buttons of different phases at the bottom of the histogram to view the current
information of corresponding phases.
Click<or >in the lower right corner of the screen to turn the page back and forth to
check the content of each harmonic.
(B): Click I Load menu to display parameters such as current per phase on the
load side, cosφ and THDi.
(C): Click the I Comp. menu to display parameters such as compensation current
and load rate of each phase.
EZAPF3160898EN_01 35
Active Harmonic Filter Operation
Click the Wave enter the compensation current waveform interface, which is
similar to the grid current waveform interface and the load current waveform
interface.
36 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 37
Active Harmonic Filter Operation
Setting Interface
Click the Setting on menu screen to enter the setting interface.
38 EZAPF3160898EN_01
Operation Active Harmonic Filter
EZAPF3160898EN_01 39
Active Harmonic Filter Operation
• CT Location: Divided into Load side and Grid side. It needs to be selected
according to actual installation position of the external CT.
NOTICE
USE AND CONFIGURE CT OF CORRECT SPECIFICATION
• Use CT that meets the technical requirements of APF.
• The same transformation ratio parameters as the CT must be
configured and adopted in the HMI.
Failure to follow these instructions can result in equipment damage.
• L1/L2/L3 CT Wiring: The default value is A+,B+ and C+. If there is a wiring
error, you can adjust this setting to correct it without changing the wiring.
• Power On Mode: It is divided into Automatic and Manual.
◦ In Automatic mode, APF will automatically start filtering output after the
system is powered on.
◦ In Manual mode, the system needs to be started manually in HMI.
◦ The system defaults to Manual mode.
• Operation mode: The pull-down menu of the input box contains up to 13
operation modes, different combinations of harmonic (H), reactive power (Q)
and unbalance (B), Auto-aging operation mode, etc. the user can select the
corresponding operation mode according to the actual power grid or load
status on site. Similar to the 7-inch HMI, please refer to Setting Interface,
page 17 section.
• Compensation Mode: It is divided into three types: Intelligent, Sequential
and All.
◦ Intelligent compensation: Intelligent Fourier algorithm is adopted to
intelligently adjust to the best filtering effect, which can avoid resonance to
a certain extent.
◦ Sequential compensation: Fourier algorithm is used to quickly filter out the
selected harmonics.
◦ All compensation: The instantaneous reactive power algorithm is used to
quickly filter out various harmonics and reactive power in the system.
It is recommended to select the Intelligent compensation operation mode
first. When it is necessary to adjust the harmonic compensation effect of
certain orders, adjust to Sequential compensation or All compensation
mode.
• Control Algorithm: For this function, enable and disable can be selected
from the drop-down menu of this input box. When CT is located at the power
supply side and the equipment is in closed-loop compensation state, it is
recommended to set to enable to achieve more accurate compensation
effect. The default value is enable.
• Compensation Rate: Set the compensation ratio of the current to be
compensated and measured by APF. The setting range is 0%~100%. The
default value is 100%.
• Total Capacity: Indicates the capacity of module, and the unit is A.
• Total Module Qty: Set the number of module. The setting is 1.
• Master Module No.: The default value is 0.
• Temperature Derating: APF has built-in device temperature protection
function, which can automatically derate the output according to the internal
monitoring temperature. For this function, enable and disable can be
selected from the drop-down menu of this input box. This function is enable
by default.
• Altitude Derating : This parameter is used to control the maximum output of
the equipment and is often used to set the altitude derating value. The setting
range is 0%~100%. If you set altitude derating 10%, the maximum output is
90% of APF rated capacity.
40 EZAPF3160898EN_01
Operation Active Harmonic Filter
Under level II permission, click System setting menu to add the following
advanced parameter setting items on the basis of level I permission setting
parameters: including Compensation Setting, Comp. Parameter Setting,
Reactive Power Setting, Other Setting and Protection Setting.
EZAPF3160898EN_01 41
Active Harmonic Filter Operation
42 EZAPF3160898EN_01
Operation Active Harmonic Filter
• Abnormal input Current: For this function, enable and disable can be
selected from the drop-down menu of this input box. When the field current
jumps, it may cause the APF to falsely report an over-current fault. In this
case, it can be set to disable this function to facilitate on-site debugging. The
default value is enable.
• Overheat times: When the internal temperature of APF is too high, the
equipment will automatically stop output, and automatically recover output
after the internal temperature becomes normal. However, when the set value
is exceeded, the equipment will stop working and report over-temperature
fault, which needs to be manually cleared before it can resume operation. The
default value is 3.
• ECO Mode Load Threshold: Low load coefficient can be set. If the output of
APF system falls below the target parameter, the equipment will stop output
compensation. The setting range is 0%~100%. The default value is 0%.
EZAPF3160898EN_01 43
Active Harmonic Filter Operation
Click Power Saving setting button to enter the time setting interface, as follows:
44 EZAPF3160898EN_01
Operation Active Harmonic Filter
When setting security questions, please note that at least three security questions
are set, and each question supports up to 26 characters.
EZAPF3160898EN_01 45
Active Harmonic Filter Operation
Click < and > in the lower right corner of the screen to view more event
records.
2. Historic Alarms interface
As shown in the figure, this interface displays the historical alarm information
of the equipment, the occurrence time and end time of the alarm.
Click < and > in the lower right corner of the screen to view more event
records.
46 EZAPF3160898EN_01
Operation Active Harmonic Filter
Click < and > in the lower right corner of the screen to view more event
records.
About Interface
Click About in the menu screen to enter the interface and view the version
information of HMI.
Fault Reset
EZAPF3160898EN_01 47
Active Harmonic Filter Operation
When APF encounters some fault alarms (such as over-temperature alarm), the
equipment will automatically enter the operation locking state: the equipment
stops harmonic output and cannot automatically resume operation. After the fault
is removed, it is necessary to click Fault Reset to manually clear the fault locking
state before restarting the equipment.
It should be noted that the operation of clicking Fault Reset only releases the
operation locking status of the equipment and does not clear the fault alarm
records generated before.
48 EZAPF3160898EN_01
Operation Instructions for Startup/Shutdown and Debugging Active Harmonic Filter
Startup Steps
After the Schneider Electric APF module (or multi-module paralleled system) is
powered on, startup process can be performed.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personnel protective equipment (PPE) and follow safe
electrical work practices. Refer to your local regulations.
• This equipment must only be installed in area accessible to electrically
skilled personnel and electrically instructed personnel with the proper
authorization and serviced by qualified electrical personnel.
• This equipment must only be installed in area without combustible materials.
• Turn off all power to auxiliary contacts and short CT secondary’s before
working on or inside the equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Ensure all disconnect switches are disconnected before servicing
equipment. More than one may be present.
• After removing power, wait 15 minutes to allow capacitors to discharge
before opening or removing covers.
• Replace all devices and covers before turning on power to this equipment.
• Carefully inspect the interior for tools left behind before replacing covers.
• Verify the rating of the neutral conductor for each unit in the system is
greater than the neutral current limit setting.
Failure to follow these instructions will result in death or serious injury.
DANGER
DANGER OF ELECTRIC SHOCK, EXPLOSION OR FLASH BURN
• After the power port of the equipment is powered on, the internal auxiliary
power supply of the equipment will be automatically turned on.
• Appropriate sensing devices with rated voltages should always be used to
confirm that the power is on.
Failure to follow these instructions will result in death or serious injury.
EZAPF3160898EN_01 49
Active Harmonic Filter Operation Instructions for Startup/Shutdown and Debugging
Shutdown Steps
When the APF module (or multi-module paralleled system) needs to be powered
off, a shutdown can be performed.
The shutdown steps are as follows:
1. Turn off harmonic output
On HMI home screen interface and click the Power Off button. After the
permission is confirmed, the module will close harmonic output.
DANGER
DANGER OF ELECTRIC SHOCK, EXPLOSION OR FLASH BURN
• Pressing the shutdown button can only stop harmonic output of the
equipment and cannot completely power off the equipment.
• Appropriate sensing devices with rated voltages should always be used
to confirm that the power is off.
Failure to follow these instructions will result in death or serious
injury.
DANGER
DANGER OF ELECTRIC SHOCK, EXPLOSION OR FLASH BURN
• Wait 15 minutes after the power is cut off to allow the capacitor in the
module to discharge
• Appropriate sensing devices with rated voltages should always be used
to confirm that the power is completely off inside the equipment.
Failure to follow these instructions will result in death or serious
injury.
50 EZAPF3160898EN_01
Operation Instructions for Startup/Shutdown and Debugging Active Harmonic Filter
EZAPF3160898EN_01 51
Active Harmonic Filter Operation Instructions for Startup/Shutdown and Debugging
After completing the above settings, it is necessary to first return to the menu
screen of HMI and click the measurement to observe whether the actual status
parameters of power grid and load, measurement waveforms and other data are
true and correct, so as to judge whether the CT and power line are correctly
connected. After confirming that parameter settings are correct and APF has no
fault alarm, then click power on. After the permission is confirmed, the equipment
starts harmonic output, and automatically monitors and governs power grid
harmonics.
Status parameters of power grid and load before APF filtering on site are as
follows:
52 EZAPF3160898EN_01
Operation Instructions for Startup/Shutdown and Debugging Active Harmonic Filter
1. When there are not only harmonics and reactive power in the power system.
The settings need to be adjusted as follows:
• Operation Mode setting: Select the mode of harmonic + reactive power
(H+Q) or reactive power + harmonic(Q+H). Please refer to Setting
Interface, page 17 section for introductions of the operation mode.
• Target Power Factor setting: Enter 1.
• Capacitive Compensation enable: Select enable.
2. When there are not only harmonics but also unbalance in the power system.
The settings need to be adjusted as follows:
• Operation Mode setting: Select the mode of harmonic + unbalance(H
+B) or unbalance + harmonic(B+H). Please refer to Setting Interface,
page 17 section for introductions of the operation mode.
• Unbalance Load Threshold setting: Enter 0%.
EZAPF3160898EN_01 53
Active Harmonic Filter Operation Instructions for Startup/Shutdown and Debugging
3. When there are not only harmonics but also reactive power and unbalance in
the power system.
The settings need to be adjusted as follows:
• Operation Mode setting: Select the mode of harmonic + reactive power
+ unbalance(H+Q+B) or other different combination of the three modes.
Please refer to Setting Interface, page 17 section for introduction of the
operation mode.
• Target Power Factor setting: Enter 1.
• Capacitive Compensation enable: Select enable.
• Unbalance Load Threshold setting: Enter 0%.
4. When the ambient temperature at APF site exceeds the specified ambient
temperature limit.
The settings need to be adjusted in addition to previous settings:
• Temperature Derating setting: Select enable.
5. When APF is applied in high altitude.
The settings need to be adjusted in addition to previous settings:
• Altitude Derating: Enter the corresponding factor according to the
actual altitude. You can also refer to the following table for quick settings.
System Debugging
After the APF module or system is powered on, if it completes parameter setting
and turns on harmonic output of the equipment, APF will automatically monitor the
power grid status and conduct harmonic control. But sometimes it is necessary to
manually adjust and optimize the system parameters on the basis of automatic
compensation to further optimize the harmonic control effect of APF.
Debugging steps:
1. Before debugging, check whether there are alarm items on the screen
interface first, and check whether the data (THDi, etc.) on the measurement
interface are consistent with the actual working condition.
During debugging, it is recommended to use power analyzer for comparison
measurement to facilitate debugging and optimization.
54 EZAPF3160898EN_01
Operation Instructions for Startup/Shutdown and Debugging Active Harmonic Filter
2. Enter the harmonic menu from the measurement interface of the menu
screen, observe the content of each harmonic on the grid side from the
harmonic distribution diagram, and select each harmonic that needs to be
optimized and compensated.
3. Return to the Home screen and enter the Setting interface and select the
System to change the Compensation Mode from Intelligent to Sequential.
4. Click Compensation under the setting interface to enter the harmonic
compensation setting interface.
EZAPF3160898EN_01 55
Active Harmonic Filter Cybersecurity
Cybersecurity
At Schneider Electric, we have always regarded cybersecurity as a key
requirement, and are committed to providing more reliable, stable and safe
products to minimize potential network risks, so as to better protect our customers'
lives, property and the environment.
Cybersecurity aims to protect your system, communication network and
equipment from possible damage, data tampering or confidential information
disclosure. In addition to suggestions for APF in this article, it is strongly
recommended that you follow Schneider Electric's defense-in-depth approach to
achieve cybersecurity, which is described in the system technical specification
How to reduce vulnerability to cyber-attacks . In addition, you can find more useful
resources and up-to-date information on Schneider Electric's Cybersecurity
Support Portal.
WARNING
CHANGE DEFAULT PASSWORD AT FIRST USE
Changing the default password at first use helps prevent unauthorized access
and changes to important data such as operating parameters and configuration
of the device.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Equipment Safety
• Digital signature technology based on public key infrastructure (PKI) is used
to ensure the authenticity and integrity of device firmware and prevent
malicious code injection
• Use verification technology to ensure the integrity of important configuration
and business data stored in the equipment
• Provide password-based access control (see and User Access Permission,
page 30 section ) to ensure that only authorized personnel can access and
change equipment configuration
• After entering wrong password for 3 consecutive times, the equipment will be
locked for 5 minutes, which effectively alleviates the possibility of brute force
attack
• Supports password reset through security questions (see and User Access
Permission, page 30 section). Users need to set the security questions at first
use and keep the answers properly
• Provide keys to ensure that only authorized personnel can have APF cabinet
door keys and access to important interfaces (such as USB, TF) and
components
• The equipment is shipped with the debugging port disabled to prevent
attackers from reading and changing the firmware and configuration
parameters in the equipment
• Strict input verification ensures that only legitimate data from HMI and
Modbus RTU are accepted
Password Management
The password is an important line of defense against network attacks or damage
to the equipment. The default password is as follows:
• Level I (Operator) password: 08080808
56 EZAPF3160898EN_01
Cybersecurity Active Harmonic Filter
Access Control
APF provides the possibility of local access and Modbus RTU based remote
access. You must ensure that only authorized users can access it.
Local Access
It provides various possibilities for attackers to access and control devices locally.
Installs the APF in a secure area and implements and manages access rules for
the secure area. It is recommended that:
• This area remains locked at all times
• The area is equipped with an access control system, and only authorized
personnel can have the keys or access codes
• Communication ports and network cables entering the secure area, as well as
connection ports on communication equipment outside the room are
protected
EZAPF3160898EN_01 57
Active Harmonic Filter Cybersecurity
Firmware Update
When you need to upgrade firmware, please refer to HMI Software Upgrade or
contact Schneider Electric Technical Support Engineers or local agents to help
you complete the upgrade.
Safe Disposal
When the equipment needs to be disposed, please use Factory Reset (see
Setting Interface, page 17 and Setting Interface, page 38 section) and destroy it
through safe channels to ensure that the equipment will not be re deployed to your
operation system or used illegally.
atftp https://www.gnu.org/licenses/gpl.html
bridge-utils https://www.gnu.org/licenses/gpl.html
busybox https://www.gnu.org/licenses/gpl.html
dbus-glib https://www.gnu.org/licenses/gpl.html
glibc https://www.gnu.org/copyleft/lesser.html
gmp https://www.gnu.org/copyleft/lesser.html
iperf https://opensource.org/licenses/NCSA
iproute2 https://www.gnu.org/licenses/gpl.html
iw http://www.isc.org/downloads/software-support-policy/isc-license/
kmod https://www.gnu.org/copyleft/lesser.html
libatomic1 https://www.gnu.org/licenses/gpl.html
libffi https://opensource.org/licenses/MIT
libgpg-error https://www.gnu.org/copyleft/lesser.html
Libiniparser https://opensource.org/licenses/MIT
libnl https://www.gnu.org/copyleft/lesser.html
libsanitizer http://www.linfo.org/bsdlicense.html
58 EZAPF3160898EN_01
Cybersecurity Active Harmonic Filter
libts https://www.gnu.org/licenses/gpl.html
libusb https://www.gnu.org/copyleft/lesser.html
linux_kernel https://www.gnu.org/licenses/gpl.html
linuxconsoletools https://www.gnu.org/licenses/gpl.html
mtd https://www.gnu.org/licenses/gpl.html
netbsd-resolv http://www.linfo.org/bsdlicense.html
openssl https://www.openssl.org/source/license.html
readline https://www.gnu.org/licenses/gpl.html
safestring https://opensource.org/licenses/MIT
snmp https://www.agentpp.com/licenses/SNMP_PP_LICENSE.txt
sqlite3 http://en.wikipedia.org/wiki/Public_domain
uboot https://www.gnu.org/licenses/gpl.html
util-linux https://www.gnu.org/licenses/gpl.html
zlib http://zlib.net/zlib_license.html
EZAPF3160898EN_01 59
Active Harmonic Filter EasyLogic™ APF HMI Firmware Upgrade Instruction
• Upgrade Process
(1) Turn Off EasyLogic™ APF.
60 EZAPF3160898EN_01
EasyLogic™ APF HMI Firmware Upgrade Instruction Active Harmonic Filter
(3) Insert USB Disk into the slot on the left side of HMI (as shown below).
You will hear a few beep sound once upgrade is started. Then HMI will
be restarted and upgrade is completed with a few beep sound.
EZAPF3160898EN_01 61
Active Harmonic Filter EasyLogic™ APF HMI Firmware Upgrade Instruction
(2) SD card capacity should be 2G - 8G, and file system of SD card must
be FAT32 format.
• Upgrade Process
(1) Turn Off EasyLogic™ APF.
62 EZAPF3160898EN_01
EasyLogic™ APF HMI Firmware Upgrade Instruction Active Harmonic Filter
(3) Insert SD card into the slot on the left side of HMI (as shown below).
You will hear a click sound once SD card is inserted successfully.
(4) After SD card is inserted, blue screen will appear for a while, followed
by all the latest HMI interfaces flashing one by one. It will take 1-2 mins to
complete this process.
(5) Once completed, you will see the startup interface (as shown below).
(6) Remove SD card and restart HMI (switch off and on APF power) to
complete the upgrade.
3. Power Off, then Power on the Circuit breaker of EasyLogic™ APF
EZAPF3160898EN_01 63
Active Harmonic Filter EasyLogic™ APF HMI Firmware Upgrade Instruction
64 EZAPF3160898EN_01
Troubleshooting Active Harmonic Filter
Troubleshooting
When the Schneider Electric APF encounters a fault, the red fault light on the
equipment housing will light up, and the HMI will also display the fault information
and give a buzzer alarm.
In general, in case of minor fault, the equipment will automatically stop harmonic
output and automatically resume operation when the equipment is in normal state.
In case of serious fault, the equipment will not restart automatically after output
stops and it needs to be manually restarted after troubleshooting. In case of
emergency, it is necessary to press EPO to forcibly stop harmonic output of the
equipment.
DANGER
THERE IS A DANGER OF UNEXPECTED OPERATION OF EQUIPMENT
• Pressing the EPO emergency stop button can only stop harmonic output of
the equipment and cannot completely power off the equipment.
• Appropriate sensing devices with rated voltages should always be used to
confirm that the power is off.
Failure to follow these instructions will result in death or serious injury.
To completely power off the equipment, disconnect the front circuit breaker of the
APF line.
The common fault information and solution of Schneider Electric APF are as
follows for reference.
EZAPF3160898EN_01 65
Active Harmonic Filter Troubleshooting
The current flowing through any IGBT exceeds Check whether IGBT, Hall, bus capacitor, inverter
1 Inverter short circuit inductor and input relay are short circuited
the set value
One or more fans are blocked, and the fan The fan needs to be replaced. Please contact
3 Fan Fault module is disconnected or damaged Schneider Electric Product Engineer
CT Ratio Setting
Error (4.3 inch) If the CT ratio is too small, the current transformer
The actual load current is greater than the rated
5 needs to be replaced and this needs to be 1.5 to 2
Transformer reverse detection current of CT
times the maximum load
fault (7 inch)
10 Capacity Read Error Native capacity setting error Contact Schneider Electric Product Engineer
3. The internal fuse of the module is damaged 3. For module failure, the equipment code and
software version shall be recorded and timely
reported to Schneider Electric customer
service
66 EZAPF3160898EN_01
Troubleshooting Active Harmonic Filter
EZAPF3160898EN_01 67
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison2022
France
+ 33 (0) 1 41 29 70 00
www.se.com